IOM-T-289

Installation, Operation and Maintenance Manual

Smart Boiler Control 289

Please read carefully before proceeding with  

installation. Your failure to follow any attached  

instructions or operating parameters may lead to the 

product’s failure. 
Keep this Manual for future reference.

Summary of Contents for tekmar 289

Page 1: ...enance Manual Smart Boiler Control 289 Please read carefully before proceeding with installation Your failure to follow any attached instructions or operating parameters may lead to the product s fail...

Page 2: ...ler Hours or Cycles Screen 16 Menu Screen 16 Navigation 16 Menus 17 Home Screen 17 Settings 1 of 5 18 Settings 2 of 5 19 Settings 3 of 5 20 Settings 4 of 5 21 Settings 5 of 5 22 Schedule Menu 23 Notif...

Page 3: ...l alone or with a signal word on your equipment or in this Manual be alert to the potential for death or serious personal injury This pictorial alerts you to electricity electrocution and shock hazard...

Page 4: ...Industry Canada license exempt RSS standard s Operation is subject to the following two conditions 1 this device may not cause harmful interference and 2 this device must accept any interference recei...

Page 5: ...nished floor Locate the control near pumps and or zone valves if possible Provide a solid backing to mount the enclosure to For example plywood studs etc Use the conduit knockouts provided on the uppe...

Page 6: ...NMB 3 A Class 2 Circuits Input Power 115 V ac 10 60 Hz 4 W Relays 230 V ac 5 A 1 3 hp Calls 24 V ac or Short Operating Temperature 32 F to 122 F 0 C to 50 C Use Copper Conductors Only Wi Fi 802 11b g...

Page 7: ...gned and assembled in Canada The Pressure Sensor 089 must be installed downstream of a 1 4 steam gauge siphon pigtail to prevent premature failure Outdoor Sensor 070 Terminals 4 5 The 070 can be mount...

Page 8: ...er temperature and the time the sensor measures the temperature change This delay increases con siderably when mild steel black iron pipe is used In general it is recommended that a temperature well b...

Page 9: ...43 4 665 180 82 1 172 25 32 196 358 45 7 22 763 115 46 4 184 185 85 1 073 20 29 165 180 50 10 19 900 120 49 3 760 190 88 983 15 26 139 403 55 13 17 436 125 52 3 383 195 91 903 10 23 118 018 60 16 15 3...

Page 10: ...ass 2 Circuits Input Power 115 V ac 10 60 Hz 4 W Relays 230 V ac 5 A 1 3 hp Calls 24 V ac or Short Operating Temperature 32 F to 122 F 0 C to 50 C Use Copper Conductors Only Wi Fi 802 11b g n 2 4GHz 1...

Page 11: ...und Pour r duire les risques d lectrocution choc ne pas raccorder un circuit fonctionnant plus de 150 V la terre L H2065A Smart Steam Control 289 For product literature Pour la documentation du produi...

Page 12: ...rt for assistance Lock Screen When first powered on the tekmar logo appears followed by the lock screen By default the control is not locked and does not require a passcode Press Tap to Unlock and ent...

Page 13: ...ONSITE Blue indicates connection to the Watts OnSite cloud service SCHEDULE Blue indicates the programmable schedule is on SUN When displayed it indicates the schedule is in the occupied period MOON W...

Page 14: ...used to calculate the heat on time of the steam boiler using outdoor air reset The optional condensate return temperature is used to determine when steam is established at the furthest radiator The o...

Page 15: ...el screen The circle in blue indicates that the boiler is firing An empty circle indicates off The boiler run time hours is displayed Press the rotate circle button to zero the hours The boiler on off...

Page 16: ...el Menu Screen Navigation BACK Go back a level without saving HOME Go to Home screen without saving SAVE Saves the new setting value CLEAR Clears the boiler hours or cycles to 0 SKIP Skip step in Setu...

Page 17: ...1 5 to 38 0 C The desired room temperature when an indoor sensor is installed BOOST Off or On Dot is green when Boost is active EARLY START Off or On Dot is green when Early Start is active SMART SET...

Page 18: ...or On Default On Automatic synchronizes the time with the Internet TIME ZONE North American Time Zones Default Eastern Select from Newfoundland Atlantic Eastern Central Mountain Pacific Alaska Hawaii...

Page 19: ...255 255 Default 192 168 1 1 Set the router or gateway IP address Available when IP Configuration is Static DNS 1 0 0 0 0 to 255 255 255 255 Default 0 0 0 0 Set the control s primary DNS 0 0 0 0 uses...

Page 20: ...lt Off Select if the control should shut down the central heating based on the outdoor air temperature WARM WEATHER SHUT DOWN OCCUPIED 35 to 100 F 2 0 to 38 0 C Default 70 F 15 5 C Set the outdoor air...

Page 21: ...oor sensor and schedule BOOST Off or On Default Off Select the extra run time after the unoccupied period ends to recover the temperature of the building Requires a schedule and an indoor sensor is no...

Page 22: ...LERT ENABLE Off or On Default Off Select if an alert is triggered if the indoor temperature exceeds the threshold Requires an indoor sensor to be installed INDOOR TEMPERATURE HOT ALERT 32 to 100 F 0 0...

Page 23: ...t the occupied 1 time Select SKIP to ignore the occupied 1 time event UNOCCUPIED 1 TIME 12 00 am to 12 50 pm 0 00 to 23 50 Default 8 00 am 8 00 Set the unoccupied 1 time Select SKIP to ignore the unoc...

Page 24: ...es the control into a standby state and the boilers and pumps are not operated COMBUSTION AIR DAMPER Off or On Default Off Select to turn on the combustion air damper Available in Hand override BOILER...

Page 25: ...sts all details about the control This information may be required when contacting tekmar for support Help Menu Scan the QR code with your mobile phone to be directed to the product website to find sp...

Page 26: ...return sensor on the return pipe of the furthest radiator Alternatively the condensate return sensor may be installed in the boiler room It is important that the Universal Sensor 071 be strapped to th...

Page 27: ...ng outdoor air temperature As the outdoor temperature gets colder the heat loss of the building increases at a proportional rate This relationship between heat loss and colder outdoor temperatures is...

Page 28: ...allations When installed the control automatically adjusts the heating curve up or down to so that the ambient air temperature reaches the Room Target If the ambient temperature exceeds the Room Targe...

Page 29: ...ablishing Steam warm up period Establishing Steam warm up period Cool Down Period Cool Down Period Steam Established Setting on on off off Boiler On Boiler Operation 220 F 210 F 200 F 190 F 180 F 170...

Page 30: ...able schedule is in use When a programmable schedule is used to lower the build ing temperature at night there is a time delay to increase the building temperature from the Unoccupied to the Occupied...

Page 31: ...ime of the boiler from when the boiler enable contact is closed until when a flame is established The Fire Delay can be found in the boiler manual or can be timed with a watch Boiler High Output The c...

Page 32: ...ace the Outdoor Sensor 070 Once the fault is corrected the error clears automatically tekmarNet Outdoor Sensor Error The control has not received an outdoor temperature report from the tekmarNet netwo...

Page 33: ...0 5 to 4 5 V dc depending on the system pressure If either voltage reading is abnormal then replace the Pressure Sensor 089 Once the fault is corrected the error clears automatically Pressure Sensor...

Page 34: ...If the hardware fault reoccurs the control may require replacement Please contact technical support for assistance Internet Unavailable Error The control is unable to communicate to the Watts cloud th...

Page 35: ..._ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _...

Page 36: ...ility for fundamental breach of contract The pass through Limited Warranty applies only to those defective Products returned to tekmar during the warranty period This Limited Warranty does not cover t...