Testing and Troubleshooting

An electrical multimeter capable of measuring between 0 to 5 volts DC is required.
Using the electrical meter probes, measure the voltage between the black (power common) and red (reference voltage) 

wires. The expected voltage is 5.0 V(dc).
Using the electrical meter probes, measure the voltage between the black (power common) and green (ratiometric  

signal input) wires. The voltage signal should be between 0.5 to 4.5 V(dc). Using the lookup table below, compare the  

measured voltage to a mechanical pressure gauge mounted on the hydronic system. The signal should be accurate 

within 1% over the full scale.

Pressure vs Voltage Table

Call customer service if you need assistance with technical details.

Pressure (psi)

Pressure (kPa)

Ratiometric Voltage (Vdc)

0

0

0.50

0.5

3

0.63

1.0

7

0.77

1.5

10

0.90

2.0

14

1.03

2.5

17

1.17

3.0

21

1.30

4.0

28

1.57

5.0

35

1.83

6.0

41

2.10

7.0

48

2.37

8.0

55

2.63

9.0

62

2.90

10.0

69

3.17

11.0

76

3.43

12.0

83

3.70

13.0

90

3.97

14.0

97

4.23

15.0

103

4.50

Summary of Contents for tekmar 089

Page 1: ...re of a hydronic system between 0 to 15 psi 0 to 089 kPa The sensor bulb is designed to install into a tee using 1 8 27 NPT threads and includes a 10 foot 3 m long cable Please read carefully before p...

Page 2: ...ant Safety Information 3 Installation 4 Check the Contents 4 Preparation 4 Installation Location 4 Step 1 Rough In Wiring 4 Step 2 Mounting 4 Step 3 Wiring 4 Testing and Troubleshooting 5 Technical Da...

Page 3: ...sult in death or serious injury This symbol identifies hazards which if not avoided could result in minor or moderate injury This symbol identifies practices actions or failure to act which could resu...

Page 4: ...h In Wiring The sensor cable is 10 feet 3 m in length This can be extended up to 100 feet 30 m using 3 conductor 18 AWG solid or stranded cable The cable is color coded with black red and green wire j...

Page 5: ...ires The voltage signal should be between 0 5 to 4 5 V dc Using the lookup table below compare the measured voltage to a mechanical pressure gauge mounted on the hydronic system The signal should be a...

Page 6: ..._ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _...

Page 7: ...Pa Operating Temperature Range 40 to 257 F 40 to 125 C Burst Pressure 450 psi Acceptable Fluid Media Water glycol solution steam Dimensions 0 87 x 2 3 L 22 0 mm x 58 5 mm L cable 10 feet 3 0 m Threads...

Page 8: ...arranty with its customers Any representations or warranties about the Products made by Purchaser to its customers which are different from or in excess of the tekmar Limited Warranty are the Purchase...

Reviews: