4
IOM-T-089 2335
© 2023 tekmar
Installation
Check the Contents
Check the contents of this package. If any of the contents listed are missing or damaged, please refer to the Limited
Warranty and Product Return Procedure on the back of this brochure and contact your wholesaler or tekmar
®
sales
representative for assistance. Type 089 includes:
• One pressure sensor bulb
• One 10 foot electrical cable with connector
• One Installation and Operation Manual IOM-T-089
Preparation
Tools Required
• 22 mm or Crescent wrench
• Flathead screwdriver
Materials Required
• Pipe joint compound or PTFE tape
• 1/4" steam gauge siphon (pigtail)
• 1/4" to
1
⁄
8
" FIPS reducing coupler
Installation Location
• The Pressure Sensor 089 must be installed downsteam
of a 1/4" steam gauge siphon (pigtail) to prevent premature
failure.
• Keep dry. Avoid potential leakage onto the sensor.
Step 1 – Rough In Wiring
• The sensor cable is 10 feet (3 m) in length. This can
be extended up to 100 feet (30 m) using 3-conductor
18 AWG solid or stranded cable. The cable is color
coded with black, red and green wire jackets.
• Strip wire to
3
⁄
8
" (10 mm) for all terminal connections.
As with any electrical product, care should be taken to
guard against the potential risk of fire, electric shock,
and injury to persons.
Step 2 – Mounting
• Apply pipe joint compound or PTFE tape to the
sensor threads.
• Thread sensor into the tee. Tighten with wrench.
• Connect the cable to the sensor using the Metri-Pack
electrical connector.
• Should the cable need to be disconnected from the
sensor bulb, use a flathead screwdriver to release the
electrical connector spring-loaded clip.
Step 3 – Wiring
Conduit Connector
• Pull wires through a conduit as required by electrical
codes.
Terminating
• Terminate the black conductor to the control’s
power common.
• Terminate the red conductor to the control’s 5 V(dc)
reference voltage.
• Terminate the green conductor to the control’s ratiometric
signal input.