background image

IOM-T-089

Installation, Operation and Maintenance

Pressure Sensor 089

Introduction

•  The Pressure Sensor 089 provides a ratiometric signal to a  

controller to measure the pressure of a hydronic system between  

0 to 15 psi (0 to 089 kPa). The sensor bulb is designed to 

install into a tee using 

1

8

"-27 NPT threads and includes a  

10 foot (3 m) long cable.

Please read carefully before proceeding with  

installation. Your failure to follow any attached  

instructions or operating parameters may lead to  

the product’s failure.  

Keep this Manual for future reference.

Summary of Contents for tekmar 089

Page 1: ...re of a hydronic system between 0 to 15 psi 0 to 089 kPa The sensor bulb is designed to install into a tee using 1 8 27 NPT threads and includes a 10 foot 3 m long cable Please read carefully before p...

Page 2: ...ant Safety Information 3 Installation 4 Check the Contents 4 Preparation 4 Installation Location 4 Step 1 Rough In Wiring 4 Step 2 Mounting 4 Step 3 Wiring 4 Testing and Troubleshooting 5 Technical Da...

Page 3: ...sult in death or serious injury This symbol identifies hazards which if not avoided could result in minor or moderate injury This symbol identifies practices actions or failure to act which could resu...

Page 4: ...h In Wiring The sensor cable is 10 feet 3 m in length This can be extended up to 100 feet 30 m using 3 conductor 18 AWG solid or stranded cable The cable is color coded with black red and green wire j...

Page 5: ...ires The voltage signal should be between 0 5 to 4 5 V dc Using the lookup table below compare the measured voltage to a mechanical pressure gauge mounted on the hydronic system The signal should be a...

Page 6: ..._ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _...

Page 7: ...Pa Operating Temperature Range 40 to 257 F 40 to 125 C Burst Pressure 450 psi Acceptable Fluid Media Water glycol solution steam Dimensions 0 87 x 2 3 L 22 0 mm x 58 5 mm L cable 10 feet 3 0 m Threads...

Page 8: ...arranty with its customers Any representations or warranties about the Products made by Purchaser to its customers which are different from or in excess of the tekmar Limited Warranty are the Purchase...