Installation – Indoor Sensor 077
Wiring the Indoor Sensor
Run two conductor 18 AWG or similar wire between the Indoor Sensor and the
terminals on the tekmar control. Insert the wires through the hole provided in the
back of the indoor sensor enclosure and connect them to the indoor sensor
terminal block. Do not run the wires parallel to telephone or power lines. If the
indoor sensor wires are located in an area with strong sources of electromagnetic
noise, shielded cable or twisted pair should be used or the wires can be run in a
grounded metal conduit. If using shielded cable, one end of the shield wire should
be connected to the Com-Sen terminals on the control and the other end should
remain free. The shield must not be connected to earth ground. Follow the sensor
testing instructions in this brochure and connect the wires to the control.
Installing the Sensor Front Cover
Place any extra sensor wire into the electrical box. Secure the front cover of the
Indoor Sensor 077 to the electrical box. Ensure the wiring is not pinched or crushed
when installing the front plate.