Power (green)
Heating (amber)
Operation
Overview
Mounting the Control
1. Make sure the power supply to the circuit is turned off at the circuit breaker.
2. Carefully press the wires back into the electrical box.
• DO NOT use the control to push wires in, as this may cause connections to
loosen and possible failure.
3. Use the Mounting Screws provided to secure to the electrical box and tighten
by hand.
• DO NOT over-tighten the screws causing the plastic to distort, as this may
cause improper function of the control.
4. Press the Front Module onto the Power Module. Make sure both tabs at the
top are completely engaged.
• DO NOT install the Front Module with power applied on the Power Module,
as this may cause improper function of the control.
5. Secure the screw at the bottom and replace the Screw Cover.
• DO NOT over-tighten the screw causing it to strip. Turn it until snug.
On/Off and Reset
Pressing will turn the thermostat on or off. This also resets the thermostat to
clear an error or GFCI fault. See “GFCI Testing” and “Troubleshooting”.
Heating
The Heating light will show amber when the control is sending power to the
floor heating system. There may be a delay of up to 3 minutes from any changes
at the thermostat.
GFCI Testing
The GFCI (Ground Fault Circuit Interrupter) in this control must be tested when
installation is finished and once each month.
1. Make sure the control shows it is Heating. This may require temporarily
increasing the Setpoint temperature on the Thermostat.
2. Press the
GFCI TEST
button. GFCI TRIP should be indicated on the control by
a constant red light. There will also be a click sound, indicating power has
been removed from the floor heating system. If either of these indications
fail, turn off the control and replace it. Do not continue to use.
3. To reset the GFCI TRIP, press the button off and back on.
Figure 2