background image

To prevent the risk of personal injury and/or death, make  sure 

power is not applied to the product until it is fully installed 

and ready for final testing. All work must be done with power 

turned off to the circuit being worked on.

House Wiring

Pull power supply wiring to the control location.  Consider the following:
•  Leave about 6 to 8 inches (15 to 20 cm) of wire for connections later.
•  This wiring should be size 12 or 14 AWG following appropriate local code 

requirements.

•  A qualified person should run a dedicated circuit from the main circuit 

breaker panel to the control location. If a dedicated circuit is not possible, it 

is acceptable to tap into an existing circuit. However, there must be enough 

capacity to handle the load (amps) of the floor heating system being installed 

and any possible appliance, such as a hair dryer or vacuum cleaner.

•  Avoid circuits that have ballasted lighting, motors, exhaust fans, or hot tub 

pumps due to possible interference.

•  The circuit breaker should be rated 20 amps for total circuit loads up to 15 amps. 

A 15 amp circuit breaker may be used for total circuit loads up to 12 amps.

•  A GFCI (ground-fault circuit interrupter) or AFCI (arc-fault circuit interrupter) 

type circuit breaker may be used if desired, but is not necessary.

Communication Wiring

Pull 18 AWG to 24 AWG 2-conductor shielded wire through the wall from the 

SunStat Relay II location to this control location. This wire may be up to 100 

feet (30 m) in length. Strip the wire ends 1/8" to 3/16" (3 mm to 4.5 mm) long. 

If the ends are stripped longer than this they may short-circuit.

Power Leads from Heating Mat or Cable

Pull the power lead wires from the floor heating system into the control location. 

Excess power lead wire may be cut off, but leave about 6 to 8 inches (15 to 20 

cm) of wire for connections.

Screw 

Cover

Cover Screw

Front 

Module

Load 1

Line 2

Load 2

BUS A & B 

Terminals

Power 

Module

Line 1

Wiring Connections 

(see Figure 1 and 2)

Connect the wires as shown in the diagram. Consider the following:

•  Gently tug on the wires to make sure they are secure.  For added security, 

overwrap the Wire Nut connec  ons with electrical tape.

•  If the electrical box is metal, a short length of wire must be secured to the 

electrical box from the ground connec  on.

• When connec  ng the Communica  on Wires to the Bus A and B terminals, 

observe polarity.  Make sure the wire in the Bus A terminal is connected to 

the thermostat Bus A terminal.

Figure 1

Wiring

Removing the Relay Front Module

1. Remove the Screw Cover at the bottom and loosen the screw.
2. Lift the Front Module away from the Power Module.

Reviews: