background image

3

•  System must be installed in a vertical, upright and level position. 
•  Do not use with water that is microbiologically unsafe or of  

unknown water quality .

Installation Precautions

•  Do not install system on line pressure above the rated pressure as 

noted in System Specifications above .

•  Do not install the system on a hot water line. Failure to limit the 

water temperature to 100°F (38

°

C) can result in housing failure and 

property damage .

•  Do not connect the system backwards with the feed water line 

connected to the outlet . 

•  Do not use liquid pipe thread compounds for threaded  

connections . Use Teflon

®

 tape only .

•  Do not solder plumbing connections that are attached to the  

housings or inlet/outlet fittings . System damage may occur due to 

high temperature .

•  Do not allow the system to freeze. Turn off water supply and drain 

the system if temperature falls below 32°F (0

°

C) . 

•  Do not install system in direct sunlight or where the system will be 

exposed to harsh chemicals or may be subjected to being hit by 

moving equipment, carts, mops, or any other item that may cause 

damage . 

•  Allow 3" (76mm) minimum clearance under the housings for filter 

replacement . 

•  If water hammer is evident, install water hammer arrestors before 

the system . 

•  Do not over tighten fitting connections. 
•  Always back up valves and fittings with a wrench when installing 

fittings to avoid over tightening or loosening existing fittings . 

•  Do not install the unit behind equipment where it may be difficult to 

access the system for future filter replacements . 

Position the system in a suitable location . The direction of flow 

through the system is left to right . Keep this in mind when determin-

ing installation locations . Do not mount the system near any source 

of heat . Also do not mount this system over anything that may be 

adversely affected by water .  

Operation

With sufficient pressure, operation of this system is completely auto-

matic . Dependable operation involves only monitoring system pres-

sure differential, periodic filter changes, and service documentation .   

Installation

NOTICE

 

There is some light field assembly required for this system. 

Before beginning the installation of this system, please make 

sure all components are present. Compare the contents of this 

box to the system drawings located at the end of this manual. 

As illustrated by the drawings, not all systems utilize pressure 

gauges. These drawings will be referenced in the installation 

instruction steps.

  1 .   Turn off all equipment to be fed by the system, locate the water 

supply shutoff valve and turn it off .

2 .

  

Apply Teflon tape to the threads of the inlet and outlet valve assemblies 

and pressure gauges (if supplied for your model) . 

DO NOT USE PASTE 

TYPE THREAD SEALANT.

 Thread the inlet and outlet valve assemblies 

into the inlet and outlet ports of the system as shown on the system 

drawings in this manual . Install the pressure gauges, if applicable, into 

the gauge ports as indicated by the system drawings in this manual . 

DO NOT OVER TIGHTEN THESE FITTINGS INTO THE FILTER HEADS. 

When installing fittings onto this system, back any existing receiving fittings 

with a wrench to prevent fitting movement . Use a wrench to tighten gauges 

into their connection ports . Do not twist on gauge case .

3 .  Install the filters into the filter manifold . Make sure all plastic wrapping 

and protective plastic caps have been removed from the filters prior to 

their installation . Insert the prefilter into its blue canister . Make sure the 

blue canister's oring is properly inserted into its oring groove . Thread the 

housing onto the head with standard clockwise rotation (when viewed 

from below) . Hand tighten the blue housing (Not all systems will have 

a blue prefilter . See the system drawings in this manual for proper filter 

placement) . Then install the QT style filter cartridges . To install these 

filters, push them into the heads and give them a quarter twist (clockwise 

when viewed from below) . When the filter is completely inserted, the 

cartridge label will be front centered . 

  4 .  Anchor the system on a wall stud or suitable mounting material

spanning wall studs . System must be vertical, upright and  

level . The mounting hardware used must be selected and 

installed so that the system is firmly pressed against the 

mounting surface . The system mounting hardware must keep 

the system from moving during routine service and operation .    

  5 .   Run a suitable line from the tap water source to the inlet ball 

valve on the left side of the system . Brace the inlet ball valve on 

the system with a wrench when connecting the feed water line . 

 

    DO NOT OVERTIGHTEN CONNECTION FITTING INTO  

 

    BALL VALVE.

 

 6 .   Select the appropriate size tubing for the equipment being fed, 

and connect it to the outlet ball valve of the system .  

NOTICE

 

  

DO NOT OVERTIGHTEN CONNECTION FITTING INTO BALL  

   VALVE.

  7 .   Install the ¼" (8mm) tubing into the Quick-Connect fitting on the 

outlet of the system and hold it over a drain . Open the 

1

4

" (8mm)

drain valve .

  8 .   Once all inlet and outlet piping has been completed, check and 

make sure all filter housing(s) are tight, slowly open the inlet valve 

and allow all air to purge from the system through the 1/4"  

tubing . Slowly close the 

1

4

" (8mm) drain valve, allow the system 

to reach operating pressure, and check for leaks .

  9 .   If no leaks are present, open the 

1

4

" (8mm) drain line again and 

allow it to run to drain for 5 minutes to flush the system . Then 

close the valve . 

 10 .   Open the outlet water valve and check for leaks .
 11 .   Record the start up date and pressure gauge values in system 

maintenance log .

NOTICE

 

Overtightening components can damage the system causing 

water damage and/or system failure.

Maintenance 

Routine maintenance of this system involves periodic filter changes .
Filter cartridges should be changed at end of filter life, due to lack of 

filtering performance, or whenever a 15 psi pressure drop or greater 

is experienced during normal operation, whichever comes first . 

Filter Cartridge Replacement Procedure

WARNING

!

Determine whether all equipment connected to the system must 

be turned off prior to shutting off water supply from filters.

  1 .   If required, turn off downstream equipment .
  2 .   Turn OFF water to the system by closing the inlet and outlet ball 

valves .

  3 .   Open the ¼" drain valve on the outlet of the system to relieve 

pressure in the housings . 

  4 .   Remove all filters . The blue prefilter housing unscrews to the left when 

viewed from underneath . It has a standard right hand thread . The QT 

style filters are removed by rotating them 1/4 turn to the left and then 

gently pulling down . 

NOTICE

NOTICE

Summary of Contents for QTCBMX-1S-1M

Page 1: ...e Max Models QTCBMX 1L 5M QTCBMX 2L 5M and QTCBMX 3L 5M are tested and certified by WQA against NSF ANSI Standard 42 for Material Safety and Structural Integrity and NSF ANSI Standard 372 for lead free compliance Read this Manual BEFORE using this equipment Failure to read and follow all safety and use information can result in death serious personal injury property damage or damage to the equipme...

Page 2: ...icron Carbon Block with Phosphate Scale Control QTCBMX 2L 1M HSR L SED 5M 6 Months 20 5 Micron Sediment Pre Filter QTCM20 6 Months 20 QT 0 5 Micron Carbon Block with Phosphate Scale Control QTCBMX 3L 1M HSR L SED 5M 6 Months 20 5 Micron Sediment Pre Filter QTCM20 6 Months 20 QT 0 5 Micron Carbon Block with Phosphate Scale Control 2 QTCBMX 4L 1M HSR L SED 5M 6 Months 20 5 Micron Sediment Pre Filter...

Page 3: ...n gauges into their connection ports Do not twist on gauge case 3 Install the filters into the filter manifold Make sure all plastic wrapping and protective plastic caps have been removed from the filters prior to their installation Insert the prefilter into its blue canister Make sure the blue canister s oring is properly inserted into its oring groove Thread the housing onto the head with standa...

Page 4: ...t valve to the full open position Allow water to flush to drain for 5 minutes 9 Slowly close the drain valve and check the system for leaks 10 Slowly open the outlet valve to restore water flow to downstream equipment 11 Record filter change date in system maintenance log Teflon is a registered trademark of E I DuPont de Nemours Company Replacement Parts Description Ordering Code Filter Head 3 8 T...

Page 5: ...5 QTCBMX 2S 1M QTCBMX 2L 1M QTCBMX 3S 1M QTCBMX 3L 1M QTCBMX 2L 5M 25 51 14 69 5 56 25 70 15 73 5 56 26 08 15 73 5 56 QTCBMX 3L 5M 25 51 19 44 5 56 25 70 20 30 5 56 26 08 20 30 5 56 ...

Page 6: ...QTCBMX 4S 1M QTCBMX 4L 1M QTCBMX 5L 1M 25 70 24 73 5 56 26 08 24 73 5 56 26 08 29 23 5 56 Allow 3 76mm of clearance at bottom of system for removal of filter bowls for filter cartridge replacement NOTICE ...

Page 7: ...7 Notes ...

Page 8: ...any incidental special or consequential damages including without limitation lost profits or the cost of repairing or replacing other property which is damaged if this product does not work properly other costs resulting from labor charges delays vandalism negligence fouling caused by foreign material damage from adverse water conditions chemical or any other circumstances over which the Company h...

Reviews: