16 PWSRTA Twin Alternating Series Softeners
Step 14S –
Set Relay Actuation Time or Gallons using
or
. The choices are:
• Relay Actuation Time: After the start of a regeneration the amount of time that should pass prior to acti-
vating the relay. The start of regeneration is defined as the first backwash cycle, Dn brine cycle or UP brine
cycle whichever comes first. Ranges from 1 second to 200 minutes.
• Relay Actuation Gallons: Relay activates after a set number of gallons has passed through the meter.
Ranges from 1 to 200 gallons.
Press NEXT to go to Step 15S. Press REGEN to return to previous step.
Step 15S –
Set Relay Deactivate Time using
or
.
• If Set Time on is selected in Step 13S the relay will deactivate after the time set has expired. Ranges from
1 second to 200 minutes.
• If Set Gallons Softening on or Set Gallons Softening Regen on is selected in Step 13S the relay will deac-
tivate after the time set has expired or after the meter stops registering flow, whichever comes first. Ranges
from 1 second to 20 minutes.
Press NEXT to exit OEM Softener System Setup. Press REGEN to return to previous step.
Step 14S
Step 15S
EXIT OEM SOFTENER SYSTEM SETUP