background image

2

!

 

Notice to Installer

•   Do not discard this manual after installation.  This manual 

contains important operation, maintenance and precautionary 

information.  Please present this manual to user/operator/

owner after installation.

•   It is strongly encouraged that you read this manual before 

installing system to ensure the best possible installation.

•   Installation must conform to all local and state plumbing codes 

and regulations.

•   Connect system to cold water supply only. Water temperature 

cannot exceed 100°F/28°C.

  •  System 

must be

 installed in a vertical, upright and level 

position.

  •  OneFlow

®

 systems 

must not

 be used in conjunction with 

polyphosphate or any other scale inhibitor.

•   Do not use with water that is microbiologically unsafe or of 

unknown quality without adequate disinfection before or after 

the system.

•   Notice to user/operator/owner: Please retain this manual for 

future reference for parts, maintenance or troubleshooting.

•   It is recommended that all personnel responsible for operation 

and maintenance of this product read the precautions, opera-

tion and maintenance sections of this manual.

 

         Installation Precautions!

•   Do 

NOT

 install system on line pressure above 125psi.

•    Do 

NOT

 install system on HOT water line. Failure to limit line 

temperature to 100°F may result in housing failure and damage.

•   Do 

NOT

 install the system backwards with the feed water line 

connected to the outlet.

•   Do 

NOT

 use liquid pipe compounds for fitting connections.  

USE two to three wraps of Teflon

®

 tape.

•   Do 

NOT

 solder plumbing connections attached to filter housing 

or inlet valve.  Inlet valve and filter housing will be damaged by 

high temperature.

•   Do 

NOT

 allow system to freeze. Turn off water supply to housing 

and drain housing if temperature falls below 32°F.

•   Do 

NOT

 install system in direct sunlight or where system is 

exposed to harsh chemicals or may be subjected to being 

struck by moving equipment, carts, mops or any other item 

that may cause damage.

• 

 ALLOW

 a minimum of 3" under the housing to allow for filter 

replacement.

• 

 IF

 water hammer is evident, install water hammer arrestors 

before the OneFlow

®

 unit.  

•   Do 

NOT

 overtighten fitting connections into inlet valve or 

housing outlet.  

•   Always back-up valves and fittings with a wrench when install-

ing a fitting to avoid turning the valve.

•   Do 

NOT

 install the unit behind equipment where it may be dif-

ficult to access the system for filter replacement.

Position the OneFlow

®

 unit in a suitable location. The direction of 

flow through the OneFlow

®

 unit is always left to right; keep this in 

mind when determining installation location.  Do NOT mount the 

OneFlow

®

 system near any source of heat.  Also, do not mount 

the system above any device or area that would be adversely 

affected by water. 

Installation 

1.   Turn off all equipment to be fed by the OneFlow

®

 System, 

locate water supply cut-off valve and turn OFF

2.   Determine if water line has an existing water treatment system. 

If so, examine system for use of polyphospate or other scale 

inhibitors. OneFlow

®

 will not be effective if used in conjunction 

with other scale inhibitors. Remove the scale inhibitors from the 

water line or discontinue installation.

3.   Install a 

1

/

2

" full-flow ball valve on the water supply side that 

will feed the water system.

4.   Anchor the OneFlow

®

 system on a wall stud or suitable mount-

ing material spanning wall studs. System must be vertical, 

upright and level.

5.   Run a suitable line from the 

1

/

2

" full-flow ball valve at the tap 

water source to the inlet ball valve on the left side of the 

OneFlow

®

 system.  Use 2-3 wraps of Teflon

®

 tape and brace 

the inlet ball valve on the system with a wrench when con-

necting the feed water line. 

NOTE:

 DO NOT OVERTIGHTEN 

CONNECTION FITTING INTO BALL VALVE.

6.   Select the appropriate size tubing for the equipment being 

fed and connect it to the outlet of the OneFlow

®

 System. 

NOTE: 

DO NOT connect the tubing to the equipment at this 

time. Prior to making connection to the equipment, this line 

will be used to facilitate flushing the system. As an option, a 

drain valve in a tee on the outlet side of the OneFlow

®

 sys-

tem could be provided in the line to facilitate flushing when 

changing filters. 

7.   With OneFlow

®

 inlet valve closed, slowly open the 

1

/

2

" full-flow 

ball valve at the tap water source. Check for leaks.

8.   If a drain valve was not installed on the outlet side of the 

system, hold the tubing that will connect to equipment in 

a clean bucket or over sink or drain. Open the system inlet 

feed valve and allow water to flush through system for 2 

minutes at the specified system flow rate to allow air and 

any carbon fines to escape.  

NOTE:

 NO ACTIVATION IS 

REQUIRED FOR THE OneFlow

®

 SYSTEM TO PERFORM 

PROPERLY. FLUSHING IS RECOMMENDED TO ALLOW AIR 

TO ESCAPE THE SYSTEM AND REMOVE ANY CARBON 

FINES PRIOR TO CONNECTING TO EQUIPMENT.

9.   Make certain that the end of the tubing to be connected to 

the equipment is clean and sanitary. 

10.  Connect tubing to equipment. Open all water supply valves 

and check for leaks.

11.   If no leaks, turn on equipment and check for normal operation.
12.  Attach the Service Log to the installed OneFlow

®

 system and 

fill in install date.

i

!

Teflon

® 

is a registered trademark of the E.I. Dupont de Nemours & Company.

Summary of Contents for OneFlow OF220-2

Page 1: ...llation and routine maintenance you will have years of trouble free operation Please refer to this manual when performing routine filter chang es The instructions make periodic maintenance quick and easy and ensure you will receive maximum benefit from your system System Specifications Maximum Pressure 125psi 8 6 bar Maximum Temperature 100 F 38 C Min 35 F 2 C Inlet Outlet Connections 1 2 FNPT Ser...

Page 2: ...s always left to right keep this in mind when determining installation location Do NOT mount the OneFlow system near any source of heat Also do not mount the system above any device or area that would be adversely affected by water Installation 1 Turn off all equipment to be fed by the OneFlow System locate water supply cut off valve and turn OFF 2 Determine if water line has an existing water tre...

Page 3: ...3 Installation Drawings Dimensions 3 3 3 Direction of Flow ...

Page 4: ... or bucket for two minutes or until water runs clear If no flush valve is present disconnect line from equipment to flush to drain 10 VERY IMPORTANT With water supply inlet valve OPEN and water flow confirmed turn on connected equipment Failure to supply water to equipment may cause serious damage 11 Record filter change on the service log 8 4 7 6 3 2 Maintenance Routine maintenance of your OneFlo...

Page 5: ...cement Cartridge 9 Pressure Relief Button Replacement Filter Cartridges OneFlow systems are designed tested and certified with One Flow filter cartridges with proven performance size and operat ing capacities Use of replacement cartridges other than those specified will void warranties certifications and may compromise equipment protection water quality and cartridge life 8x 6 5 4 3 7 8 1a 1 9 1a ...

Page 6: ...acement parts will be delivered to the owner F O B nearest factory at no cost excluding freight and local labor charges if any Our obligation under this warranty with respect to the OneFlow media will be limited to furnishing a replacement for the media within two years from date of original installation Such replacement media will be delivered to the owner F O B nearest factory at no cost excludi...

Page 7: ...orrecta instalación y el mantenimiento periódico usted contará con años de uso sin problemas Consulte este manual al realizar los cambios de filtro periódicos Las instrucciones facilitan y agilizan el mantenimiento periódico lo que le permitirá aprovechar su sistema al máximo Especificaciones del sistema Presión máxima 125 psi 8 6 bar Temperatura máxima 100 F 38 C Mín 35 F 2 C Conexiones de entrad...

Page 8: ...tor al determinar el lugar de instalación NO montar el sistema OneFlow cerca de ninguna fuente de calor Tampoco montar el sistema sobre dispositivos o zonas que puedan sufrir daños por los efectos del agua Instalación 1 Apagar todos los equipos que se abastecerán del sistema OneFlow localizar la válvula de corte del suministro de agua y CERRARLA 2 Determinar si la tubería de agua ya cuenta con un ...

Page 9: ...ARED FIRME EN ENTRAMADOS O PANEL PARA PARED NO MONTAR A TABLAROCA NI PLACA DE YESO SIN SOPORTE VÁLVULA ESFÉRICA DE 1 2 PARA CAUDAL TOTAL CON CONEXIÓN DE ENTRADA DE 1 2 FPT DESDE EL SUMINISTRO DE AGUA DEL INMUEBLE CONEXIÓN DE SALIDA DE 1 2 FPT AL EQUIPO ESPACIO PARA EXTRACCIÓN PRESIÓN MÁX 125 psi TEMPERATURA MÁX 100 F LA UNIDAD DE FILTRACIÓN DE AGUA DEBE INSTALARSE ÚNICAMENTE EN EL SUMINISTRO DE AG...

Page 10: ...e o a un cubo durante dos minutos o hasta que el agua salga transparente Si no hay una válvula de purga desconectar la tubería proveniente del equipo para purgar al desagüe 10 MUY IMPORTANTE Con la válvula de entrada de suministro de agua ABIERTA y el caudal de agua confirmado encender el equipo conectado La falta de suministro de agua al equipo puede ocasionar daños graves 11 Registrar el cambio ...

Page 11: ...esto OF120RM 9 Botón de alivio de presión Cartuchos de filtro de repuesto Los sistemas OneFlow son diseñados probados y certificados con los cartuchos de filtro OneFlow que poseen capacidades de funcionamiento rendimiento y dimensiones comprobadas El uso de cartuchos de repuesto distintos a los especificados anulará las garantías y certificaciones y puede poner en peligro la protección del equipo ...

Page 12: ...la está limitada al reemplazo o la reparación a nuestra elección de cualquier pieza o piezas a nuestra satisfacción con defectos comprobados dentro del período de garantía antes estipulado Tales piezas de repuesto serán entregadas al propietario bajo condición Libre a bordo Free on Board FOB en la fábrica más cercana sin costo alguno sin incluir gastos de flete y mano de obra local de corresponder...

Page 13: ...tallation et un entretien de routine adéquats assureront un fonctionnement sans problème pendant plusieurs années Consulter ce manuel pour le remplacement de routine du filtre Les instructions permettent d effectuer l entretien périodique facilement et rapidement et garantissent de tirer le meilleur parti des avantages du système Spécifications du système Pression maximale 8 6 bar 125 psi Températ...

Page 14: ...e gauche à droite garder ceci à l esprit lors de la sélection de l emplacement NE PAS monter le système OneFlow près d une source de chaleur De même ne pas monter le sys tème au dessus d un appareil ou d une zone qui pourrait être endommagé par de l eau Installation 1 Éteindre tout l équipement devant être alimenté par le système OneFlow Repérer le robinet d arrêt et le fermer 2 Déterminer si la c...

Page 15: ...DE GYPSE NON SOUTENUS ROBINET À BILLE À PASSAGE INTÉGRAL D 1 2 PO AVEC RACCORD D EN TRÉE D 1 2 PO À PARTIR DE L ALIMENTATION EN EAU DU BÂTIMENT PRESSION MAX 125 psi TEMPÉRATURE MAX 38 C 100 F L UNITÉ DE FILTRATION DE L EAU DOIT ÊTRE INSTALLÉE SUR L ALIMENTATION EN EAU FROIDE UNIQUEMENT MONTER SUR DES POTEAUX DE CLOISON OU DES PANNEAUX MU RAUX SOLIDES NE PAS MONTER SUR DES PANNEAUX DE PLÂTRE OU DE ...

Page 16: ...ue l eau qui s écoule soit propre S il n y a pas de robinet de rinçage débrancher la conduite de l équipement pour effectuer le rinçage 10 TRÈS IMPORTANT Avec le robinet d alimentation en eau OUVERT et le débit d eau confirmé mettre l équipement raccordé en marche Si l équipement n est pas alimenté en eau des graves dommages peuvent avoir lieu 11 Noter la date de remplacement du filtre sur le jour...

Page 17: ...ssipation de la pression Cartouches de filtre de rechange Les systèmes OneFlow sont conçus testés et certifiés avec des cartouches à filtre OneFlow dont la performance la taille et les capacités de fonctionnement sont prouvées L utilisation de cartouches de rechange autres que celles indiquées annulera les garanties et les certifications et peut compromettre le système de protection de l équipemen...

Page 18: ...ssus Ces pièces de rechange seront fournies gratuitement au propriétaire FAB à l usine la plus proche à l exception des frais de transport et de main d œuvre locale le cas échéant Notre obligation dans le cadre de cette garantie par rapport au média filtrant OneFlow sera limitée à son remplacement dans les deux années suivant la date d installation d origine Le média filtrant de rechange sera four...

Page 19: ......

Page 20: ...815 Chestnut St No Andover MA 01845 6098 www watts com Canada 5435 North Service Rd Burlington ONT L7L 5H7 www wattscanada ca Une entreprise de Watts Water Technologies IOM OF220 2 1017 Réf EDP 2915000 2010 Watts ...

Reviews: