background image

3

Installation 

  1.   Turn off all equipment to be fed by the OneFlow system, 

locate water supply shut off valve and turn OFF.

  2.   Determine if the water line has an existing water treatment 

system. If so, examine system for use of polyphospate or 

other scale inhibitors. OneFlow will not be effective if used 

in conjunction with other scale inhibitors. Remove the scale 

inhibitors from the water line or discontinue installation.

  3.  Install a user supplied ball valve on the water supply side 

that will feed the water system.

  4.  Anchor the OneFlow system on a suitable mounting surface 

that can support the weight of the system while in operation. 

System must be vertical and upright.

  5.  Run a suitable line from the user supplied ball valve at the 

tap water source to the inlet ball valve on the left side of the 

OneFlow system. Use 2-3 wraps of Teflon

®

 tape on the feed 

water connection and brace the inlet ball valve on the system 

with a wrench when connecting the feed water line. 

DO NOT OVERTIGHTEN CONNECTION FITTING INTO 

BALL VALVE.

  6.  Select the appropriate size tubing for the equipment being 

fed and connect it to the outlet of the OneFlow system. 

DO NOT connect the tubing to the equipment at this time.  

Prior to making connection to the equipment, this line will  

be used to facilitate flushing the system. As an option, a  

drain valve in a tee on the outlet side of the OneFlow system 

could be installed in the line to facilitate flushing when 

changing filters. 

  7.  With OneFlow inlet valve closed, slowly open the ball valve 

at the tap water source. Check for leaks.

  8.  If a drain valve was not installed on the outlet side of the  

system, hold the tubing that will connect to equipment in a 

clean bucket or over sink or drain. Open the system inlet feed 

valve and allow water to flush through system for 2 minutes at 

the system’s rated flow rate to allow air bubbles to escape. 

NO ACTIVATION IS REQUIRED FOR THE OneFlow system  

TO PERFORM PROPERLY. FLUSHING IS RECOMMENDED 

TO ALLOW AIR TO ESCAPE THE SYSTEM.

  9.  Make certain that the end of the tubing to be connected to 

the equipment is clean and sanitary. 

10.  Connect tubing to equipment. Open all water supply valves 

and check for leaks.

11.  If no leaks, turn on equipment and check for normal operation.
12.  Attach the Service Log to the installed OneFlow system and 

fill in install date.
The system is now ready for operation.

Teflon

®

 is a registered trademark of The Chemours Company.

NOTICE

NOTICE

NOTICE

WARNING

!

Using OneFlow with Other Water 

Treatment Equipment

Due to the unique properties of OneFlow, there are some 

unique requirements for using OneFlow in conjunction with 

filtration or other forms of water treatment.
1.  OneFlow must be the last stage in the treatment chain. 

 

Do not install any filters after OneFlow or before any devices 

for which scale prevention is required. POU filters, e.g. car-

bon, RO or Ultraviolet (UV) are exempt from this requirement.

2.  Do not apply any other antiscalants before or after OneFlow.
3.  The addition of soaps, chemicals, or cleaners, before or after 

OneFlow treatment, may reverse its anti-scale treatment 

effects and/or create water with a heavy residue or spotting 

potential. Any adverse conditions caused by the addition  

of soaps, chemicals, or cleaners are the sole responsibility 

of the end user.

4.  OneFlow is not a water softener and does not soften 

the water - Water treatment chemistry (e.g. antiscalants, 

sequestrants, soaps, chemicals or cleaners etc...) will most 

likely have to be changed to be compatible with OneFlow 

treated water.

Laundry and ware-washing chemistry will likewise require 

adjustments.

NOTICE

Spotting May Occur on External 

Plumbing Surfaces

OneFlow media systems perform best in single pass potable 

water applications with NO additional chemical additives. 

Depending on hardness, soft scale spotting may occur. Soft 

scale spots in most cases can be easily wiped down with a 

damp cloth and will not form hard scale deposits. 
A Point of Use (POU) Water Softener should be used on mandatory 

spot-free applications (e.g. glass stemware, dishware).

Summary of Contents for OneFlow OF110-1

Page 1: ... capacity for OneFlow These systems are designed to operate 24 7 365 for 1 year Contaminants present in the water will gradually degrade the effectiveness of these cartridges Change the cartridges at least once annually IOM OF110 1_OF120 2_OF140 4 WARNING Read this Manual BEFORE using this equipment Failure to read and follow all safety and use information can result in death serious personal inju...

Page 2: ... OneFlow media needs to be protected from excess levels of certain metals that can easily coat the active surface reducing its effectiveness over time Public water supplies rarely if ever present a problem but if the water supply is from a private well confirm that the levels of iron Fe and manganese Mn are less than 0 3 mg L and 0 05 mg L respectively Pursuant to the EPA drinking water standards ...

Page 3: ...ystem TO PERFORM PROPERLY FLUSHING IS RECOMMENDED TO ALLOW AIR TO ESCAPE THE SYSTEM 9 Make certain that the end of the tubing to be connected to the equipment is clean and sanitary 10 Connect tubing to equipment Open all water supply valves and check for leaks 11 If no leaks turn on equipment and check for normal operation 12 Attach the Service Log to the installed OneFlow system and fill in insta...

Page 4: ...ight and the height of the inlet fitting varies due to material variations and assembly tolerances Please allow additional clearance above the filter for making connections Peak Flow Rates Weights Model Maximum Flow Dry Weight Service Weight OF110 1 1 gpm 3 8 lpm 5 lbs 2 3 kgs 8 lbs 3 6 kgs OF120 2 2 gpm 7 6 lpm 8 lbs 3 6 kgs 15 lbs 6 8 kgs OF140 4 4 gpm 15 1 lpm 18 lbs 8 2 kgs 32 lbs 15 kgs Excee...

Page 5: ... drain or bucket for two 2 minutes or until water runs clear If no flush valve is present disconnect line from equipment to flush to drain 10 With water supply inlet valve OPEN and water flow confirmed turnonconnectedequipment Failuretosupplywatertoequipment may cause serious damage 11 Record filter change on the service log Maintenance Routine maintenance of your OneFlow system involves periodic ...

Page 6: ...t Ball Valve 4 1 Filter Housing Wrench 1A 3 1B 4 2 1C 3 1B 1 1 1 2 3 4 1A 1B 1C 1A 3 1B 4 2 1C 6 3 1A 5 4 1B 2 1C 1 1 5 6 3 4 2 1A 1B 1 1C Replacement Parts for OneFlow OF140 4 ITEM QTY DESCRIPTION 1 1 Housing with Pressure Relief and O ring 1A 1 Housing Lid 1B 1 O Ring 1C 1 Housing Bowl 2 1 Replacement OneFlow Filter Cartridge 3 1 Inlet Ball Valve 4 1 Filter Housing Wrench 5 1 Mounting Bracket 6 ...

Page 7: ...ch replacement parts will be delivered to the owner F O B nearest factory at no cost excluding freight and local labor charges if any Our obligation under this warranty with respect to the OneFlow media will be limited to furnishing a replacement for the media within two years from date of original installation Such replacement media will be delivered to the owner F O B nearest factory at no cost ...

Page 8: ......

Page 9: ...ntes en el agua degradarán gradualmente la eficacia de estos cartuchos Cambie los cartuchos al menos una vez al año ADVERTENCIA Lea este manual ANTES de utilizar el equipo Si no lee y respeta toda la información sobre seguridad y uso las consecuencias pueden ser la muerte lesiones graves daños materiales o daños en el equipo Conserve este manual para consultarlo en el futuro Deberá consultar los c...

Page 10: ...xcesivos de ciertos metales que pueden cubrir fácilmente la superficie activa y reducir su efectividad con el tiempo El suministro público de agua potable raras veces si acaso presenta problemas pero si el suministro de agua proviene de un pozo privado confirme que los niveles de hierro Fe y manganeso Mn sean menores de 0 3 mg l y 0 05 mg l respectivamente De conformidad con las normas de agua pot...

Page 11: ...GAR LA TUBERÍA PARA PERMITIR QUE EL AIRE SALGA DEL SISTEMA 9 Asegúrese de que el extremo de la tubería que se va a conectar al equipo esté limpio e higiénico 10 Conecte la tubería al equipo Abra todas las válvulas de suministro de agua y verifique que no haya fugas 11 Si no hay fugas encienda el equipo y verifique que la operación sea normal 12 Adhiera el registro de servicio al sistema OneFlow in...

Page 12: ... la efectividad y anular la garantía C D A INSTALADO EN MUROS ESTABLES EN TRAVESAÑOS O EL PANEL DEL MURO NO LO INSTALE EN UNA HOJA DE TABLARROCA SIN SOPORTE O EN UNA PLACA DE YESO INSTALADO EN MUROS ESTABLES EN TRAVESAÑOS O EL PANEL DEL MURO NO LO INSTALE EN UNA HOJA DE TABLARROCA SIN SOPORTE O EN UNA PLACA DE YESO CONECTAR EL AGUA DE SUMINISTRO DE ENTRADA A LA VÁLVULA DE BOLA DE ENTRADA CONECTAR ...

Page 13: ...e y purgar los cartuchos nuevos al desagüe o a un cubo durante dos 2 minutos o hasta que el agua salga transparente Si no hay una válvula de purga desconectar la tubería proveniente del equipo para purgar al desagüe 10 Con la válvula de entrada de suministro de agua ABIERTA y el caudal de agua confirmado encender el equipo conectado La falta de suministro de agua al equipo puede ocasionar daños gr...

Page 14: ... 1 Llave de la carcasa del filtro 1A 3 1B 4 2 1C 3 1B 1 1 1 2 3 4 1A 1B 1C 1A 3 1B 4 2 1C 6 3 1A 5 4 1B 2 1C 1 1 5 6 3 4 2 1A 1B 1 1C Piezas de repuesto para OneFlow OF140 4 ARTÍCULO CANT DESCRIPCIÓN 1 1 Carcasa con alivio de presión y junta tórica 1A 1 Tapa de la carcasa 1B 1 Junta tórica 1C 1 Recipiente de la carcasa 2 1 Cartucho de filtro OneFlow de repuesto 3 1 Válvula de bola de entrada 4 1 L...

Page 15: ...repuesto serán entregadas al propietario bajo condición Libre a bordo Free on Board FOB en la fábrica más cercana sin costo alguno sin incluir gastos de flete y mano de obra local de corresponder Nuestra obligación bajo la presente garantía con respecto al material OneFlow estará limitada a suministrar repuestos por el material durante dos años desde la fecha de la instalación original Tales mater...

Page 16: ......

Page 17: ...ces cartouches Changez les cartouches au moins une fois par an AVERTISSEMENT Lisez ce manuel AVANT d utiliser cet équipement Le non respect de ces instructions ou des renseignements relatifs à la sécurité et à l utilisation risque de provoquer des blessures graves voire mortelles des dégâts matériels et des dommages à l équipement Conservez ce manuel à titre de référence ultérieure Vous êtes tenu ...

Page 18: ...doit être protégé contre des niveaux excessifs de certains métaux qui peuvent facilement recouvrir la surface active ce qui réduit son efficacité au fil du temps L eau fournie par les services publics pose rarement voire jamais de problème mais si l approvisionnement en eau provient d un puits privé confirmez que les niveaux de fer Fe et de manganèse Mn sont inférieurs à 0 3 mg l et 0 05 mg l resp...

Page 19: ...ÈME 9 Assurez vous que l extrémité de la tuyauterie raccordée à l équipement est propre et désinfectée 10 Raccordez la tuyauterie à l équipement Ouvrez tous les robinets d alimentation d eau et vérifiez l étanchéité 11 S il n y a pas de fuite mettez l équipement sous tension et vérifiez le fonctionnement normal 12 Attachez le journal d entretien au système OneFlow et inscrivez la date d installati...

Page 20: ...uire l efficacité et annuler la garantie C D A MONTÉ AFIN DE FIXER LE MUR SUR DES MONTANTS OU UN PANNEAU MURAL NE PAS MONTER SUR DES PANNEAUX DE GYPSE OU EN FEUILLE DE PLÂTRE NON SOUTENUS MONTÉ AFIN DE FIXER LE MUR SUR DES MONTANTS OU UN PANNEAU MURAL NE PAS MONTER SUR DES PANNEAUX DE GYPSE OU EN FEUILLE DE PLÂTRE NON SOUTENUS CONNECTER L EAU D ALIMENTATION À LA VANNE À BILLE CONNECTER L EAU D ALI...

Page 21: ...seau pendant deux 2 minutes ou jusqu à ce que l eau qui s écoule soit propre S il n y a pas de robinet de rinçage séparer la conduite de l équipement pour effectuer le rinçage 10 Avec le robinet d alimentation en eau OUVERT et le débit d eau confirmé mettre l équipement raccordé en marche Si l équipement n est pas alimenté en eau des graves dommages peuvent avoir lieu 11 Noter la date de remplacem...

Page 22: ... d entrée 4 1 Clé de boîtier de filtre 1A 3 1B 4 2 1C 3 1B 1 1 1 2 3 4 1A 1B 1C 1A 3 1B 4 2 1C 6 3 1A 5 4 1B 2 1C 1 1 5 6 3 4 2 1A 1B 1 1C Pièces de rechange pour OneFlow OF140 4 PIÈCE QTÉ DESCRIPTION 1 1 Boîtier avec décharge de pression et joint torique 1A 1 Couvercle du boîtier 1B 1 Joint torique 1C 1 Bol de boîtier 2 1 Cartouche de filtre OneFlow de remplacement 3 1 Clapet à bille d entrée 4 1...

Page 23: ...à l exception des frais de transport et de main d œuvre locale le cas échéant Notre obligation dans le cadre de cette garantie par rapport au média filtrant OneFlow sera limitée à son remplacement dans les deux années suivant la date d installation d origine Le média filtrant de rechange sera fourni gratuitement au propriétaire FAB à l usine la plus proche à l exception des frais de transport et d...

Page 24: ...Notes Notas Notes ...