Lync AEGIS
2: INTRODUCTION
L-OMM-012_A
•
4/20/2022
Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST
8
of
37
To limit the possible discomfort that can be generated by excessive heat dissipation, or
excessive and rapid spillage of water from the top of the tanks, you can use the probe BT2
to operate a "comfort" function. In this case, even if the temperature BT1 is higher than the
value of "Set point unit OFF", the unit operate when the BT2 is lower than a value of "Set point
comfort ON".
Operation with only the BT1 probe is allowed, while the use of the BT2 probe requires the presence
of the BT1 probe. The unit will turn off only when both the BT1 and BT2 temperatures are greater
than the related set points.
I M P O R T A N T
The unit will begin to run with only the BT1 probe, regardless of BT2 probe. If the unit
runs based on the BT2 probe, regulation with BT1 probe will also start automatically,
even if the starting parameter (ST02) is OFF.
Please refer to Aegis Electronic Controller Manual (L-OMM-013) for information on enabling
and choosing between local analog and remote digital input.
2.4. Version With Cool Recovery (Air Source Unit Only)
Using the cool recovery option, heat can be drawn from a water stream rather than the ambient air,
thus providing cooling to a water loop. This can be used to not only increase the performance of the
heat pump, but also increase the performance of water loops such as a central chilled water
system. See Aegis Electronic Controller Manual (L-OMM-013) for further details on how to
activate and control this function. NOTE: This option is available only for the Air source unit.
Set Point ON comfort
Set Point OFF comfort