Series 007 may be installed in either a vertical or horizontal posi-

tion. Pipe lines should be thoroughly flushed to remove for-

eign material before installing the unit. A strainer should be installed 

as shown, ahead of backflow preventer to prevent disc from 

unnecessary fouling. Install valve inline with arrow on valve body 

pointing in the direction of flow.

For indoor installations, it is important that the valve be easily 

accessible to facilitate testing and servicing. Do not install in a con-

cealed location.

 

CAUTION

!

Do not install with strainer when backflow preventer is used on sel-

dom-used water lines which are called upon during emergencies, 

such as fire sprinkler lines, etc.

It is important that Series 007 and LF007 be tested periodically in 

compliance with local codes, but at least once a year or more often 

depending upon system conditions.

 

NOTICE

Fire Protection System Installations

The National Fire Protection Agency (NFPA) Guidelines require a 

confirming flow test to be conducted whenever a “main line” valve 

such as the shutoff valves or a backflow assembly have been oper-

ated. Certified testers of backflow assemblies must conduct this 

test. The trim valves of the detector meter bypass line, on assem-

blies so equipped, should be shutoff during the confirming flow 

test. When the test is completed, the trim valves must be returned 

to a fully open position.

Outside Building Above Ground - 

Figure 5

In an area where freezing conditions do not occur, Series 007 and 

LF007 can be installed outside of a building. The most satisfactory 

installation is above ground and should be installed in this manner 

whenever possible. In an area where freezing conditions can occur, 

Series 007 and LF007 should be installed above ground in an insu-

lated enclosure.

Annual inspection of all water system safety and control valves is 

required and necessary. Regular inspection, testing and cleaning 

assures maximum life and proper product function.

Parallel - 

Figure 6

Consult Local codes for Approval

Two or more Series 007 and LF007 smaller size valves may be 

piped in parallel (where approved) to serve a larger supply pipe 

main. This type of installation is employed whenever it is vital to 

maintain a continuous supply of water/where interruptions for test-

ing and servicing would be unacceptable. It also has the advantage 

of providing increase capacity where needed beyond that provided 

by a single valve and permits testing or servicing of an individual 

valve without shutting down the complete line. For two valve instal-

lations the total capacity should equal or exceed that required by 

the system.

The quantity of valves used in parallel should be determined by the 

engineer's judgement based on the operating conditions of a spe-

cific installation. (See F-FC regarding flow curves)

 

NOTICE

The flange gasket bolts for the gate valves should be retightened 

during installation as the bolts may have loosened due to storage 

and shipping.

Installation Instructions

Series 007 and LF007

2

1

2

" and 3" 

2

1

2

", 3" 007 / LF007

2

1

2

", 3" 007 / LF007

Meter

Strainer 

Series 77F-DI-FDA-125

Strainer Series 77F-DI-FDA-125

WattsBox Insulated Enclosures

Available in Aluminum or Fiberglass.

For more information, send for ES-WB.

Figure 4

Figure 5

Figure 6

Reviews: