7.5 Exchanging the supply and return line
The flow is on the right side.
1. Disconnect the power supply and secure it against being
switched on again.
2. Disassemble motor from 3-way mixer.
3. Remove lines from bracket and detach connecting tube
from 3-way mixer.
4. Exchange the lines.
The supply line is now on the left side.
5. Loosen the connection to the ball valve, turn the return
pipe and tighten the connection to the ball valve again.
6. Release the end cap from the 3-way mixer and close the
opposite side with it.
7. Connect the connection tube to the 3-way mixer and insert
the cords into the holder.
8. Reorient the mixer rotary plug valve and mount the motor.
9
Observe the separate operating instructions of the
motor.
9
Check the pump group for leaks.