HKFC20-IM-DE-W-UK-04-2022-Rev.1 | Part no. 10084532
11
EN
ENGLISH
8.5 Disassembling the 3-way mixer
1. Disconnect the power supply and secure it against being
switched on again.
2. Remove the front panel of the pump group.
3. Close all stop valves.
4. Disassemble thermometer handles and intermediate
insulation.
5. Move the mixer rotary plug valve to center position by
manual adjustment of the motor.
6. Disassemble the motor (Pos. B, the assembly/disassembly
of the motor can be found in the respective manufactur-
er's instructions).
7. Remove the mixer (pos. A) by loosening the union nuts.
9
The assembly / disassembly of the motor can be
found in the respective manufacturer’s manual.
A
B
8.6 Installing the 3-way mixer
1. Replace damaged or defective seals if necessary.
2. Install the 3-way mixer (B) and tighten the union nuts (for
tightening torques see “Technical data” on page 4).
3. Mount the motor (A).
4. Slowly open the ball valves by turning the thermometer
handle.
5. Restore the power supply to the pump group.
6. Disassemble the thermometer handles.
7. Install the intermediate insulation, the thermometer han-
dles, and the front panel.
9
The assembly / disassembly of the motor can be
found in the respective manufacturer’s manual.
8.7 3-way mixer motor setting
Mixer closed
Mixer open