5  Installation and commissioning

Electricity!

Risk of death from electric shock.

•  Work on parts carrying live voltage must 

only be carried out by trained electricians.

•  Disconnect the power supply of the sys-

tem and secure it against being switched 
back on before carrying out any installa-
tion, maintenance, cleaning or repair work.

The installation and commissioning of the 
HIU 2 must only be carried out by trained 
personnel who have been authorized by 
the manufacturer.

When installing and operating a circula-
tion system, the recognized rules of engi-
neering as well as the hygiene regulations 
according to “DVGW Arbeitsblatt W551” 
(German association for gas and water, 
worksheet W551) must be observed.

The HIU  2 may only be installed in an 
upright position.

When repairing the unit or replacing parts, 
be sure to observe the specified installa-
tion positions and flow directions of the 
parts being replaced.

Material damage!

Pressure shocks may occur if the stop 
valve is opened quickly.

•  Always open the stop valve slowly and in 

a controlled way.

Bad water quality!

Hard water causes limescale deposits in 
the HIU 2 and diminishes the quality of 
the water.

•  Measure the water hardness in the supply 

system.

•  Install a water softening unit from a degree 

of hardness of 17° dH.

5.1  Installation

All screw fittings must be checked and tightened if nec-
essary prior to installation and commissioning.

Torque:

•  ¾” screw fittings 35 Nm
•   1” screw fittings 55 Nm

Requirements

•  The HIU 2 cabinet (surface-mounted or flush mounted) is 

installed.

•  A safety valve that cannot be shut off must be installed in 

the cold water inlet to the HIU 2. In so doing, the acknowl-
edged rules of technology must be taken into account. 

•  The installation sequence must be observed to prevent 

electrochemical corrosion of galvanized lines and fittings. 

•  The valves are pre-installed at the factory but must be 

checked for leaks during commissioning (hydraulic pressure 
test).

Recommendation: Install water filter into the cold 
water inlet.

Summary of Contents for HIU 2 Series

Page 1: ...eneration and heat distribution Installation and Operating Manual translated from the original operating manual Issued 08 2018 Revision 1 Watts Industries Deutschland GmbH Godramsteiner Hauptstr 167 7...

Page 2: ...n regulations etc Incorrect operation or operating the HIU 2 contrary to the specifications shall void all rights to any warranty claim This installation and operating manual is a component of the HIU...

Page 3: ...HIU2 IM DE W DE 08 2018 Rev1_DE enUS Art No 10078860 3 EN ENGLISH 1 4 Product marking...

Page 4: ...g HK12 HK17 HKM12 HKM17 approx 15 kg 16 Kg 18 Kg 19 kg Connections to pipe network Heat interface unit 1 male thread and male thread flat sealing Meter connections Adapter for heat meter 110 mm G Adap...

Page 5: ...2 outdoors The unit may be used only in accordance with its intend ed use 3 3 Intended use Ready to install compact decentralized heat interface unit for hygienic domestic hot water generation and hea...

Page 6: ...consideration the applicable standards provisions regu lations and laws and his her technical training and technical knowledge to carry out work on the HIU 2 and to detect and prevent potential hazar...

Page 7: ...rs Optional Water hammer arrestor Art No 10079166 Circulation set Art No 10080335 Thermostatic circulation bridge Art No 10079903 HIU 2 HKM 10079851 HIU 2 HKM 12 CU 10079892 HIU 2 HKM 12 STS 10078463...

Page 8: ...8 HIU2 IM DE W DE 08 2018 Rev1_DE enUS Art No 10078860 EN ENGLISH 4 1 Hydraulic diagram HIU 2 HK Optional Optional 490mm 130mm 705mm Optional 500mm 140mm 705mm HIU 2 HKM...

Page 9: ...8 Actuating drive 9 Flow switch 10 Connection for supply temperature sensor of the heat meter 11 Dirt trap 12 Membrane regulator differential pressure regulator 13 Circulation set optional 14 Zone val...

Page 10: ...drive 9 Flow switch 10 Connection for supply temperature sensor of the heat meter 11 Dirt trap 12 Membrane regulator differential pressure regulator 13 Circulation set optional 14 15 Adapter for cold...

Page 11: ...nd flow directions of the parts being replaced Material damage Pressure shocks may occur if the stop valve is opened quickly Always open the stop valve slowly and in a controlled way Bad water quality...

Page 12: ...bserve the recognized rules of technology when doing so 1 Insert the HIU 2 and connect to the connection rail Optional 2 Install the water hammer arrestor circulation set and circulation manifold 3 Co...

Page 13: ...C 55 C 60 C 50 C Heat interface unit HIU 2 26 plates 12 l min 200 mbar DHW temperature secondary circuit with various primary supply temperatures Heat interface unit HIU 2 36 plates 17 l min 200 mbar...

Page 14: ...00 10 000 Druckabfall mbar Durchfluss L h Sekund re Seite Trinkwasser warm 26 Platten 12 l min Kvs Wert 2 2 m h gestrichelte Linie 36 Platten 17 l min Kvs Wert 2 5 m h durchgehende Linie Pressure drop...

Page 15: ...Linie HIU 2 HK Kvs Wert 1 7 m h durchgehende Linie 1 10 100 1 000 10 100 1 000 10 000 Druckabfall mbar Durchfluss L h Sekund re Seite Trinkwasser kalt Kvs Wert 6 5 m h Pressure drop mbar Pressure drop...

Page 16: ...erating and performance parameters are set correctly Check flow noise during operation Ask users if there are any noticeable problems 3 Ball valves Check that stop valves and ball valves can move free...

Page 17: ...ing 4 Slowly open the stop valves and vent the system 7 4 Replacing the plate heat exchanger 1 Close all stop valves 2 Depressurize the HIU 2 e g by opening the vent valve 3 Loosen the nuts pos A and...

Page 18: ...3 4 male thread 10080352 Plate heat exchanger XB06H 1 26 4x3 4 copper brazed 10080356 Plate heat exchanger XB06H 1 26 4x3 4 stain less steel brazed 10080358 Plate heat exchanger XB06H 1 36 4x3 4 copp...

Page 19: ...ould like to return the HIU 2 or parts of it 9 2 Reporting to administrative bodies and the manufacturer Inform the manufacturer about decommissioning and disposal of the HIU 2 for statistical purpose...

Reviews: