13
Installation Diagrams - Series HCTA-200-PPSM
Duplex Alternating Systems
Notes: duplex alternating 2" water softeners
1. All dimensions shown in table are in inches, unless otherwise noted & are ± 1 inch (25mm).
2. All items shown in phantom line are to be provided by others.
3. All dimensions are subject to change without any notice.
4. Provide a 2 feet minimum clearance above mineral tank for filling media.
5. A GFCI equipt electrical outlet should be provided within 5 feet of equipment location.
6. Provided system shall not be subject to any vacuum. If risk of vacuum is present, install
siphon break on drain line & install vacuum relief valve watts ordering code # 0556031
on inlet line.
7. Brine tank dimensions shown on table are factory selected for use with the specified
system size.
8. Do not install drain line directly to a drain. For proper drain connection follow all national,
state and local codes. Do not construct drain line to elevations that exceed 4 feet above the
control valve’s drain port.
9. The full weight of the piping and valves must be supported by pipe hangers or other means.
10. Inlet and outlet supply piping needs to be sized according to flow rate requirements by others.
11. Power requirements: 115v/60hz 2.7 Amps per control valve unless otherwise specified.
12. Brine tank must be located within 10 feet of system control valve and on a common floor
elevation with mineral tank to ensure proper brine draw operation.
13. Use factory supplied brine tubing. Do not use smaller diameter tubing than what is supplied.
14. Limit inlet pressure to not exceed maximum published operating pressure.
Installation Reference Notes For All System Installation Drawings:
Front View
Side View
Drain and Brine Connection Detail
Drain water out to drain
Control Valve Brine Connection Port-
Connect brine tube from brine tank.
Use tube fittings located in system
manual bag.
Control valve
drain connection
Drain Line Flow Control
Housing & Flow Button -
Flow button
must
face
the flow of the drain water.
Point arrow on drain line
flow control housing in
direction of flow.
Top View