Com fort Operating Mode (Sun):

 Press +/- button(s) to adjust the  

desired setpoint.

Nigh t Setback Mode (Moon):

 Sets the operating temperature to a lower point. 

Use the +/- button(s) to adjust the setback temperature.

Time r  (Clock): 

Thermostat can be tied into an external timer to control system 

operation.

 

 

Blinking sun indicates system is in Comfort Mode.

 

 

Blinking moon indicates system is in Setback Mode.

J1

°F

°C

Operating Mode Menu 
(power, comfort, set-back, timer)

Heat/Cool Operation Indicator

Indicates Display is Showing  
Current Temperature

Shows Measured or Set Temperature

Operation Parameter (see chart for details)

Note:  Do not apply power to the relay ("dry" contact) terminals on the  

Dual Sensing Thermostat. Doing so will cause damage to the thermostat.

Wall Anchor Point
"Dry" Contacts

Electrical Access

Sensor Connections

18-2
Electrical Wire

Optional External 
Floor Sensor Wire

Battery

Transformer

Optional Floor Sensor

To Relay Box TT Terminals

24V Digital DualTemp

 1   2   3   4

24VA

C

POW

X

X

ZONE 3

ZONE 1ZONE 2

ZONE 4

POWER

INPUT

ZONE 2

ZR

ZC

ZONE 1

ZONE 3ZONE 4

Optional Floor Sensor

Transformer

Black

Green

White

Green

White

Black

Fusetron

To Relay Coil "

B

" Side

To Relay Coil "A" Side

24V Digital DualTemp

ES-Dual-Sensing-Thermostat 

1142 

       

© 

2011 

Watts 

Radiant

USA:

 

No. Andover, MA • Tel. (855) 699-2887 • Fax: (978) 794-1848 • 

radiant.watts.com

Canada:

 

Burlington, ONT. • Tel. (905) 332-4090 • Fax: (905) 332-7068 •

 radiant.watts.com

CONTrOl SETTiNgS AND PArAMETErS

J0:

 

°C/°F Temperature display section.

J1:

   Hot/Cold regulation mode. Select Hot for Heating, Cold for cooling.

  

Hot:

 opens actuator when temperature rises above setpoint.

  

Cold:

 closes actuator when temperature drops below setpoint.

Cy:

   Proportional Integral regulation time cycle, value in minutes  

(default: 15 minute cycle).

 

 

 This setting adjusts how frequently the control monitors the sensor 

readings. Lower mass systems (frame floor applications) can lose heat 

faster than high mass systems (slabs) and may require a faster cycle 

time.

bp:

   Proportional Integral regulation band amplitude value in degrees °C/°F  

(default: 2.0°C/35.6°F). 

J4:

   NO/NC Normally Open or Normally Close actuator selection. 

 

 

NC: If using an isolation relay and/or a relay box.

 

 

NO: if connecting to a Watts Zone Valve control.

J5:

   Select PMP (Pump Maintenance Program) to perform a 1 minute exercise 

everyday.

 

 

 Use this setting to allow the thermostat to cycle the circulator for 1 

minute every day. This setting helps maintain lubrication during no-heat 

periods.

J6:

   Air:   Air (room) setpoint. Displays air temperature with floor low (FL) and high 

(FH) limits.

 

Flr:   Floor (external sensor) setpoint. Displays floor temperature without floor 

low/high limits. Air temperature is not a control boundary.

J7:

   rEG (proportional Integral) or HYs (0.3°C Hysteresis) regulation type selection.

  

rEG

 is preferred setting for use with radiant applications. 

    

HYs

 is preferred setting for use with forced air or other convection 

systems.

Cp:

   Proportional Integral regulation temperature compensation value in °C/°F  

(default: 2.0°C/35.6°F).

 

 

 Adjusts the calibration between the displayed temperature reading and 

the calibrated temperature reading. Do not adjust this value unless 

necessary.

Ao:

   Air Sensor offset adjustment (default: no offset), display measure air sensor 

value.

 

 

 Adjust the display reading to match the air sensor reading. 

Fo:

   Floor sensor offset adjustment (default: no offset), display measure floor sen-

sor value.

  

 Adjust the display reading to match the floor sensor reading. 

FL:

   Floor temperature LOW limitation (default: 5°C/41°F), effective only if floor 

sensor present and set 

J6

 to 

Air

.

 

 

 This setting keeps the floor from dropping below the designated tem-

perature.

FH:

   Floor temperature HIGH limitation (default: 28°C/82°F), effective only if floor 

sensor present and set 

J6

 to 

Air

.

 

 

 This setting keeps the floor from rising above the designated tempera-

ture.

CLr:

 Press 

OK

 to reset to factory defaults.

End:

 Press 

OK

 to exit installation parameters.