background image

5

Watts Water Technologies, Inc.

The difference between the downstream pressure P2 measured with no flow and the same pressure measured at
the generic flow rate Q represents the pressure drop DP of the pressure reducing valve. It depends on the flow
rate, as indicated by the pressure drop diagrams. If you want the downstream pressure never to exceed a given
value P2, you must regulate this to value P2 with no flow. At flow Q, the downstream pressure will be less than
value P2 by an amount equivalent to the pressure drops DP. If the pressure reducing valve is installed to
guarantee that the downstream pressure reaches a given value P2 at a given flow rate Q, this pressure must be
regulated to value P2 + DP with no flow. At flow rate Q, the downstream pressure will be equivalent to P2.

The criterion for choosing the pressure reducing valve consists in determining the diameter in such a way that the speed of 
the fluid does not reach excessively high values, at the rated flow rate, causing excessive pressure drop and outflow noise 
transmitted to the distribution network. The flow rate-speed diagrams help you to choose the diameter of the pressure 
reducing valve in the case of liquids (see water) or gases at pressures of 8-10 bar (see air).

Example 1 (cavitation)

Pressure reducing valve with:
Inlet pressure  

P1=14 bar

Outlet pressure   P2=3 bar

From the cavitation diagram it can be seen that the pressure reducing valve is constantly working in the red zone.
To avoid rapid deterioration, two pressure reducing valves could be used, one connected upstream to the other.
Upstream pressure reducing valve: pressure front from 14 to 6 bar (green zone).
Downstream pressure reducing valve: pressure front from 6 to 3 bar (green zone).

Example 2 (flow rate)

DRV/N pressure reducing valve with:
Inlet pressure (minimum)   P1=8 bar
Outlet pressure    

P2=4 bar

Maximum flow rate Q = 50 l/min

From the flow rate-speed diagram, it can be deduced that a 20 or 25 diameter should be used.
From the pressure drop diagram, the following two cases emerge:
DRV20/N Q = 50 l/min Dp=1.1 bar
DRV25/N Q = 50 l/min Dp=0.68 bar

Setting

Sizing

Exemples of sizing

Summary of Contents for DRV Series

Page 1: ...WattsIndustries com DRV DRVM DRVN DRVMN Series Pressure reducing valves Technical Data Sheet ...

Page 2: ...T DRV Type Part No DN Weight Kg DRV 0501115 1 2 MM 0 9 DRV 0501120 3 4 MM 1 2 DRV 0501125 1 MM 1 7 DRV 0501132 1 1 4 MM 3 1 DRV 0501140 1 1 2 MM 5 1 DRV 0501150 2 MM 6 3 The DRV DRVM DRVN DRVMN Series pressure reducing valves are devices capable of reducing the pressure of the fluid downstream to a desired level and keeping it constant even in the presence of major variations in the flow rate and ...

Page 3: ...th M3A ABS50 Series pressure gauge Scale 0 6 bar DRVMN Type Part no DN Weight Kg DRVMN 0502615 1 2 MM 0 7 DRVMN 0502620 3 4 MM 1 0 DRVMN 0502625 1 MM 1 4 DRVMN 0502632 1 1 4 MM 2 2 DRVMN 0502640 1 1 2 MM 3 5 DRVMN 0502650 2 MM 4 3 Technical features DRV and DRVN Maximum upstream pressure 25 bar Downstream pressure outlet 1 5 6 bar Connections M M tailpiece Downstream pressure adjustment screw 4 Cl...

Page 4: ...as the inlet pressure acts on the two openings A and B see Fig 1 having the same cross section it is compensated and does not therefore result in any force on the pin plug system when the opening angle of the valve is varied The outlet pressure acts on the diaphragm and thus also on the pin plug system which is thus subjected to two contrasting forces the force exerted by the outlet pressure which...

Page 5: ...alues at the rated flow rate causing excessive pressure drop and outflow noise transmitted to the distribution network The flow rate speed diagrams help you to choose the diameter of the pressure reducing valve in the case of liquids see water or gases at pressures of 8 10 bar see air Example 1 cavitation Pressure reducing valve with Inlet pressure P1 14 bar Outlet pressure P2 3 bar From the cavit...

Page 6: ...e rapid damage of the internal parts If the pressure reducing valve is to operate in the red zone contact the Technical Department of Watts Industries Italia 20 18 16 14 12 10 8 6 4 2 0 0 1 2 3 Downstream pressure bar 4 5 6 7 A B C Inlet pressure bar A Cavitation Zone B Transition Zone C Work Zone Flow rate Speed m s D N 1 5 30 20 10 8 1 0 6 0 4 0 2 0 1 0 1 0 2 0 4 0 6 0 8 2 4 6 10 20 60 200 1000 ...

Page 7: ... Pressure drop bar l m 0 8 1 1 2 4 3 5 6 8 20 30 10 40 60 80 100 200 400 DRV50 DRV40 DRV32 DRV25 DRV20 DRV15 0 08 0 1 0 2 0 3 2 0 6 0 4 Pressure drop Flow rate bar l m 0 8 1 1 2 4 3 5 6 8 20 30 10 40 60 80 100 200 400 DRVN50 DRVN40 DRVN32 DRVN25 DRVN20 DRVN15 DRV DRVN ...

Page 8: ...ernal filter Noise 20db Class 1 in Germany PN 25 bar Adjustable downstream pressure 1 5 6 bar with calibration screw Maximum operating temperature 60 C 30 C DVGW Compliant with DVGW SVGW DRVM Series Diaphragm pressure regulator with compensated seat complete with tailpiece WATTS brand DRV Series with threaded male thread DN 1 2 2 Model with pressure gauge M1 ABS50 series scale 0 6 bar Brass body C...

Reviews: