Deep Well Pump Control Valve

Full Port Ductile Iron Dual Chamber Valve
Features

•  Installed on branch of tee off main pumping header
•  Normally open construction
•  Discharges to atmosphere on pump start-up
•  Closes slowly diverting pressure into system during pumping 

cycle

•  Opens slowly on pump shut-off
•  Limit Switch turns pump off when valve is fully open
•  Adjustable Opening and Closing Speed
•  Solenoid equipped with Manual Operator

1

3

4

2(L)

CLOSES VALVE

OPENS VALVE

FLOW

5

X

X

X/Y

(Supply Pressure)

Engineering Specification

Standard Components

Options and Accessories

 

{

L – Dual Limit Switch

1 – Main Valve (900GD - Dual Chamber)
2 – Limit Switch 
3 – 4-Way Solenoid 
4 – Adjustable Opening Speed
5 – Adjustable Closing Speed
Y – Y-Strainer
X – Isolation Cocks 

LEAD FREE

*

The information contained herein is not intended to replace the full 

product installation and safety information available or the experi-

ence of a trained product installer. You are required to thoroughly 

read all installation instructions and product safety information 

before beginning the installation of this product. 

NOTICE

* The wetted surface of this product contacted by consumable water 

contains less than 0.25% of lead by weight.

Operation

The Deep Well Pump Control Valve is designed to minimize the 

surges associated with the starting and stopping of well pumps. 

The valve slowly opens and closes as required to control pumping 

related surges. The pump starts and stops against an open valve.

Pump start up:

 When the pump is signaled to start, the 4-Way 

Solenoid is energized and directs fluid and pressure into the cover 

chamber (above the diaphragm), and relieves fluid and pressure 

from the power chamber (below the diaphragm). The fluid and 

pressure relieved from the cover chamber is vented to atmo-

sphere or available floor drain. The valve closes at an adjustable 

rate, gradually admitting pumping pressure into the distribution 

system. Rate of valve closure is controlled by the adjustable clos-

ing speed control, which restricts the speed at which fluid and 

pressure evacuate the power chamber. The valve remains closed 

during the pumping cycle.

Pump shutdown:

 When the pump is signaled to shut-off, the 

4-Way Solenoid is de-energized, and directs fluid and pressure 

into the power chamber (below the diaphragm), and relieves fluid 

and pressure from the cover chamber (above the diaphragm). The 

fluid and pressure relieved from the cover chamber is vented to 

atmosphere or available floor drain. The valve opens at an adjust-

able rate, gradually reducing pumping pressure, allowing the 

system check valve to slowly close. Rate of valve opening is con-

trolled by the adjustable opening speed control, which restricts 

the speed at which fluid and pressure evacuate the cover cham-

ber. When the valve reaches the full open position, the limit switch 

is actuated, turning the pump off.

Manual Operation:

 Engaging the Solenoid Manual operator 

simulates power to the solenoid, manually closing the main valve. 

Disengaging the Solenoid Manual operator returns the valve to 

the open position.

Series LF985GD

Summary of Contents for AMES LF685GD Series

Page 1: ...cal codes and ordinances WARNING Need for Periodic Inspection Maintenance This product must be tested periodically in compliance with local codes but at least once per year or more as service conditions warrant All products must be retested once maintenance has been performed Corrosive water conditions and or unauthorized adjustments or repair could render the product ineffective for the service i...

Page 2: ...he pump starts and stops against an open valve Pump start up When the pump is signaled to start the 4 Way Solenoid is energized and directs fluid and pressure into the cover chamber above the diaphragm and relieves fluid and pressure from the power chamber below the diaphragm The fluid and pressure relieved from the cover chamber is vented to atmo sphere or available floor drain The valve closes a...

Page 3: ...bly This assembly is the only moving part within the valve allowing it to open or close as commanded by the pilot control system When pressure is applied to the upper diaphragm chamber and released from the lower diaphragm chamber the valve travels to a closed position When pressure is applied to the lower diaphragm chamber and released from the upper diaphragm chamber the valve travels to a full ...

Page 4: ...sure Drop psi 2 3 4 6 8 10 20 30 40 60 80 100 Flow Rate Gallons per minute Water 2 4 10 20 40 60 80 100 200 500 1000 2000 5000 10000 20000 100000 8 6 1 4 1 6 1 2 1 0 8 6 4 3 2 1 2 2 1 2 1 0 8 6 4 3 2 1 2 2 Angle Globe C V Suggested Maximum continuous flow based on velocity of 20 ft per second Maximum intermittent flow based on velocity of 25 ft per second Minimum flow rates based on a 20 40 psi pr...

Page 5: ...le Iron 11 Diaphragm Buna N Nitrile 12 Inner Bearing Bolts 3 and Smaller ASTM A276 304 Stainless Steel 13 Inner Bearing Retainer 3 and Smaller ASTM A276 302 Stainless Steel 13A Bearing Retaining Ring 4 and Larger ASTM A276 302 Stainless Steel 14 Inner Bearing ASTM A276 304 Stainless Steel 15 O ring Buna N Nitrile 16 O ring Buna N Nitrile 17 Stem ASTM A276 304 Stainless Steel 18 Disc Retainer ASTM ...

Page 6: ...enter Angle Thread Angle 150 Angle 300 Angle Thread Angle 150 Angle 300 Port Size NPT Port Size NPT Port Size NPT Shipping Weights A B C D E F G H I J K L M in in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm in in in lbs kgs 6 20 508 21 533 187 16 468 10 254 101 2 267 6 152 61 2 165 3 4 3 4 3 4 340 154 8 253 8 645 263 8 670 213 4 554 123 4 324 131 4 337 8 203 81 2 216 1 1 1 665 302 10 ...

Page 7: ... EPDM optional Viton optional Voltage 24VDC 24VAC or 120VAC Enclosure General Purpose NEMA 4 standard Explosion Proof NEMA 6 6P 7 9 optional Action 4 Way Actuation Solenoid Action only Main valve action energize to open or energize to close is dependent on the particulars of the pilot system Brass solenoids are not lead free and it is illegal to use them in potable services in the United States su...

Page 8: ... the valve opens or closes The adjustable collar is normally set to contact the trip arm when the main valve is closed The collar can be positioned on the stem by loosening the set screw to actuate the switch at the desired point of valve travel Single Pole Double Throw Switch Common Lug Normally Open Normally Closed Specifications Body Material Stainless Steel Elastomers Buna N standard EPDM opti...

Page 9: ...on In the free flow direction the seat moves out of the flow path to all unrestricted flow Specifications Standard Flow Control Large Flow Control FLOW FLOW CLOSED Fluid Speed Controlled by Needle FLOW External Threads Internal Threads FLOW OPEN Free Flow Seat Full Open Size Standard Flow MNPT x 3 8 FNPT High Flow 1 2 MxF NPT Body Material Lead Free Brass Stainless Steel optional Seat Lead Free Br...

Page 10: ...pilot circuit speed controls and pilots The filter element can be accessed for cleaning by removing the clean out cap or may be cleaned by installing an optional blow down ball valve The wetted surface of this product contacted by consumable water contains less than 0 25 of lead by weight Body Material Lead Free Copper Silicon Alloy CF8M 316 Stainless Steel optional Retainer Cap Lead Free Copper S...

Page 11: ...are used in pilot lines to provide a positive shutoff in any override or maintenance situation for simple trouble shooting This 2 piece full port valve features bottom loaded stems PTFE seats and packing Size Dimensions Weight C H L in in mm in mm in mm lbs kg 1 4 113 16 46 37 16 87 13 4 45 0 4 0 2 3 8 113 16 46 37 16 87 13 4 45 0 4 0 2 1 2 113 16 46 37 16 87 115 16 50 0 4 0 2 3 4 21 4 57 4 101 25...

Page 12: ...e switches at the desired point of valve travel Body Material Stainless Steel Elastomers Buna N standard EPDM optional Viton optional Enclosure NEMA 1 3 4 and 13 General Purpose standard NEMA 1 7 and 9 Explosion Proof optional Electrical Form C SPDT Switch 15 amp 125 250 or 480 VAC amp 125 VDC amp 250 VDC Conduit Connection The wetted surface of this product contacted by consumable water contains ...

Page 13: ... made during installation to protect the piping circuit from dam age Only remove the pilot control system from the valve if necessary Tubing and fittings should be kept clean and replaced exactly as removed Consult appropriate hydraulic schematic to ensure proper re assembly 6 Connect solenoid wiring leads to desired switching device using safe standard electrical practices 7 Wire the limit switch...

Page 14: ... of movement and remove excess air trapped within the cover chambers See Figure 1 Below To increase the rate of opening closing turn the adjustment screws on the speed controls OUT counterclockwise In decrease the rate of opening closing turn the adjustment screws on the speed controls IN clockwise STEP 2 Prior to pump start energize the solenoid to confirm connection to power source STEP 3 De ene...

Page 15: ...ee flow goes into the lower chamber the Opening speed flow control restricts flow out of the upper cham ber of the main valve If valve opening is too slow turn the adjustment screw OUT counterclockwise increasing the rate of opening If valve opening is too quick turn the adjustment screw IN clock wise decreasing the rate of opening See Figure 2A STEP 8 At valve full open position deep well pump wi...

Page 16: ...t valve specification sheets for approximate cover capacity A continuous flow of water from the open port indicates a damaged diaphragm or loose disc diaphragm assembly Disassemble valve and replace diaphragm or tighten disc diaphragm assembly Test 2 Seat Seal Test 1 Close downstream isolation valve and install pressure gauges on an open inlet and outlet port of main valve 2 Open upstream isolatio...

Page 17: ...lation valves ensure open Diaphragm is damaged Conduct diaphragm seal test repair and replace if necessary Main valve stem assembly corroded damaged Inspect stem assembly clean replace if necessary Blockage in main valve Perform freedom of movement test if valve does not close disassemble and remove blockage Worn damaged valve seat Perform seat sealing check disassemble and inspect re pair seat if...

Page 18: ...tem Nut examine stem threads for mineral build up Remove deposits with a fine wire brush Extreme care should be taken not to damage the finish on stem guiding surfaces when disassembling Avoid applying pipe wrenches to top or bottom stem guide surfaces 6 After removing the Stem Nut the remainder of the Disc Diaphragm Assembly should disassemble easily Polish stem guide surfaces with fine emery clo...

Page 19: ...es not work properly other costs resulting from labor charges delays vandalism negligence fouling caused by foreign material damage from adverse water conditions chemical or any other circumstances over which the Company has no control This warranty shall be invalidated by any abuse misuse misapplication improper installation or improper maintenance or alteration of the product Some States do not ...