background image

2

•   Most field problems occur because dirt and debris are present 

in the system at the time of installation and becomes trapped 

in check #1. The system should be flushed before the back-

flow valve is installed. If the system is not flushed until after the 

backflow valve is installed, remove both check modules from 

the valve and open the inlet shutoff to allow water to flow for 

a sufficient time to flush debris from the water line. If debris in 

the water system continues to cause fouling, a strainer can be 

installed upstream of the backflow assembly.

•   Series C400, C500, and LFC500 can be installed in either 

horizontal, “N” pattern, or “Z” pattern position as long as the 

backflow assembly is installed in accordance with the direction 

of the flow arrow on the assembly and the local water authority 

approves the installation.

•   The assembly should be installed with adequate clearance 

around the valve to allow for inspection, testing, and servicing. 

Ensure a minimum clearance of 12" between the lower portion 

of the assembly and the floor or grade. Protect the valve  

from freezing.

•   Installing a backflow preventer in a pit or vault is not  

recommended.

•   Normal discharge and nuisance spitting are accommodated by 

the use of an Ames air gap fitting and a fabricated indirect waste 

line. Provide floor drains of the same size in case of excessive 

discharge.

•   Have a certified technician test the series at the time of installation.

 

NOTICE

Assembly body should not be painted.

Installation Guidelines

Relief Valve Discharge Rates 2

1

2

" – 10" 

  lpm gpm

 1330 350

 1140 300

  950 250

  760 200

  570 150

  380 100

 190 50

  0 0

20 

40 

60 

80 psi

138 

276 

413 

551 kPa

Rate of Flow

Pressure

Horizontal Installation

N Pattern

Z Pattern

Summary of Contents for AMES Colt C400

Page 1: ...y in compliance with local codes but at least once per year or more as service conditions war rant All products must be retested once maintenance has been performed Corrosive water conditions and or u...

Page 2: ...on the assembly and the local water authority approves the installation The assembly should be installed with adequate clearance around the valve to allow for inspection testing and servicing Ensure a...

Page 3: ...re C 5 Remove the check 2 module with the same instructions as in step 4 For servicing 6 checks see the maintenance instructions for valve sizes 8 to 10 6 To clean or inspect either check module inser...

Page 4: ...service hole and thread in the service bolt by hand until it contacts the linkage See Figure A 4 Continue to thread in service bolt with the wrench until the service hole in the linkage is aligned wi...

Page 5: ...d to remove it then unscrew the relief valve from the housing 5 Remove the cover plate of the relief valve by detaching the four connecting screws 6 Remove the rubber diaphragm from the relief valve N...

Page 6: ...Open valves B and C bleeding to atmosphere Then closing valve B restores the system to a normal static condition Observe the pressure differential gauge If there is a decrease in the indicated value c...

Page 7: ...ng First Check Module Relief Valve Second Check Module Troubleshooting PROBLEM CAUSE SOLUTION Relief valve discharges water while system is not flowing Check 1 is fouled Remove and clean check 1 Relie...

Page 8: ...nt In the event of such defects within the warranty period the Company will at its option replace or recondition the product without charge THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE...

Reviews: