background image

Standard Components

Operation

The Combination Pressure Reducing and Sustaining ACV with 
Downstream Surge Control Feature is designed to automatically reduce 
a fluctuating higher upstream pressure to a constant lower downstream 
pressure regardless of varying flow rates, throttles to sustain a minimum 
upstream pressure, and will quickly modulate toward a closed position 
if downstream pressure suddenly becomes greater than the desired 
regulated setpoint. The quick closing action prevents possible damaging 
high inlet pressure from passing through the valve to downstream pip-
ing. Pressure Reducing action is controlled by a normally open, pressure 
reducing pilot designed to: 1) Open (allowing fluid out of the main valve 
cover chamber) when downstream pressure is below the adjustable 
setpoint, and 2) Close (allowing fluid to fill the main valve cover cham-
ber) when downstream pressure is above the adjustable setpoint. A 
decrease in downstream pressure causes the valve to modulate toward 
an open position, raising downstream pressure. An increase in down-
stream pressure causes the valve to modulate toward a closed position, 
lowering downstream pressure.

1

X

X

X

Y/FC

1

P/L

5

2

3

4

CLOSES VALVE

OPENS VALVE

FLOW

(AOS)

Start-up of an automatic control valve requires that proper procedures be followed. Time must be allowed for the valve to react to adjustments 
and the system to stabilize. The objective is to bring the valve into service in a controlled manner to protect the system from damaging over-
pressure.
1.  Prior to installation, flush line to remove debris.

2.  Install valve so the flow arrow matches flow through the line, and gauges to monitor valve inlet and outlet pressures. A Position Indicator 

can be installed to provide visual indication of valve position and operation without disassembly.

3.  Install isolation valves upstream and downstream of the main valve.

4.  Open the isolation ball valves in the control tubing if so equipped. Failure to open these will prevent the valve from functioning properly.

5.  Install pressure gauges at locations upstream and downstream of the valve.

Note: 

If using butterfly valves, ensure valve disc does not contact the main valve.

6.  Provide adequate clearance for valve servicing and maintenance. Refer to valve servicing dimensions on next page.

7.  Avoid installing valves 6" and larger in the vertical position (main valve stem horizontal). Automatic Control Valves (ACVs) are designed for 

horizontal in-line installation, with the cover facing up (main valve stem vertical). Slow operation or premature stem and guide wear may 
occur if valve is not installed according to factory recommendations. Consult factory for detailed engineering review prior to ordering if valve 
is to be installed other than horizontally in-line.

8.  If valve is equipped with a pilot control system, extra precautions should be made during installation to protect the piping circuit from dam-

age. Only remove the pilot control system from the valve if necessary. Tubing and fittings should be kept clean and replaced exactly as 
removed. Consult appropriate hydraulic schematic to ensure proper re-assembly.

9.  After installation, vent entrapped air from valve cover and pilot system by following instructions on Technical Bulletin.

The normally closed sustaining pilot remains open when upstream pressure is above the adjustable setpoint, and modulates toward a closed 
position if upstream pressure falls below the setpoint. As the sustaining pilot closes, fluid is directed into the main valve cover chamber, allowing 
the valve to modulate toward a closed position, raising upstream pressure. Normal pressure reducing operation resumes when upstream pres-
sure is above the sustaining pilot setpoint, and downstream pressure is below the reducing pilot setpoint.

If downstream pressure suddenly becomes greater than the desired regulated setpoint, the normally closed surge control pilot opens and rapidly 
admits higher inlet pressure into the valve cover, increasing rate of valve closure. Normal pressure reducing operation resumes when downstream 
pressure decreases below the desired regulated setpoint.

1 - Main Valve (905GD - Single Chamber) 

2 - Pressure Reducing Control 

3 - Downstream Surge Control 

4 - Pressure Sustaining Control 

5 - Fixed Orifice

X - Isolation Cocks

Installation

912GD-11 (Globe) Pressure Reducing and Sustaining Control 
Valve with Downstream Surge Control Feature

2          IOM-A-ACV-912-11_612-11   2115 

EDP# 1917038 

© 2021 Watts

Summary of Contents for Ames 912GD-11

Page 1: ...tion 2 Setting the Pressure Reducing Control 3 Maintenance Schedule 6 Trouble Shooting Guide 6 Valve Disassembly Instructions 8 ACV Schematic 11 Local building or plumbing codes may require modifica t...

Page 2: ...valves ensure valve disc does not contact the main valve 6 Provide adequate clearance for valve servicing and maintenance Refer to valve servicing dimensions on next page 7 Avoid installing valves 6...

Page 3: ...4 16 24 26 28 30 34 40 48 48 Size in 11 4 11 2 2 21 2 3 4 6 8 10 12 14 16 C in 16 16 20 22 22 24 32 34 38 44 48 52 D in 10 10 12 14 14 16 24 26 28 30 34 40 STEP 2 To ensure proper operation any trappe...

Page 4: ...pressure set point by turning the adjustment screw OUT counterclockwise until downstream pressure decreases to the desired setpoint See Figure 3 STEP 6 Adjust the Surge Control by turning the adjustm...

Page 5: ...ise increasing the rate of closing Setting the Pressure Sustaining Control Step 1 Setting The Relief Sustaining Control requires lowering the upstream pressure to the desired minimum sustained pressur...

Page 6: ...specification sheets for approximate cover capacity A continuous flow of water from the open port indicates a damaged diaphragm or loose disc diaphragm assembly Disassemble valve and replace diaphragm...

Page 7: ...ly by partially opening from full closed position Improperly configured opening speed control if equipped Adjust opening speed control to verify functionality adjust as required Standard setting for o...

Page 8: ...move cover nuts and washers 3 Remove the cover If cover is not free to be removed loosen it by tapping upward along its outside edge with a dull cold chisel pic tured above a Large valves may require...

Page 9: ...rush or by using a Mineral Dissolving Solution Inspect parts for wear and replace if necessary 7 Inspect valve seat If seat is not damaged removal is not necessary Valve seats 6 and smaller are thread...

Page 10: ...ts in a crossing pattern to ensure even distribution Test the Disc and Diaphragm Assembly for smooth travel by following the Freedom of Movement Test procedure in previous section 11 Test the integrit...

Page 11: ...el 9 Stem Washer ASTM A276 304 Stainless Steel 10 Diaphragm Washer ASTM A536 65 45 12 Epoxy Coated Ductile Iron 11 Diaphragm Buna N Nitrile 12 Disc Retainer ASTM A536 65 45 12 Epoxy Coated Ductile Iro...

Page 12: ...resulting from labor charges delays vandalism negligence fouling caused by foreign material damage from adverse water conditions chemical or any other circumstances over which the Company has no cont...

Reviews: