Benchmark with Edge [I]: Operation-Maintenance Manual
SECTION 2: OPERATION
OMM-0145_A99
• GF-218 • 9/18/2019 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
21
of
157
Vent Type
Select
Choose the vent material: PVC, cPVC, Polypro, Stainless
Steel.
Exhaust Safety
Enable/Disable
Depending on exhaust temperature and value of Vent Type,
triggers an exhaust temperature warning, reduced fire rate or
unit shutoff.
Fuel Type
Toggle
Choose
Natural Gas
Control Type
Select
Displays the controller type: Edge [i].
Control Use
Select
Choose either
Boiler
or
Water Heater
.
Language
Select
Choose the language
of the Controller’s display:
English
,
Spanish
,
French
.
Unit of Measurement
Toggle
Choose unit of measure:
Metric
or
English
.
Temperature Sensor
Toggle
Choose the sensor type in use on the unit, either
Balco
or
PT
1000
. Do not change unless the sensor type is switched.
Beeper
Toggle
Enables/disables the audible fault alarm.
Run Cycles
Numeric Entry
Displays number of run cycles since last system reset. Can be
reset to 0 or any number.
Run Hours
Numeric Entry
Displays the number of run hours since the last system reset.
Can be reset to 0 or any number.
Reset Common Settings
Select Yes/No
Press
Yes
to restore
common
settings to default values.
Clear Fault Log
Select Yes/No
Press
Yes
to clear the Unit Event History.
Reset All Settings
Select Yes/No
Press
Yes
to restore
all
settings to default values.
Main Menu
→
Advanced Setup
→
Unit
→
Front Panel Configuration
Upper Left Display
Select
Choose
Setpoint
or
Water Inlet
.
Upper Right Display
Select
Choose
Water
Outlet
or
System Header
.
Multi-Function Bar
Select
Choose the Multi-Function Bar display:
Fire Rate
or
Valve
Position
.
Brightness
Numeric Entry
Adjusts Touchscreen brightness.
Screensaver Password
Enable/Disable
If set to
Enabled
, all access to the Controller requires a
Password.
Screen Timeout Minutes
Numeric Entry
Specifies touchscreen timeout in minutes (
Screensaver
Password
=
Enabled
).
Screen Timeout Now
Toggle
Choose
Yes
to put Controller into sleep mode. (
Screensaver
Password
=
Enabled
).
Main Menu
→
Advanced Setup
→
Unit
→
Settings Transfer
Restore All Settings
Select
Restores all settings to the factory default.
Restore Common Settings
Select
Restores common settings to the factory default.
Save All Settings
Select
Saves all settings to USB or onboard memory.
Main Menu
→
Advanced Setup
→
Unit
→
Fault Management
Power Reset
Toggle
Choose if power fault reset mode,
Manual
or
Automatic
.
Water Temp Reset
Toggle
Choose water temperature fault reset mode,
Manual
or
Automatic
.
Gas Pressure Reset
Toggle
Choose if gas pressure fault reset mode,
Manual
or
Automatic
.
Main Menu
→
Advanced Setup
→
Unit
→
Freeze Protection
Freeze Protection
Enable/Disable
Enables/disables Freeze Protection functionality.
Pump On Temperature
Numeric Entry
If enabled, ambient temperature below this value triggers the
system pump to start (20 to 245°F
, Freeze Protection
=
Enabled
).
Unit On Temperature
Numeric Entry
Ambient temperature below this value triggers the unit to fire
(20 to 245°F ,
Freeze Protection
=
Enabled
).
Stop Temperature
Numeric Entry
Ambient temperature above this value returns system to
normal operation
(20 to 245°F,
Freeze Protection
=
Enabled
).
Main Menu
→
Advanced Setup
→
Unit
→
Unit Application Configuration