Description of Controls and Functions
BAS Menu
The BAS Menu selections are generally described in the table below:
Item Field
Range
Default
When
Displayed
Description
Additional Info
BAS Type
NONE <>
BAC-IP <>
BAC-MSTP <>
MODBUS
NONE
Always
Building Automation
Type:
None = control runs in stand alone.
BAC-IP = control is connected to a
BACnet/IP system.
BAC-MSTP = control is connected to
a BACnet/MS-TP system.
MODBUS = control is connected to a
Modbus system.
BACnet
DEVICE ID
0 to 4194303
1
BAS Type = BAC-IP or
BAC-MSTP
Buttons on screen are
OK, DEL, <–, --> ?
BACnet device ID
BACnet Port
1 to 65535
47808
BAS Type = BAC-IP
Use keypad entry 0
thru 9
BACnet Port
key in BACnet PORT
Buttons on screen are
OK, DEL, <–, -->, ?
Register
Foreign Dev
OFF<>ON
OFF
BAS Type = BAC-IP
Is a BACnet Device that has an IP
subnet address different from those
comprising the BACnet/IP network.
BBMD TIME
OFF, 30 to 65535 OFF
BAS Type = BACnet
Time-to-live (Seconds)
BACnet Broadcast Management. A
specified time, extending that time
by periodic (automatic) renewal
requests.
Register Foreign Dev
≠ OFF
Use keypad entry 0
thru 9
key in BBMD TIME
Buttons on screen are
OK, DEL, <–, -->, ?
BBMD IP
0.0.0.1 to
255.255.255.255
127.127.127.127
BAS Type = BACnet
Use keypad entry 0
thru 9
BACnet Foreign device internet
Protocol address. A numerical label
assigned to the foreign device.
Register Foreign Dev ≠
OFF
key in IP Address
Buttons on screen are
OK, DEL, <–, --> ?
BBMD PORT
0 to 65535
47808
BAS Type = BACnet
Use keypad entry 0
thru 9
BACnet Broadcat Management Port.
Register Foreign Dev ≠
OFF
key in BBMD PORT
Buttons on screen are
OK, DEL, <–, --> ?
BAC-MSTP
Address
0 to 127
1
BAS Type = BAC-
MSTP
Buttons on screen are
OK, DEL, <–, --> ?
Set the MSTP address. Each MSTP
device must have a unique address.
BACnet Baud
Rate
9600, 19K2, 38K4,
57K6, 76K8,
115K2
9600
BAS Type = BAC-
MSTP
Slider, OK,<–, --> ?
BACnet MS/TP baud rate
Modbus
Address
1 to 247
1
BAS Type = MODBUS
Radio buttons, OK, ?
Modbus Address:
1 to 247
Modbus Data
Type
RTU <> ASCII
RTU
BAS Type = MODBUS
Slider, OK,<–, --> ?
Modbus Data Type
RTU or ASCII
Modbus baud
Rate
1200, 4800, 9600,
14K4, 19K2,
28K8, 38K4,
57K6, 76K, 115K2
9600
BAS Type = MODBUS
Slider, OK,<–, --> ?
Modbus baud rate
Modbus Parity None <> Odd <>
Even
Even
Slider, OK,<–, --> ?
Modbus Parity type.