The following tables detail the recommended minimum valve servicing dimensions.

          

B

          

          

FLOW

FLOW

FLOW

          

FLOW

Valve Servicing Dimensions

IOM-A-ACV-980-16-19_680-16-19   2115 

EDP# 1917102 

© 2021 Watts         3

Commissioning the Pump Control Valve

STEP 1

NOTE:

 System needs to be filled, pressurized, and ready for flow. Due to an internal system check feature, Automatic Control Valve will 

not flow until pump starts.

Pre-set pilots as noted:

Opening and Closing Speed

 – Prior to pump start, actuate manual operator on solenoid to enable diaphragm assembly to stroke 

open and closed. Observing the limit switch stem indicator, monitor rate of opening and closing speed. Adjust accordingly per applica-
tion requirements.  

NOTE

: Cycle diaphragm multiple times to confirm rate of movement and remove excess air trapped within the cover chambers.

To increase the rate of opening/closing, turn the adjustment 
screws on the speed controls OUT, counterclockwise (See Figure 
1B). In decrease the rate of opening/closing, turn the adjustment 
screws on the speed controls IN, clockwise (See Figure 1A).

STEP 2

Prior to pump start, energize the solenoid to confirm connection 
to power source.

STEP 3

De-energize the solenoid prior to initial pump start.

STEP 4 

Energize the solenoid at pump start to open the main valve, 
checking that the main valve opens.

Globe

Angle

Size (in)

2

21/2

3

4

6

8

10

12

14

16

20

24

A (in)

20

22

22

24

32

34

38

44

48

52

56

56

B (in)

20

22

22

25

36

38

40

44

48

50

50

50

Size (in)

2

2

 

1/2

3

4

6

8

10

12

14

16

C (in)

20

22

22

24

32

34

38

44

48

52

D (in)

20

22

22

25

36

38

40

44

48

50

Figure 1 

Flow Control

Counterclockwise to INCREASE 

the rate of opening

Clockwise to DECREASE 

rate of opening

1A

1B

Summary of Contents for 680GD-16-19

Page 1: ...l Valve 3 Maintenance Schedule 6 Trouble Shooting Guide 6 Valve Disassembly Instructions 8 ACV Schematic 11 Local building or plumbing codes may require modifica tions to the information provided You...

Page 2: ...to minimize the surges asso ciated with the starting and stopping of pumps The valve slowly opens and closes as required to control pumping related surges The pump starts and stops against a closed v...

Page 3: ...to confirm rate of movement and remove excess air trapped within the cover chambers To increase the rate of opening closing turn the adjustment screws on the speed controls OUT counterclockwise See Fi...

Page 4: ...nue to operate as the main valve closes To close main valve de energize the solenoid checking that the main valve closes STEP 7 Closing Speed Flow Adjustment While free flow goes into the upper chambe...

Page 5: ...cification sheets for approximate cover capacity A continuous flow of water from the open port indicates a damaged diaphragm or loose disc diaphragm assembly Disassemble valve and replace diaphragm or...

Page 6: ...Main Valve will not close Closed isolation valves in pilot system Check isolation valves ensure open Diaphragm is damaged Conduct diaphragm seal test repair and replace if necessary Main valve stem a...

Page 7: ...e cover nuts and washers 3 Remove the cover If cover is not free to be removed loosen it by tapping upward along its outside edge with a dull cold chisel pic tured above a Large valves may require the...

Page 8: ...its and inspect for excessive wear Remove any mineral build up from other components with wire brush or by using a Mineral Dissolving Solution Inspect parts for wear and replace if necessary 7 Inspect...

Page 9: ...r smooth travel by following the Freedom of Movement Test procedure in previous section 11 Test the integrity of the Seat Seal by following the Seat Seal Test procedure in previous section 12 Return v...

Page 10: ...r 3 and Smaller ASTM A276 302 Stainless Steel 13A Bearing Retaining Ring 4 and Larger ASTM A276 302 Stainless Steel 14 Inner Bearing ASTM A276 304 Stainless Steel 15 O ring Buna N Nitrile 16 O ring Bu...

Page 11: ...IOM A ACV 980 16 19_680 16 19 2115 EDP 1917102 2021 Watts 11 NOTES...

Page 12: ...2 2021 Watts USA Backflow T 978 689 6066 F 978 975 8350 AmesFireWater com USA Control Valves T 713 943 0688 F 713 944 9445 AmesFireWater com Canada T 888 208 8927 F 905 481 2316 AmesFireWater ca Latin...

Reviews: