background image

STEP 8

(If Installed)

 

Opening Speed Flow Control Adjustment

: The 

Opening speed needle valve restricts flow out of the cover of the 
main valve. 

If the main valve is opening too slowly turn the adjustment screw 
OUT, counterclockwise, increasing the rate of opening (See Figure 
2B).

If the main valve is opening too quickly, turn the adjustment screw 
IN, clockwise, decreasing the rate of opening (See Figure 2A). 

STEP 5 

Actuate the solenoid to open the main valve. 

STEP 6  

Actuate the solenoid to close the main valve, checking that the 
main valve closes. 

STEP 7 

Closing Speed Needle Valve Adjustment: The closing speed 
needle valve regulates fluid pressure into the main valve cover 
chamber, controlling the valve closing speed. If valve closing is 
too slow, turn the adjustment screw OUT, counterclockwise, 
increasing the rate of closing.

STEP 9

When installing float, set angle similar to Figure 3 by adjusting 
F10-11 modulating float pilot linkage screw shown in Figure 4.

4          IOM-A-ACV-979-15_679-15   2115 

EDP# 1917118 

© 2021 Watts

IOM-A-ACV-979-15_679-15   2115 

EDP# 1917118 

© 2021 Watts         5

Counterclockwise to INCREASE 

the rate of opening

Clockwise to DECREASE 

rate of opening

2A

2B

Figure 2 

Flow Control

Linkage 

Adjustment 

Screw

Figure 4 

Modulating Float Control Pilot

Figure 3 

Modulating Float Control Pilot in Tank

Summary of Contents for 679GD-15

Page 1: ...ting the Float Control Valve 3 Maintenance Schedule 6 Trouble Shooting Guide 6 Valve Disassembly Instructions 8 ACV Schematic 11 Local building or plumbing codes may require modifica tions to the info...

Page 2: ...ly 3 Install isolation valves upstream and downstream of the main valve 4 Provide adequate clearance for valve servicing and maintenance Refer to valve servicing dimensions on next page Avoid installi...

Page 3: ...n the valve See Figure 1 STEP 4 Pressure the line by opening the upstream isolation valve slowly Air is vented through the air bleed valve Tighten the fitting when liquid begins to vent See Figure 1 R...

Page 4: ...he main valve closes STEP 7 Closing Speed Needle Valve Adjustment The closing speed needle valve regulates fluid pressure into the main valve cover chamber controlling the valve closing speed If valve...

Page 5: ...specification sheets for approximate cover capacity A continuous flow of water from the open port indicates a damaged diaphragm or loose disc diaphragm assembly Disassemble valve and replace diaphragm...

Page 6: ...1 2 turns open from full closed position Can be adjusted in field Main Valve will not close Closed isolation valves in pilot system Check isolation valves ensure open Diaphragm is damaged Conduct diap...

Page 7: ...move cover nuts and washers 3 Remove the cover If cover is not free to be removed loosen it by tapping upward along its outside edge with a dull cold chisel pic tured above a Large valves may require...

Page 8: ...rush or by using a Mineral Dissolving Solution Inspect parts for wear and replace if necessary 7 Inspect valve seat If seat is not damaged removal is not necessary Valve seats 6 and smaller are thread...

Page 9: ...uts in a crossing pattern to ensure even distribution Test the Disc and Diaphragm Assembly for smooth travel by following the Freedom of Movement Test procedure in previous section 11 Test the integri...

Page 10: ...ess Steel 10 Diaphragm Washer ASTM A536 65 45 12 Epoxy Coated Ductile Iron 11 Diaphragm Buna N Nitrile 12 Disc Retainer ASTM A536 65 45 12 Epoxy Coated Ductile Iron 13 Seat Disc Buna N Nitrile 14 Spac...

Page 11: ...IOM A ACV 979 15_679 15 2115 EDP 1917118 2021 Watts 11 NOTES...

Page 12: ...resulting from labor charges delays vandalism negligence fouling caused by foreign material damage from adverse water conditions chemical or any other circumstances over which the Company has no cont...

Reviews: