Installation Instructions 

n

General Instructions

Figure 5.

to disassemble and replace sensitive tube assembly: 

The Accritem Controller requires a clean, reliable supply 

of compressed air or cold water at room temperature and 

15 tgo 20 pounds of pressure. Other fluids may be used, 

such as gas, oil, etc., providing provision is made for safe 

disposal. 

Figure 6

The parts in Figure 7 are identified by letter in order of disas-

sembly. For item number reference, see Parts Drawing: A (item 

3) adjusting knob with set screw, B (item 10) cover screws, C 

(item 2) cover plate, D (item 8) spring retainer screw, E (item 9) 

lever spring, F (item 21) lever pivot, G (item 7) lever. 
Always locate the controller as close as possible to the 

controlled device. The piping between the controller and 

 controlled device (valve or damper motor) should be 1/8" 

NPT brass pipe or 6.4 mm (1/4") OD copper tubing.
Difference in height between Accritem controller and con-

trolled device should be kept to a minimum. When controller 

is 

below

 controlled device, elevation cannot exceed 3 m (10") 

with 104 kPa (15 psi) supply pressure. If controller is 

above

 

controlled device, adjust springs on valve or damper motor to 

compensate for static head pressure. 

Pressure Controller for Use with Water

Set pressure at 104–138 kPa (15–20 psi) when water is  flowing. 

Clean strainer at regular intervals. 

Both Air and Water Controllers
To disassemble 

(Refer to Parts Drawing and Figure 5):

1. Remove knob 

3

after loosening its set screw.

2. Remove cover plate 

2

3. Remove spring retainer screw 

8

and lever spring 

9

4. Back out one lever pivot 

20

and remove lever 

7

.

5. Unscrew sensitive tube assembly 

20

from body

1

REVERSE ACTING

SPRING LOCATION (behind lever)

8

DIRECT ACTING

SPRING LOCATION (in front of lever)

Lever

Spring

Retainer

Screw

Spring

Retainer

Screw

9

7

Lever

9

8

7

Select sensitive element location with care to insure satisfac-

tory results. Bulb must project entirely into the liquid or air being 

controlled.
Flush or blow out all lines before making final connections. Put 

supply pressure through all control lines and check for leaks.

iNStALLAtiON FOR AiR OpERAtiON

Controller should normally be installed in horizontal position; 

however, other positions may be used if the supply and control 

connections are parallel with the ground and calibration is 

checked after installation.

iNStALLAtiON FOR WAtER OpERAtiON

Controller should normally be installed in horizontal position with 

drain connection at bottom. For positive drainage at all times, 

drain piping should be 3/8" minimum.

tO CHANgE CONtROLLER ACtiON

(See Figures 6 and 7)
1.  Turn adjusting knob clockwise to remove tension.
2.  Remove adjusting knob and cover.
3.  Remover lever spring retainer (D) and spring (E).
4.  Relocate lever pivots (F).
5.  Turn lever pivots to be snug without binding.
6.  Replace lever spring retainer (D) and spring (E).
7.  Replace cover and adjusting knob.
8. Recalibrate.

Summary of Contents for POWERS Accritem Controller 3

Page 1: ...uthorities for additional local requirements WARNING WARNING Flush all pipes thoroughly before installation Installation and field adjustment are the responsibility of the installer WARNING Need for P...

Page 2: ...nse time Also see Figure 8 on page 7 Figure 1 Operation Instructions n 2 The sensitivity of the Accritem controller is adjusted by turn ing the restriction screw Figure 2 The restriction screw is fact...

Page 3: ...Both Air and Water Controllers To disassemble Refer to Parts Drawing and Figure 5 1 Remove knob 3 after loosening its set screw 2 Remove cover plate 2 3 Remove spring retainer screw 8 and lever sprin...

Page 4: ...ighten the knob set screw very firmly 8 Turn the adjusting knob to the desired control temperature for approximate calibration 9 Recalibrate as required after the controller is installed and connected...

Page 5: ...1 Stainless Steel 10 Cover Screw 030 041 030 041 6 Brass 11 O Ring Not used 047 050 1 Silicone Rubber 12 Retaining Ring 100 124 100 124 1 Phos Bronze 13 Valve 744 155 744 163 1 Phos Bronze 15 Valve Sp...

Page 6: ...744 107 Dotted line item not included Provides materials necessary to reduce the incoming air supply pressure to within the supply pressure range of the Accritem WATER Accessory Kit No 744 180 Dotted...

Page 7: ...e Normally CLOSED valve Hot piped to Normally OPEN port of valve Valve OPENS on air failure Valve CLOSES on air failure Valve opens to HOT flow on air failure REVERSE Acting Normally CLOSED valve Norm...

Page 8: ...on This expresswarranty is in lieu of and excludes all otherwarranties guarantees or representations express of implied There are no impliedwarranties oF merchantability or of fitness for a particular...

Reviews: