Watts Industries POWERS Accritem Controller 3 Technical Instructions Download Page 2

Direct Action Controller

A temperature change in the medium being controlled creates a 

change in length of the sensitive tube 

1

. An increase in tempera-

ture lengthens the sensitive tube  

1

  and moves the Invar rod 

2

 away from the lever 

3

. The lever 

3

, which pivots at Point 

A, is moved to open the exhaust valve 

4

 by spring 

5

. This 

permits the supply (air or water) (S) to increase the pressure in the 

control line (R) and close the normally-open valve. A decrease in 

temperature shortens the sensitive tube 

1

 and moves the Invar 

rod against the lever 

3

. The lever 

3

 moves against the pres-

sure spring 

5

, to open the exhaust valve 

4

. This exhausts the 

pressure in the control line and opens the valve.
The sensitivity adjustment screw 

6

 regulates the rate of flow 

of the supply air (or water) to the controller to a change in tem-

perature. Turning the screw clockwise increases the sensitivity 

by reducing the flow and increasing the response time. Turning 

the screw counterclockwise decreases the sensitivity by 

increasing the flow and reducing the response time.
Also see Figure 8 on page 7.

Figure 1

Operation Instructions 

n

2

The sensitivity of the Accritem controller is adjusted by turn-

ing the restriction screw (Figure 2). (The restriction screw is 

 factory-set for air operation.) For water operation, the restriction 

screw should be opened a minimum of 1/2 turn and controller 

recalibrated. Restriction screw must never be fully closed. Make 

Sensitivity 

n

adjustments slowly, allowing about two (2) minutes after each 

adjustment for the controller to balance.  

Calibration 

n

Set restriction screw for desired sensitivity. Air: 1/8 turn 

from closed (minimum). Water: 1/2 turn from closed 

 (minimum).

Turn adjusting knob until 52 kPa (7-1/2 psi) control pres-

sure shows on gauge. Read temperature at bulb with 

an accurate thermometer.

Loosen set screw and turn adjusting knob to indicate 

temperature at bulb. Tighten set screw. Set controller for 

desired control temperature.

Figure 2

Figure 3

Figure 4

Flowrite Valve

(Normally Open)

Exhaust Air

Tank

A

B

D

C

R

S

4

5

3

2

1

6

Positions “B” and “D” (dotted) show 

pivot point (“B”) and spring when 

controller is 

REVERSE 

acting.

Positions “A” and “C” (solid) show pivot 

point (“A”) and spring when controller is 

DIRECT 

acting.

NOTICE

If sensitivity is changed, controller must be recalibrated.

Summary of Contents for POWERS Accritem Controller 3

Page 1: ...uthorities for additional local requirements WARNING WARNING Flush all pipes thoroughly before installation Installation and field adjustment are the responsibility of the installer WARNING Need for P...

Page 2: ...nse time Also see Figure 8 on page 7 Figure 1 Operation Instructions n 2 The sensitivity of the Accritem controller is adjusted by turn ing the restriction screw Figure 2 The restriction screw is fact...

Page 3: ...Both Air and Water Controllers To disassemble Refer to Parts Drawing and Figure 5 1 Remove knob 3 after loosening its set screw 2 Remove cover plate 2 3 Remove spring retainer screw 8 and lever sprin...

Page 4: ...ighten the knob set screw very firmly 8 Turn the adjusting knob to the desired control temperature for approximate calibration 9 Recalibrate as required after the controller is installed and connected...

Page 5: ...1 Stainless Steel 10 Cover Screw 030 041 030 041 6 Brass 11 O Ring Not used 047 050 1 Silicone Rubber 12 Retaining Ring 100 124 100 124 1 Phos Bronze 13 Valve 744 155 744 163 1 Phos Bronze 15 Valve Sp...

Page 6: ...744 107 Dotted line item not included Provides materials necessary to reduce the incoming air supply pressure to within the supply pressure range of the Accritem WATER Accessory Kit No 744 180 Dotted...

Page 7: ...e Normally CLOSED valve Hot piped to Normally OPEN port of valve Valve OPENS on air failure Valve CLOSES on air failure Valve opens to HOT flow on air failure REVERSE Acting Normally CLOSED valve Norm...

Page 8: ...on This expresswarranty is in lieu of and excludes all otherwarranties guarantees or representations express of implied There are no impliedwarranties oF merchantability or of fitness for a particular...

Reviews: