ABSENCE/VACATION mode of operation 

Time-limited operation of REDUCED TEMPERTURE mode  .  

 

Duration can be set between 1 and 24 hours and up to a maximum of 44 days. Upon expiration of this 

period the Controller switches over to operating mode 

 

 

By means of the arrow keys 

(◄) 

the cursor is first moved to   . Then 

 

appears on the display at 

13

 

The duration of absence can be changed using buttons 

(+)

 or 

(-)

 . 

Example:  

 = 1 hour;  

 = 1 day 

 

Both symbols 

 

and

 

 

start blinking. The remaining time is displayed at 

13

.  

To discontinue this mode of operation before time you have to set the remaining time at 

13 

to 

 using 

the 

(-) 

key. 

 

 

STOP mode 

This mode is used to switch off the system.  

 

The device switches off the system. The Controller software version is indicated on the display for about 3 

seconds and then switches off (no indications).   

 

By pressing any of the keys the Controller can be switched on. 

 

 ATTENTION: When the Controller is switched off the heating system could freeze!  

 

 

6.4 P

ROGRAM MENUS

 

By means of the arrow keys 

(◄) 

and

 

(►)

 you scroll through the program menus. The cursor should be positioned 

on the symbol you wish to select. 

 

 

TIME AND DATE Program menu 

– setting 

In this menu you can set the actual time and date as well as the day of the week. 

 
Using the cursor select   first and then press the 

(OK)

 key. 

By keys 

(+)

 or

 (-) 

set the minutes; confirm by pressing 

(OK).

 

By keys 

(+)

 or

 (-) 

set the hour; confirm by pressing 

(OK)

By keys 

(+)

 or

 (-) 

set the day of the week; press 

(OK) 

to confirm.

 

 

PROGRAMMING menu 

In this menu you choose the program of the Controller (duration of the periods for operation in reduced 

temperature and heating mode), which is to be followed in operating mode 

. You can choose between 

factory set programs from P1 to P9 (

 6.2.1.) and one of the user’s programs from U1 to U4.   

 
First you select   with the help of the cursor. The indication    appears at 

5

. Press the 

(OK)

 key and the 

indication  

 

starts blinking. By the keys 

(+)

 or

 (-) 

now you can select the program you need and confirm it 

by pressing 

(OK)

 

User-defined Programs (U1 

– U4)   

If you choose one of the user programs from U1 to U4, you can program the REDUCED temperature and 

NORMAL heating times directly. Proceed as follows:  

At 

13

 the time indication blinks and day 1 is highlighted, while at 

7

 the time cursor blinks at 0 h on the 

symbol   (heating mode). Pressing the 

(-)

 key you can move the time cursor to the   symbol (REDUCED 

temperature mode). Then the time cursor jumps to the next hour. Thus NORMAL and REDUCED tempera-

ture cycles are selected using the 

(+)

 and

 (-) 

keys. 

 

Using arrow keys 

(◄) 

and

 

(►)

 you can select the time in the same manner.  

 

When day 1 programming is completed the time cursor switches automatically to 0:00h of day 2. Thereby 

the programmed values for day 1 are stored. Programming other days is done using identical procedure 

moving the cursor by pressing 

(►)

. When you switch over to programming the next day the program for 

the previous day is saved. On completing the programming of the last day 7, the indication first switches to 

Summary of Contents for CLIMATIC CONTROL-H

Page 1: ...ge 1 MANUEL D INSTALLATION ET D UTILISATION F R GULATION CLIMATIQUE 3 14 MONTAGE UND BETRIEBSANLEITUNG D HEIZUNGSREGLER CLIMATIC CONTROL 15 25 INSTALLATION AND USER GUIDE GB CLIMATIC CONTROL 26 36 CLI...

Page 2: ...PPLIMP2350Bb page 2...

Page 3: ...N 9 7 MENU INSTALLATION 12 7 1 PARAMETRES D INSTALLATION 12 7 2 COURBES REGULATION 13 8 CARCTERISTIQUES TECHNIQUES 13 9 PROBLEMES ET SOLUTIONS 13 1 APPLICATION Le module de r gulation hydraulique est...

Page 4: ...lation n est pas tanche aux claboussures ou aux projections d eau Il doit donc tre mont dans un endroit sec Pr ter une attention particuli re lors du c blage des sondes n inter changez jamais les conn...

Page 5: ...une patte ou support elle devra alors tre fix e au plus pr s du groupe Pr ter une attention particuli re au placement de la r gulation si elle n est pas mont e sur un groupe hydraulique afin de laisse...

Page 6: ...ferm e dans le cas Ou il n y a pas eu de demande de chauffe du thermostat depuis 30 minutes Ou la vanne m langeuse est en position ferm e depuis 30 minutes Aucune demande d eau chaude suppl mentaire d...

Page 7: ...t en posi tion 5 et 13 sur l afficheur les valeurs affich es sont moyenn e En appuyant sur OK vous pourrez visualiser la temp rature d eau th orique fonction de la courbe en 5 ainsi que la valeur du d...

Page 8: ...K vous pourrez visualiser la temp rature d eau th orique fonction de la courbe en 5 ainsi que la valeur du d calage de courbe ajout e cette temp rature en 13 Valeur usine 10 0 pas de d calage Vous pou...

Page 9: ...pouvez parcourir les jours de la semaine avec les touches et afin de visualiser le pro gramme Programmes Utilisateur U1 U4 Si vous choisissez un des 4 programmes utilisateurs vous serez invit le cr er...

Page 10: ...n du programme si aucune touche n est press e durant 20 secondes la r gulation revient l cran d accueil du mode Programme si vous attendez encore 15 secondes elle reviendra sur le mode AUTOMATIQUE et...

Page 11: ...ammes sont suivis uniquement dans le mode AUTO Le programme ne fait qu osciller entre le mode CONFORT et ECO Du fait si des d calages de courbe ont t rentr s dans les modes CONFORT et ECO ils seront a...

Page 12: ...re d eau sera fix e 25 C pour les 3 premiers jours 7 6 5 La temp rature d eau sera fix e la valeur max ajust e en Hi pour les 4 jours restants 4 3 2 1 Valeur de l offset ajout en cas d utilisation d u...

Page 13: ...d part d eau V rifier les connections et le c ble Remplacer le c ble ou la sonde si n cessaire 2 Temp ratures 2 1 Temp rature de d part d eau trop chaude la vanne m langeuse est invers e V rifier le c...

Page 14: ...PPLIMP2350Bb page 14 F...

Page 15: ...S 17 5 3 RAUMTEMPERATUR AUFSCHALTUNG 18 6 BETRIEBSARTEN PROGRAMM MEN 19 6 1 BETRIEBSARTEN 19 6 2 PROGRAMM MEN S 20 6 2 1 VERLAUF DER HEIZ UND ABSENKZEITEN DER WERKSPROGRAMME P1 P9 21 7 SYSTEM PARAMETE...

Page 16: ...sbestimmungen vor allem die VDE 0100 einzuhalten Der Regler ist nicht spritz und tropfwassergesch tzt Montieren Sie diesen daher an einem trockenen Ort Es ist darauf zu achten dass die F hleranschl ss...

Page 17: ...verbunden dann erfolgt die Montage in unmittelbarer N he dieser Einheit Soll der Regler aus Gr nden der besseren Zug nglichkeit an anderer Stelle als direkt bei einer Regelstation mon tiert werden da...

Page 18: ...r Anpassung Beispiel 1 Sollwert Vorlauftemp 35 C Raumtemp Sollwert 21 C Istwert 19 C offset 1 5 Berechnung 1 35 C 21 C 19 C 1 5 Vorlauftemperaturerh hung um 3 0 K auf 38 C Beispiel 2 Sollwert Vorlauft...

Page 19: ...senkbetrieb und liegt die Vorlauftemperatur vom WE unter der vom Heizungsregler berechneten Solltemperatur ist folglich kein Heizbetrieb m glich Gleichwohl l uft allerdings die Umw lzpumpe und das 2 3...

Page 20: ...ahl des Regler Programms Zeitverlauf der Absenk und Heizzeiten wel ches in der Betriebsart ausgef hrt wird Zur Auswahl steht entweder eines der werkseitig festgelegten Programme P1 bis P9 6 2 1 oder e...

Page 21: ...mme P1 P9 Der Regler arbeitet nur in der Betriebsart nach den gew hlten Heiz und Absenkzeiten W hrend der Heizzeiten erfolgt die Vorlauf Temperaturregelung anhand der gew hlten Heizkurve und der aktue...

Page 22: ...Cursor auf danach 10 Sekunden gedr ckt halten Im System Parameter Men 7 dry anw hlen und mit auf 0 dry ndern und mit OK best tigen Wert zur Vorlauftemperatur Anpassung Nur in Funktion falls ein Funk R...

Page 23: ...inimalwert auf 34 C W hrend der Belegreif Heizphase den Regler in der Betriebsart NORMAL fahren Informationen zum Belegreifheizen bietet beispielsweise der Bundesverband Fl chenheizung und Fl chenk hl...

Page 24: ...2 2 Vorlauftemperatur zu gering wegen falsch ange schlossenem 3 Punkt Antrieb Wirksinn verkehrt Anschluss des Antriebs an den Regler berpr fen 5 2 2 3 Verkehrte Betriebsart gew hlt Betriebsart richti...

Page 25: ...PPLIMP2350Bb page 25 D...

Page 26: ...27 3 SAFETY INSTRUCTIONS 27 4 DISPLAY 27 5 INSTALLATION AND ELECTRIC CONNECTIONS 28 5 1 CONTROLLER INSTALLATION 28 5 2 ELECTRIC CONNECTIONS 28 5 3 ROOM TEMPERATURE DIRECT PLUG IN 29 6 TYPES OF OPERAT...

Page 27: ...tions of nominal voltages 1000 VAC The controllers are neither splash nor drip proof Therefore they must be mounted at a dry place Do not interchange the connections of the sensors and the 230V conne...

Page 28: ...FRG or FlowBox and if it is not attached to that unit by any installation plate or support it should be installed next to that unit Pay attention to the correct connection of the cables if the Control...

Page 29: ...temperature Example 1 preset value of flow temperature 35 C room temperature preset value 21 C actual value 19 C offset 1 5 Estimation 1 35 C 21 C 19 C 1 5 K flow temperature increased by 3 0 K to 38...

Page 30: ...y the WE is below the preset temperature calculated by the Controller heating mode is not available However if the circulation pump is actually running and the 2 3 way valve may also be opened by the...

Page 31: ...m by pressing OK By keys or set the day of the week press OK to confirm PROGRAMMING menu In this menu you choose the program of the Controller duration of the periods for operation in reduced temperat...

Page 32: ...rom P1 to P9 you confirm it by pressing the key Then pressing the arrow key scroll back to the menu for selecting an operation mode if the arrow key is not pressed in about 15 seconds the display turn...

Page 33: ...ntroller operates only in mode according to the selected NORMAL and REDUCED temperature periods During NORMAL periods the flow temperature is controlled on the basis of the chosen heating curve and th...

Page 34: ...intained at its preset maximum value days 4 3 2 1 Value for adjustment of the flow temperature Functional only if RF thermostat is available The flow temperature is adjusted by this value depending on...

Page 35: ...t control automatic detection of operating point Electrical protection Class II IP 30 Supply voltage 230 V 10 50 Hz Outputs pump 3 point control 5 A 250 V relay L N PE 2 TRIACS 75 W max Sensor outside...

Page 36: ...orrectly con nected valve drive reverse action Check the connection of the valve drive 5 2 2 3 Incorrect selected operation mode Select the correct mode of operation 2 4 When Controller operating in A...

Page 37: ......

Page 38: ...www wattsindustries com...

Reviews: