                  FAN-COIL 4T 

Electronic Controller

 

 
 
 

 

Fig. 1 

 
 
 
 

 

 

Fig 2. 

 

 

Fig.3 

 

 

Fig.4 

 

Fig 5. 

Safety warnings and operating instructions 

 
• This product should be installed preferably by a qualified professional. Subject to observation of the 
above  terms,  the  manufacturer  shall  assume  the  liability  for  the  equipment  as  provided  by  legal 
stipulations. All instructions in this 
Installation & Operation manual should be observed when working with the controller. 
• Failures due to improper installation, improper use or poor maintenance are voiding manufacturer 
liability 
• Any attempt to repair voids the responsibility and the obligation to guarantee and replacement from 
the manufacturer. 
 

 
Product description: 

 

FAN-COIL  CONTROLLER  4T

:  Fan-coils  electronic  controller  suitable  for  models  equipped  with 

double heat exchanger (4-pipes plants), 3-speeds asynchronous electric motor connected to the fan, 
ON/OFF type valves, SUMMER/WINTER switch either manual or automatic (on the basis of the air 
temperature), ventilation consent on the basis of the water temperature (if necessary). 
 
 

Operating instructions and legend (Fig.1): 
 

 

– Two steps ON/OFF button 

OFF mode 

ON mode with manual ventilation  

 

 

– Manual ventilation switch (minimum, middle, maximum speed) 

 

– Blue and red warning  

Led is permanently blue: fan coil is in cooling mode 
Led is permanently red: fan coil is in heating mode 
Red led is blinking: water temperature is too low to heat 
Both red and blue led blinking: temperature probe is faulty or disconnected 

 

– Control knob for temperature setting from 5 to 35 °C 

 

– Manual switch mode 

SUMMER/COOLING 

WINTER/HEATING 

 
 

Wall mounting instructions: 

 
Install the controller in an easily accessible area suitable for functions setting and efficient for room 
temperature detection (at least 1.5 m from the floor). Therefore, avoid: 
• direct sunlight exposure 
• direct exposure to hot or cold air currents 
• placing obstacles which impair correct temperature detection (curtains or furniture); 
• the constant presence of water vapour (kitchens, etc.) 
• covering or recessing the controller into the wall. 
Please, respect the following instructions (Fig.2) 
• remove the controller temperature setting knob 
• remove the controller closing screw 
• pass the cables through the slots on the base and fasten the controller with the reserved holes 
• close the controller back up using the closing screw and insert again the temperature setting knob 
 

Electrical connections: 

 
All of the operations must be carried out by qualified staff, in accordance with regulations in force. 
For any electrical related procedure, refer to the electrical diagrams attached to this documentation. 
We  also suggest  making  sure  that the  characteristics  of  the  electrical  network  are suitable for the 
absorption levels reported in the electrical data table. Before carrying out any operation on electrical 
parts, make sure the power supply is disconnected. Check that the net voltage is compatible with the 
specifications of the unit (voltage, number of phases, frequency) shown on the unit rating plate. The 
supply  voltage  must  not  fluctuate  by  more  than  ±5%  in  relation  to  the  rated  value.  The  electrical 
connections must be set up according to the electrical diagram attached to the specific unit and with 
the regulations in force. 
 

Operating and adjustment setting  

 
On the electric circuit of the controller there are electric devices able to modify three different settings: 

•  REMOTE  jumper  used  to  specify  the  position  of  the  air  probe  on  the  basis  of  which  the 
controller  makes  the  adjustment.  The  two  possibilities  are  on  board  probe  (factory  default 
setting) or remote wired probe (Fig. 3). 
• AUTO jumper to specify how the changeover (SUMMER/WINTER) is supposed to be applied 
by the controller). The two possibilities are the manual selection (factory default setting) or the 
automatic changeover on the basis of air temperature (Fig. 3). 
• Potentiometer for the hysteresis calibration (from 1°C to 10°C) around the temperature SET 
for  the  automatic  SUMMER/WINTER  changeover,  we  suggest  not  to  modify  this  value  if  not 
strictly  necessary,  for  example  as  a  consequence  of  a  quick  and  large  variation  of  the  air 
temperature (Fig. 3) 
 

 

Adjustment logics: 
 

The thermostat operation (either cooling or heating) takes place with a difference of 0,2°C from the 
set point of the controller (Fig. 4). The thermostat switches on the fan and opens the valve (if any). 
Ventilation is activated (limited to 2 minutes every 8 minutes) and forced without a real necessity only 
with  the  following  setting:  cooling  mode  and  remote  air  probe;  this  is  due  to  the  fact  that  in  this 
situation a good air temperature detection is possible only if the air is periodically moved. 
The water consent to ventilation (only if the water probe is connected) is driven by the activation and 
deactivation logic reported in figure 5. 
 
 

Technical data: 
 

Power supply 

230 V - 50/60Hz 

IP rating 

IP30 

Exit relay 

6(2)A/250V 

Temperature probes 

NTC 10K Ohm @25°C 

Electric class of protection WAT FAN 
COIL CONTROLER 2T and 4T 

II 

Dimensions 

125 x 75 x 32 mm 

EU Declaration of conformity 
Hereby, Watts Electronics declares 
that the equipment is in compliance 
with the relevant Community 
harmonisation legislation: 

•Directive 2001/95/EC on 
General   Products Safety 
• Low Voltage Directive 
2014/35/EU  
• RoHS Directive 2015/863 

Weight 

0.162kg 

 

The full text of the EU declaration of conformity is available by written request t

https://wattswater.eu

  

 

 
Wiring diagram 
 

 

 

Neutral 

Neutral fan speed 

Live 

Neutral heating actuator 

Heating/cooling actuator.  9 

Neutral cooling actuator 

Minimum fan speed 

10 -11  Water probe (Option) 

Medium fan speed 

12- 13  Air probe (Option) 

Maximum fan speed 

C1 

Two steps ON/OFF button

 

C2 

Manual ventilation switch

 

C5 

Control knob for temperature 
setting 

 
 
Displosal and recycling information: 

 

 

2012/19/EU (WEEE directive): Products marked with this symbol cannot be disposed of 
as  unsorted  municipal  waste  in  the  European  Union.  For  proper  recycling,  return  this 
product to your local supplier upon the purchase of equivalent new equipment, or dispose 
of it at designated collection points. For more information see

www.recyclethis.info

  

 