Call 800.879.8585 for Technical Support
WIRING DIRECTIONS
WARNING
TURN POWER OFF AT THE CIRCUIT BREAKER BEFORE
INSTALLING POWER PACKS, SWITCHES OR SENSORS.
Each WattStopper BZ series power pack can supply power for 5 DT-305 sensors. When
using more sensors than this, multiple power packs are required.
Refer to the wiring diagram on the next page for the following procedures:
Connect the
low voltage:
• RED wire (+24VDC) from power pack to the
+24V
terminal on the sensor.
• BLACK wire (Return) from power pack to
Common
terminal on the sensor.
• BLUE wire from power pack to
Control Out
terminal on sensor.
To add a MANUAL SWITCH
such as the LVSW Momentary Toggle Switch, or RS2-3 Low
Voltage Momentary Switch to the above applications (see wiring diagram “Manual-On
wiring with low voltage momentary switch”) – connect:
• Wire from one side of switch to
+24V
terminal on sensor.
• Wire from other side of switch to
Man Switch
terminal on sensor.
Wiring the ISOLATED RELAY:
The Isolated Relay is rated for 1A@30VAC/VDC. Connect the wires necessary to the application that requires
this output:
• Relay Com
mon (must be used for proper operation)
• N.O.
(Normally Open)–Closed when occupancy is detected
• N.C.
(Normally Closed)–Open when occupancy is detected
CONNECTING WIRES
• Care should be taken to separate high voltage power from low voltage (Class 2) control wiring.
• All connections to sensor are low voltage, Class 2.
Control Out.
Man. Switch
+24V
Common
DT-305
360
°
Dual Technology
Occupancy Sensor
U.S.Patents:
5,640,113
Patent Pending
PIR & 40kHz Ultrasonic
+24VDC/VAC
Connect to WattStopper
Class 2 Power Packs
For Indoor Use Only
02829r4
C US
LISTED
88T9
Appliance
Control
www.wattstopper.com
800.879.8585
v3
Wiring terminals
Load #1
Load #2
(Optional)
DT-305
Standard wiring with local off switch
Rear Housing
Depluggable
Terminal
Front Cover
Ceiling
Spring Clips (2)
Blue
Control Out
+24V
Common
Low Voltage
Class 2
Line
Voltage
Line
Neutral
Feed Through
Power Pack
Black
Red
#1
#2
Line Voltage
Switches
White
Black
Red
Line Voltage
Wire Color Legend
Standard wiring with local off switch
LVSW
Load
Rear Housing
Depluggable
Terminal
Front Cover
Ceiling
Spring Clips (2)
Blue
Control Out
Black
+24V
Low Voltage
Class 2
Line Voltage
Line
Neutral
Feed Through
Power Pack
Man.Switch
Red
DT-305
Manual-On wiring with low voltage momentary switch
Common
For low voltage
momentary switch
use trigger option
6 or 7
Man.Switch
+ 24V
Jumper
Back
of
LVSW
White
Black
Red
Line Voltage
Wire Color Legend
Manual-On wiring with low voltage momentary switch
MOUNTING THE SENSOR
Directly to Ceiling
1. Attach the plastic spring clips to the edge of the sensor in the slots provided.
2. Cut a 3.5” to 4” round hole in the acoustic ceiling tile at the mounting location. A 3.5” hole is
recommended for a secure fit.
3. Pull the low voltage wire from the power pack to the sensor through the hole.
4. Connect the low voltage wires to the appropriate terminals on the sensor.
5. Push the sensor up through the hole until the Spring Clips hold the sensor securely in place.
6. Snap the front cover onto the sensor.
Using an Octagonal J-Box
1. Pull the low voltage wires from the power pack into the J-Box through the conduit knockout.
2. Connect the low voltage wires to the appropriate terminals on the sensor.
3. Loosen the appliance mounting screws attached to the J-Box
4. Align the sensor in the J-Box so that the mounting screws on the box match the key holes
on the sensor’s rear housing.
5. Push the sensor up into the J -Box and twist it so that the mounting screws are seated in the
keyhole slots.
6. Tighten the two screws to secure the sensor to the J-Box.
7. Snap the front cover onto the sensor.
Rear
housing
Front
cover
Ceiling
Spring clips (2)
Depluggable terminal
Ceiling Mount
Depluggable terminal
Rear
Housing
4" Octagonal J-Box
(at least 1.5" deep)
Front
Cover
Ceiling
Screws
J-Box Mount