Watson McDaniel 455 SERIES Installation & Operating Instructions Download Page 1

   

SERIES 455-SCREWED

DIAPHRAGM ASSY

 DIAPHRAGM*
 DIAPHRAGM WASHER
 DIAPHRAGM CASE NUTS
 & BOLTS

PACKING ASSY

 PACKING*
 PACKING NUT
 SPRING

BOTTOM PLUG

VALVE BODY

MAIN VALVE ASSY

 MAIN VALVE
 MAIN VALVE SEAT
 PILOT VALVE & STEM
 PILOT VALVE STEM NUT

DIAPHRAGM STEM

STEM

BOTTOM DIAPHRAGM CASE

REGULATING SPRING

TOP DIAPHRAGM CASE

VALVE BRACKET

BRACKET LOCKNUT

VALVE BONNET

FLOW

SERIES 455-FLANGED

TOP DIAPHRAGM CASE

DIAPHRAGM ASSY

 DIAPHRAGM*
 DIAPHRAGM WASHER
 DIAPHRAGM CASE NUTS
 & BOLTS

BOTTOM DIAPHRAGM CASE

REGULATING SPRING

SPRING YOKE

PACKING ASSY

 PACKING*
 PACKING NUT
 PACKING GLAND

STEM LOCK NUT

STUDS & NUTS

TOP

PLATE

TOP

PLATE

GASKET*

REGULATING NUTS

DIAPHRAGM STEM ASSY
 DIAPHRAGM STEM
 DIAPHRAGM WASHER

MAIN VALVE ASSY

 MAIN VALVE
 MAIN VALVE SEAT
 PILOT VALVE & STEM
 PILOT VALVE STEM NUT

BOTTOM PLUG

VALVE BODY

B Y-PA SS 

RELIEF
VA LV E

TYPICAL INSTALLATION

10 PIP E DIA ME TE RS MIN.

455

RE GULATIN G

VA LVE

LINE

NE EDLE
VA LVE

STRAINE R

STEA M
SU PPLY

I

NSTALLATION AND 

O

PERATION

 

 

Before installing the pressure regulating valve, be sure to blow out the 

pipe line to remove all dirt, pipe scale, pipe chips, etc. 

 

Watson McDaniel recommends a 'Y' type strainer be placed in the line on 
the inlet side of the pressure regulating valve.  A bypass line and hand 

shut off valves and gauges should be in stalled on either side of the 

regulating valve as shown in sketch. 

 

Install the Series 455 pressure regulating valve in a straight horizontal run 

of pipe away from any meters, tees, elbows, etc. which would cause flow 

turbulence and effect regulation.  The flow should be in the direction of 

the arrow on the body with the diaphragm chamber above the center line 

of the pipe.  However, if head room is scarce, the second best position is 
to install the valve in an inverted orientation with the diaphragm chamber 

below the center line of the pipe.. 

 

WARNING:  The Series 455 valve should not be installed in a vertical run 

of pipe as the weight of the parts will cause increased wear and 

subsequently shorten the life of the valve. 

 

Connect a control line from the top of the diaphragm chamber to the top 
of the piping on the downstream side of the valve. The control line should 

be installed approximately 10 pipe diameters downstream of the valve in a 

straight run of pipe away from any flow turbulence.  A needle valve should 

be installed in this control line for the purpose of dampening the response 

of the valve if required. 

 

On start-up check to see that the by-pass valve is closed and the 

downstream pressure gauge is reading zero.  The upstream pressure 

gauge should indicate the line pressure, and the hand valves on 

the inlet and outlet side of the pressure regulating valve should 

be full open before adjusting downstream pressure. 
 

The Series 455 pressure regulating valves are diaphragm 

actuated, spring loaded and are normally open.  Increasing the 

spring compression results in a higher downstream pressure, 

while decreasing the spring compression reduces the down 

stream pressure.  On start up, slowly increase downstream 

pressure (on steam wait for the pipe to heat and expand) until 

the desired pressure is reached. 
 

This instruction sheet is intended as general information and is 

not to be interpreted as specific information on any particular 

application.  If, after reading the above instructions, you are 

uncertain as to the product's adaptability for your application, 

please call factory or authorized representative before installing 

or using product. 

*Recommended Spare Parts 

*Recommended Spare Parts 

 

 
 
                                                                                                                                                                     
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

428 Jones Boulevard 

Limerick Airport Business Center 

Pottstown, PA 19464 

Phone: (610)495-5131 

Fax: (610)495-5134 

www.watsonmcdaniel.com 






 

INSTRUCTION PART NO. 2227900 

REVISION 3 

Each  Watson  McDaniel  Company  Product  is  warranted  against  defects  in  material  and  workmanship  for  one  year from  date  of  shipment.    This  warranty 
extends to the first retail purchaser only.  All defective material must be returned to the person from whom you purchased the Product, transportation prepaid, 
free of any liens or encumbrances, and if found to be defective will be repaired free of charge or replaced, at the warrantor's or seller's option.  If the material 
is  replaced,  any  replacement  will  be  invoiced  in  the  usual  manner  and  after  inspection  of  alleged  defective  material  an  adjustment  will  be  made  for 
depreciation caused by purchaser's use.  In no event will Watson McDaniel Company be liable to do more than refund the original contract price. Incidental 
and  consequential  damages  are  excluded,  whether  under  this  warranty  or  otherwise.    All  implied  warranties,  including  warranties  of  merchantability

 

and 

fitness for a particular purpose, are disclaimed and excluded. 

PAGE 37 