Wa t l o w P o w e r S e r i e s
P a r a m e t e r s
■
6 . 2 1
NOTE: For more information about how parameter settings affect the controller’s operation, see Chapter Five, Features.
✔
NOTE: The values entered in the preceding prompts are used with the corresponding analog to digital
counts. The parameter
[`Err]
will be displayed if the calibrations fails; otherwise the parameter will
return to
[idle]
.
Active if in factory mode.
5415 r/w [1]
5425 r/w [2]
5435 r/w [3]
[idle]
cali-
bration
inactive (0)
[`Err]
invalid calibra-
tion (-1)
[idle]
calibration
inactive (0)
[`req]
enables cali-
bration request (1)
[CALA]
Calibrate Analog
Input Request
Request analog
input signal calibra-
tion.
Active if in factory mode.
5414 r/w [1]
5424 r/w [2]
5434 r/w [3]
[(000]
(9000)
[Uol_]
to
[(999]
(Low V Cal Point to
9999)
[Uol–]
High V Cal Point
Sets the high voltage
value for the corre-
sponding analog
input calibration.
Active if in factory mode.
5413 r/w [1]
5423 r/w [2]
5433 r/w [3]
[!000]
(1000)
[)000]
to
[UOL–]
(0 to High V Cal
Point)
[Uol_]
Low V Cal Point
Sets the low voltage
value for the corre-
sponding analog
input calibration.
*
NOTE: The display prompts are set to two decimal places because of the resolution of the display.
The comms registers are set and stored with three decimal places of resolution.
Active if in factory mode.
5412 r/w [1]
5422 r/w [2]
5432 r/w [3]
[1^00]
(16000)
[nna_]
to
[2)00]
(Low mA Cal Point to
20000)*
[nna–]
High mA Cal Point
Sets the high current
value for the corre-
sponding analog
input calibration.
Active if in factory mode.
5411 r/w [1]
5421 r/w [2]
5431 r/w [3]
[$000]
(4000)
[)000]
to
[nna–]
[or
[(999]
whichever is
smaller]
(0 to High mA Cal
Point [or 9999])
[nna_]
Low mA Cal Point
Sets the low current
value for the corre-
sponding analog
input calibration.
[CIn1] [CIn2] [CIn3]
Calibrate Analog Input Signal Zones 1, 2, and 3 Menus
[Fcty] [Fcty]
[Fcty]
Factory Page
This menu is used to set up the analog inputs.
Input 1 is used if Input/Output Configuration is single phase, single zone or three phase.
Input 1 and Input 2 are used if Input/Output Configuration is single phase, two zones.
All zones are used if Input/Output Configuration is single phase, three zones.
NOTE: Care should be taken to allow a buffer between each of the settings and their respective hardware
limits to prevent unexpected operation because of noise or signal variations.
Display
Parameter
Range
Default
Modbus
Conditions for
(Modbus Value)
Address
Parameters to Appear
read/write
Summary of Contents for PC1X-N20
Page 4: ...ii Watlow Power Series Table of Contents...
Page 72: ......