Watlow Din-a-mite User Manual Download Page 1

1241 Bundy Boulevard, Winona, Minnesota USA 55987

Phone: +1 (507) 454-5300, Fax: +1 (507) 452-4507

http://www.watlow.com

Please consult this user’s manual when you place your new
DIN-A-MITE in service. It contains all the  necessary
information to mount and wire it into the  application. This
manual also contains all  pertinent specifications and
semiconductor  fusing recommendations. Please refer to
 national and local electrical code safety guidelines whenever
you install electrical equipment.

This DIN-A-MITE product is capable of switching up to 100
amperes single-phase, at 600V

Å

(ac) at 30°C (86°F),

depending on the model selected. It is electrically touch-safe
and includes standard back-panel mounting, on-board
semiconductor fuses, and a current transformer option for
 external load current monitoring. Shorted SCR alarm output
option is also available.

The DIN-A-MITE Style D mounting footprint matches that of

an industry-standard 100-amperes mercury displacement
relay. This DIN-A-MITE is CE-approved, UL

®

508-listed and

C-UL

®

.

0600-0025-0013 Rev J

January 2016

DIN-A-MITE

®

Style D

Solid-State Power Controller

User’s Manual

Thermal Devices, Inc. Mount Airy, Maryland USA www.thermaldevices.com

Thermal Devices, Inc. Mount Airy, Maryland USA www.thermaldevices.com

Summary of Contents for Din-a-mite

Page 1: ...witching up to 100 amperes single phase at 600V ac at 30 C 86 F depending on the model selected It is electrically touch safe and includes standard back panel mounting on board semiconductor fuses and...

Page 2: ...to 19 7mA Temperature stability is less than 0 15 C change Alarm Shorted SCR Alarm Option Alarm state when the input command signal off and a 15A or more load current is detected by the current transf...

Page 3: ...User s Manual 3 3 5 203 mm 8 00 in 203 mm 8 00 in clearance for air flow and bending radius 203 mm 8 00 in 203 mm 8 00 in clearance for air flow and bending radius 178 mm 7 00 in 185 mm 7 28 in 13 mm...

Page 4: ...G Only authorized and qualified personnel should be allowed to install and perform preventive and corrective maintenance on this unit Failure to do so could result in damage to equipment and personal...

Page 5: ...MITE alarm option provides an alarm output for shorted SCR conditions A shorted SCR alarm is detected when there is no command signal and a load current is detected The alarm output is then energized...

Page 6: ...age Dips Short Interruptions and Voltage Variations EN 61000 3 2 2009 Harmonic Current Emissions Reviewed to IEC 61000 3 2 2014 EN 61000 3 3 2013 Voltage Fluctuations and Flicker3 16A EN 61000 3 11 20...

Page 7: ...rs and medical alert systems Verify that suppressed carrier current or other desirable communications on power lines creates no hazard to people or property Failure to observe this warning could resul...

Page 8: ...you can get technical assistance from your local Watlow representative or in the U S dial 1 507 454 5300 For technical support ask for for an Applications Engineer Please have the following informatio...

Page 9: ...nited Kingdom Tel 44 115 964 0777 Fax 44 115 964 0071 Asia and Paci c Watlow Singapore Pte Ltd 16 Ayer Rajah Crescent 06 03 04 Singapore 139965 Tel 65 6773 9488 Fax 65 6778 0323 Email info watlow com...

Reviews: