D8 Series User’s Guide
Chapter 3: Communicating by DeviceNet
53
ATTRIBUTE
ACCESS
NAME
TYPE
DESCRIPTION
14 (E hex)
Get
Produced
Connection Path
EPATH
Specifies the Application Object(s)
whose data is to be produced by this
Connection Object.
15 (F hex)
Get
Consumed
Connection Path
Length
UINT
Number of bytes in the Consumed
Connection Path Length
16 (10 hex)
Get
Consumed
Connection Path
EPATH
Specifies the Application Object(s) that
are to receive data consumed by this
Connection Object.
Input Object
The Input Object provides read/write access to all input parameters. Instance 0 of this object
contains the class attributes listed in Table 3.17. The four-loop controller has four additional
instances, and the eight-loop controller has eight additional instances, each containing the attributes
listed in Table 3.18. Instance 1 corresponds to loop 1, instance 2 corresponds to loop 2, and so on.
Table 3.16
– Input Class and Services
Class Code
64 hex
Class Services
0E hex Get Attribute Single
Instance Services
0E hex Get Attribute Single
10 hex Set Attribute Single
Table 3.17
– Input Class Attributes (Instance 0)
ATTRIBUTE
ACCESS
NAME
TYPE
DESCRIPTION
1 (1 hex)
Get
Revision
UINT
Revision of this object
2 (2 hex)
Get
Max instance
UINT
Maximum instances of this object (8)
3 (3 hex)
Get
Number of instances
UINT
Number of object instances
Table 3.18
– Input Instance Attributes (Instances 1 to 4 or 8)
ATTRIBUTE
ACCESS
NAME
TYPE
DESCRIPTION
100 (64 hex)
Get/Set
Set Point
INT
101 (65 hex)
Get
Process Variable
INT
102 (66 hex)
Get/Set
Input Type
SHORT_STRING
103 (67 hex)
Get/Set
Loop Name
SHORT_STRING
104 (68 hex)
Get/Set
Input Units
Array of 3 USINT
105 (69 hex)
Get/Set
Calibration Offset
INT
106 (6A hex)
Get/Set
Reverse Thermocouple Detection
BOOL
107 (6B hex)
Get/Set
Display Format
USINT
108 (6C hex)
Get/Set
Input Range High
INT
109 (6D hex)
Get/Set
Input Range Low
INT
110 (6E hex)
Get/Set
Input High Signal
INT
111 (6F hex)
Get/Set
Input Low Signal
INT
112 (70 hex)
Get/Set
Input Filter
USINT