Active if Output 4 is equipped for
communications (96 _ _-_ _ _ R-
_ _ _ _ or 96 _ _-_ _ _ U-_ _ _ _)
and Setup Page Lock (Lockout
Menu) is not set to
[hide]
.
none*
[9600]
[1200]
1200
[2400]
2400
[4800]
4800
[9600]
9600
[1(20]
19.2K
[bAUd]
Baud Rate
Sets
communications
baud rate.
Active if Output 4 is retransmit
(97 _ _-_ _ _ M-_ _ _ _), and
Analog Output 4 (Output 4
Menu) is set to
[`yes]
and
Setup Page Lock (Lockout
Menu) is not set to
[hide]
.
none*
0
-1999 to 9999
[ACAL]
Analog Output
Offset
Sets analog output
offset.
Active if Output 4 is equipped for
retransmit (97 _ _-_ _ _ M-_ _ _ _),
and Analog Output 4 (Output 4
Menu) is set to
[`yes]
and
Setup Page Lock (Lockout
Menu) is not set to
[hide]
.
none*
999
Analog Range Low to
9999
[A`hi]
Analog Output
High
Sets analog output
range high scaling.
Active if Output 4 is equipped for
retransmit (97 _ _-_ _ _ M-_ _ _ _),
and Analog Output 4 (Output 4
Menu) is set to
[Proc]
and
Setup Page Lock (Lockout
Menu) is not set to
[hide]
.
none*
-999
-1999 to Analog Range
High
[A`Lo]
Analog Output
Low
Sets analog output
range low scaling.
Active if Output 4 is equipped for
retransmit (97 _ _-_ _ _ M-_ _ _ _)
and Setup Page Lock (Lockout
Menu) is not set to
[hide]
.
none*
[4-20]
[4-20]
4-20 mA
[0-20]
0-20 mA
[0-`5]
0-5V
Î
(dc)
[1-`5]
1-5V
Î
(dc)
[0-10]
0-10V
Î
(dc)
[Prc4]
Process 4 Type
Sets process 4 out-
put type.
Active if Output 4 is equipped for
retransmit (97 _ _-_ _ _ M-_ _ _ _)
and Setup Page Lock (Lockout
Menu) is not set to
[hide]
.
none*
[proc]
[``no]
not active
[proc]
process
[Aout]
Analog Output 4
Selects output 4
retransmit signal.
Active if Output 4 is equipped for
a relay (97 _ _-_ _ _ D-_ _ _ _),
Output 4 is Set to
[``AL]
(Alarm) and Setup Page Lock
(Lockout Menu) is not set to
[hide]
.
none*
[`yes]
[``no]
no
[`Yes]
yes
[Anu4]
Alarm
Annunciation 4
Selects alarm 4
annunciation option.
Active if Output 4 is equipped for
a relay (97 _ _-_ _ _ D-_ _ _ _),
Output 4 (Output 4 Menu) is
set to
[``AL]
(Alarm) and
Setup Page Lock (Lockout
Menu) is not set to
[hide]
.
none*
[al`0]
[al`0]
alarm condition
de-energizes output
[al`C]
alarm condition
energizes output
[Lgc4]
Alarm Logic 4
Selects alarm 4
output condition in
alarm state.
Wa t l o w S e r i e s 9 7
P a r a m e t e r s
■
6 . 1 3
Setup Page / Output 4 Menu
Display
Parameter
Range
Default
Modbus
Conditions for
Address
Parameters to Appear
read/write
NOTE: For more information about how parameter seetings affect the controller’s operation, see Chapter Five, Features.
*Output 4 parameters cannot
be changed with the Modbus
interface.