Appendix
36
WATLOW Series 945 User's Manual
0-5V/4-20mA Input
NOTE:
Before calibration on
an installed control,
make sure all data
and parameters are
documented. See
Setup and Operation
Tables, Pages 18
and 20.
IMPORTANT:
When the MANUAL
LED is ON the unit is
automatically
calibrating. Your
sequence is
VERY important.
Always move to the
next prompt before
changing the
calibration
equipment.
0 - 5 Volt Input Field Calibration Procedure
Equipment Required:
•
Precision voltage source 0-5 volt minimum range with 0.001 volt resolution.
Setup And Calibration
1.
Connect the AC line voltage L1, L2, and ground to the proper terminals on the 945.
2.
Connect the voltage/current source to Terminal #1 and #3 on the Series 945 terminal
strip. Use regular 20 - 24 gauge wire.
3.
Apply power to the unit and allow it to warm up for 15 minutes. After warm-up put the
unit in the CAL menu. See Page 32. Press the MODE key until OU is displayed.
4.
Press AUTO/MAN twice to enter the MANUAL mode. The unit is calibrating when the
MANUAL LED is ON. Make sure the unit is in the MANUAL mode only when you are
in the correct parameters. See Figure 41.
5.
At the OU parameter, set the voltage/current source to 0.000volts. Allow at least 10
seconds to stabilize. Press the MODE key.
6.
At the 5U parameter, set the voltage/current source to 5.000 volts. Allow at least 10
seconds to stabilize. The unit leaves the CAL mode if 1 minute passes between key
activations. Press AUTO/MAN twice to exit the MANUAL mode. To conclude the 0-5
Volt calibration, advance the MODE key to the next prompt or exit the CAL menu.
4-20mA Input Field Calibration Procedure
Equipment Required:
•
Precision current source 0-20mA minimum range with 0.01 mA resolution.
Setup And Calibration
1.
Connect the AC line voltage L1, L2, and ground to the proper terminals on the Series
945. Jumper for correct line voltage. See Chapter 2.
2.
Connect the voltage/current source to Terminal #1 and #3. Jumper Terminal #2 to #3
on the Series 945 terminal strip. Use regular 20 - 24 gauge wire.
3.
Apply power to the unit and allow it to warm up for 15 minutes. After warm-up put the
unit in the CAL menu. See Page 32. Press the MODE key until 4A is displayed.
4.
Press the AUTO/MAN key twice to enter the MANUAL mode. The unit is calibrating
when the MANUAL LED is ON. Make sure the unit is in the MANUAL mode only when
you are in the correct parameters. See Figure 41.
5.
At the 4A parameter, set the mA source to 4.00mA. Allow at least 10 seconds to
stabilize. Press the MODE key.
6.
At the 20A parameter, set the voltage/current source to 20.00mA. Allow at least 10
seconds to stabilize. The unit leaves the CAL mode if 1 minute passes between key
activations. Press AUTO/MAN twice to exit the MANUAL mode. To conclude,
advance the MODE key to the next prompt or exit the CAL menu.