Setup, Chapter 4
17
WATLOW Series 945 User's Manual
Setup
Setup Menu
Use this page as a master copy for configuring your Series 945.
Do not enter any values here; make photocopies instead.
Table 2 -
Setup Menu Prompts
and Descriptions.
Parameter
Value
Range
Factory Default
Appears If:
LOC
0 - 3
0
In
J, K (appears as H), t, n, c, Pt2,
J or r
r, S, b, rtd, rt.d, 0-5, 420
rSP
OFF, 0-5, 420
OFF
In = T/C or RTD
dEC
0, 0.0, or 0.00
0
In = 0-5 or 420
C _ F
C or F
F
In = T/C or RTD
rL
rL to rH
Input dependent.
rH
rH to rL
Input dependent.
Ot1
ht or CL
ht
HYS1
1°F - 99°F, 1°C - 55°C, 1U - 99U
3°F
0.1°F - 9.9°F, 0.1°C - 5.5°C, 0.1U - 9.9U
Ot2
ht, CL or no
CL
Unit has secondary output
HYS2
1°F - 99°F, 1°C - 55°C, 1U - 99U
3°F
Unit has secondary output
0.1°F - 9.9°F, 0.1°C - 5.5°C, 0.1U - 9.9U
Ot2 = ht or CL
AL1
Pr, dE or no
Pr
Unit has alarms
LAt 1
LAt or nLA
nLA
Unit has alarms and
AL1 = Pr or dE
HYS3
1°F - 99°F, 1°C - 55°C, 1U - 99U
3°F
Unit has alarms and
0.1°F - 9.9°F, 0.1°C - 5.5°C, 0.1U - 9.9U
AL1 = Pr or dE
Ot4
no, PrOC, StPt
PrOC
Hardware is present
AL 2
Pr, dE or no
Pr
Unit has alarms
LAt 2
LAt or nLA
nLA
Unit has alarms and
AL2 = Pr or dE
HYS4
1°F - 99°F, 1°C - 55°C, 1U - 99U
3°F
Unit has alarms and
0.1°F - 9.9°F, 0.1°C - 5.5°C, 0.1U - 9.9U
AL2 = Pr or dE
SIL
On or OFF
OFF
Unit has alarms & AL1 = dE
rtd
JIS or din
din
In = rtd or rt.d