Watlow EZ-ZONE
®
PM Integrated Controller
•
62
•
Chapter 5 Operations Page
Operations Page
Dis-
play
Parameter name
Description
Range
Default
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Param-
eter ID
Data
Type
& Read/
Write
[a;sir]
[A.Sir]
Alarm (1 to 4)
Alarm Silence Request
Write to this register to
silence an alarm
Note:
If an alarm is setup
to silence alarm when
active
[a;sir]
will ap-
pear on the display.
[`sil]
Silence Alarm
(1010)
Instance 1
Map 1 Map 2
1506 1906
Offset to next
instance (Map1
1 50,
Map 2
equals
+60)
0x6D
(109)
1 to 4
0xE (14)
- - - -
9014
uint
W
[`a;st]
[ A.St]
Alarm (1 to 4)
Alarm State
Current state of alarm
[`Str]
Startup (88)
[nonE]
None (61)
[`bLo]
Blocked (12)
[`AL;l]
Alarm low (8)
[`AL;h]
Alarm high (7)
[`Err]
Error (28)
Instance 1
Map 1 Map 2
1496 1896
Offset to next
instance [Map1
+50], [
Map 2
+60]
0x6D
(109)
1 to 4
9
- - - -
9009
uint
R
No
Dis-
play
Alarm (1 to 4)
Alarm Clearable
Indicates if alarm can be
cleared.
[``no]
No (59)
[`YES]
Yes (106)
Instance 1
Map 1 Map 2
1502 1902
Offset to next
instance (Map1
1 50,
Map 2
equals
+60)
0x6D
(109)
1 to 4
0xC (12)
- - - -
9012
uint
R
No
Dis-
play
Alarm (1 to 4)
Alarm Silenced
Indicates if alarm is
silenced.
[`YES]
Yes (106)
[``no]
No (59)
- - - -
Instance 1
Map 1 Map 2
1500 1900
Offset to next
instance (Map1
1 50,
Map 2
equals
+60)
0x6D
(109)
1 to 4
0x0B (11)
- - - -
9011
uint
R
No
Dis-
play
Alarm (1 to 4)
Alarm Latched
Indicates if alarm is
latched.
[`yes]
Yes (106)
[``no]
No (59)
- - - -
Instance 1
Map 1 Map 2
1498 1898
Offset to next
instance (Map1
1 50,
Map 2
equals
+60)
0x6D
(109)
1 to 4
0x0A (10)
- - - -
9010
uint
R
[CUrr]
[oPEr]
Current Menu
[`C;hi]
[ C.hi]
Current (1)
Current High Set
Point
Set the current value
that will trigger a high
heater error state.
-1,999.000 to 9,999.000
50.0
Instance 1
Map 1 Map 2
1134 1374
0x73 (115)
1
8
- - - -
15008
float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can
be read with other interfaces.
R: Read
W: Write
E: EEPROM
S: User
Set