background image

2

RECOMMENDATIONS

1.  When possible, install two 45-degree angles to create a right angle rather than one 90-degree angle.
2.  Be sure to install the loop (see installation section) a minimum of 12" to 18" above spa level.
3.  Use a check valve in every system.

TYPICAL INSTALLATION OF THE BLOWER

By following the installation recommendations listed below you will be assured of optimum performance and a 
long lasting installation. Blower model numbers starting at 750 offer the option of side or bottom air discharge. 
They are supplied with plug for mounting. An external anti-surge valve (sold separately) can be used to prevent 
potential water backflow to the blower.

When using the side discharge, screw the plug to a solid base using the (3) screw holes 
provided (see Diagram 2). Apply a small amount of silicone to the vertical wall of the plug 
and set the blower housing on the plug. If gluing is necessary, spot glue only.

For bottom discharge, the 2" pipe may be used as the blower support. Be sure to keep the 
blower 12" to 18" above water level and use the Hartford loop system with a check valve 
(see Diagram 1). Again, a bead of silicone around the pipe will hold the unit firmly in place.

ELECTRICAL HOOKUP (SEE DIAGRAM 3)

1.  Check the line voltage to be sure it is correct for the air blower being used.
2.  DO NOT connect 220 volt line to 110 volt unit. THIS WILL DESTROY YOUR BLOWER.
3.  If switch is used, install as illustrated. If switch is not used, tie one line to one load, tie the other line (or neutral)  
  to the other load.
4.  GROUND ALL UNITS.
5.  ADDITIONAL GROUNDING NOTE: Double insulated (plastic) blowers do not need to be bonded.
6.  If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified  
  person in order to avoid a hazard.

AMPERAGE TEST FOR SPOT CHECKING INSTALLATION

To insure a properly installed and sized air blower, complete the following test. Pull the blower off the pipe, start 
the unit, and read the amperage. Set blower back on the pipe, start the unit, wait for air channel to clear, and read 
amperage again. A properly installed unit will not drop more than .5 amps. If the amperage is not to within the 
range, refer to Troubleshooting or Sizing sections.

TROUBLESHOOTING

NO ACTION OR TOTAL MOTOR FAILURE

1.  Check motor brushes for excessive wear.
2.  Check wiring (i.e. voltage, amperage, etc.)
3.  Check for blockage in plumbing.
4.  Be sure sizing is correct.
5.  Be sure check valve is installed properly.

BLOWER OVERHEATING

1.  Check for blockage in plumbing.
2.  Be sure sizing is correct.
3.  Be sure check valve is installed properly.

WATER DAMAGE

1.  Check valve may be failing.
2.  Sprinklers close to air blowers causing water entry through air intake.
3.  Blower installed below water level.
4.  Blower installed upside down.

DIAGRAM 1

DIAGRAM 3

Grade

32"

36"

Check

Valve

Blower

32"

32"

12" - 18"

5 ft. min

25 ft. max

20"

Hartford Loop

Grade Level

30 ft. total Air Line

2" PVC Air Line

DIAGRAM 2

NEUTRAL

LOAD

LINE

NEUTRAL

CHASIS SCREW

GROUND #12AWG

LOAD

LOAD

LINE

LINE

GROUND

CHASIS SCREW

GROUND #12AWG

GROUND

110 VOLT

220 VOLT

810-0037.0618

©2018 Waterway Plastics

Summary of Contents for SANTANNA

Page 1: ...rresponding number of air holes needed to release the proper amount of air An inadequate number of holes or holes that are too small create excessive heat buildup commonly called back up pressure resulting in potential harm to the air blower If it is determined that the existing hole sizing is incorrect additional holes may be drilled or the existing holes may be enlarged or more air injectors add...

Page 2: ...ie one line to one load tie the other line or neutral to the other load 4 GROUND ALL UNITS 5 ADDITIONAL GROUNDING NOTE Double insulated plastic blowers do not need to be bonded 6 If the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified person in order to avoid a hazard AMPERAGE TEST FOR SPOT CHECKING INSTALLATION To insure a properly installed ...

Page 3: ...VC Pipe 1 PVC Pipe to Bubblers 2 PVC Pipe Water Flow Venturi Tee 12 UL Listed Check Valve UL Listed Check Valve 2 PVC Pipe Air Flow 2 PVC Pipe UL Listed Check Valve 4 How an Air Blower enhances the performance of your spa JET ACTION ONLY TOTAL AIR ACTION 1 TYPICAL INSTALLATION 5 ft 25 ft from spa 2 LONG RUN INSTALLATION over 25 ft from spa 3 BLOWER LAYOUT DIMENSIONS 810 0037 0618 2018 Waterway Pla...

Page 4: ...AIR INJECTOR CAP DIMENSIONS 1 1 2 pipe capped stubbed Fits in 1 1 2 Schedule 40 PVC pipe Pipe cuts flush with finish coat ready for gunite air injector Optional Seat Installation Gunite Spa Typical Four in the Floor Installation 1 PVC Reduced from 2 PVC Run in from Flower 1 20 2 00 diameter 1 00 20 A B 810 0037 0618 2018 Waterway Plastics ...

Reviews: