ADDITIONAL STANDARD FUNCTIONS
Presscontrol Wall PRO is designed on a flexible platform that allows continuous updates of functions and the development of
compatible accessories to meet the most diverse needs.
The standard device allows:
- The use of any type 4-20 mA 12-16-25 bar pressure sensor on the market.
- The application of an analog flow sensor (On/Off).
- The application of a digital flow sensor to measure the flow rate.
- The assembling of pressure sets up to 4 pumps managed with a single inverter or by an inverter for each pump.
- The connection with BMS protocols (Building Management System).
- Data transfer to a mobile phone via NFC technology.
- The connection with a floater, a level probe kit and other remote controls.
- The setting of the maximum frequency up to 140 Hz to manage high speed motors.
OPTIONALS
Pressure sensor 16 and 25 bar.
Analogic and/or digital flow sensor.
Electronic box to make pressure sets up to 4 pumps with a single device.
GSM module for automatic data transmission on mobile phones.
Versions with different supply voltages.
AUTOMATIC RESTART AND ANTI-JAMMING FUNCTION
In case of stopping due to a water shortage, the devices will automatically make 10 double attempts to rearm over the 24
hours following the failure, each lasting approximately 5 seconds to allow the pumps and the system to reload if possible.
The user can try to rearm the devices at any time by pressing the Restart button.
If for any reason the pumps remain idle for 24 consecutive hours, the devices will carry out a start-up of the pump motor for
about 5 seconds without affecting the normal operation of the unit.
In case of a temporary blackout, the pressure set will automatically rearm once the electricity returns.
INSTALLATION AND STARTUP
Install the device on a wall near the pump (fig. 1).
Connect the supplied pressure sensor, make the electrical connections and energize.
Arrange the use of an expansion tank sized according to the hydraulic characteristics of the system.
To startup the pump, follow the instructions that will appear in sequence on the display of the device:
- Language selection.
- Pump motor ampere setting.
- Minimum flow acquisition.
- Setting of the working pressure and restart pressure if different from factory setting: system pressure 3 bar -
restart pressure 1,5 bar.
- It is now possible to start the pump