2 Installation
2 1 Regulation installation
and maintenance conditions
The appliance must be installed and the maintained
by an approved professional in accordance with the
prevailing regulations and code of practice, in particular:
The legislation on the handling of refrigerants.
2 2 Unpacking and reservations
2 2 1 Receipt
Carefully check, in the carrier’s presence, the general
appearance of the appliances and check that the
outdoor unit is not laid on its side or back.
In the case of any dispute, state any appropriate
reservations to the carrier in writing within 48 hours and
send a copy of this letter to the After-Sales service.
2 2 2 Handling
The outdoor unit should not be laid on its side or back
during transport.
Laying the unit down during transport is likely to damage
the internal tubes and the compressor suspensions.
Any damage caused by transportation of the unit lying
down is not covered by the warranty.
If necessary the outdoor unit may be tilted only during
manual handling (to go through a door or use a
staircase).
This operation must be conducted very carefully and
the appliance must be immediately restored to upright
position.
2 2 3 Containment of refrigerant circuits
All refrigerant circuits fear contamination from dust and
moisture. If such pollutants introduced into refrigeration
circuit, they can contribute to degrade the reliability of
the heat pump.
"
It’s necessary to ensure correct containment
connections and refrigerant circuits (hydraulic
unit, outdoor unit).
"
In case of subsequent failure and expertise, the
finding of the presence of moisture or foreign
objects into the compressor oil would lead to
systematic exclusion of warranty.
- Check upon receipt that the fittings and the refrigeration
circuit caps mounted on hydraulic unit and outdoor unit
are properly seated and locked (impossible to loosen
bare hands). If this’s not the case, tighten them using
an against wrench.
- Check also that the refrigerant connections are sealed
(plastic caps or tubes crushed at the ends and soldered).
If the caps must be removed during installation (tubes
cut by example), put back them as soon as possible.
2 2 4 Accessories provided
- Accessories provided with the outdoor unit (
figure 10
).
- Accessories provided with the hydraulic unit
(
figure 9
)
2 3 Installation position
The choice of the position for installation is particularly
important insofar as any later movement is a delicate
operation requiring the intervention of a qualified person.
Choose the site of the outdoor unit and the hydraulic
unit after discussion with the customer.
Observe the maximum and minimum distances
between the hydraulic unit and the outdoor unit
(
figure 17, page 16
) ; the guarantee of the performances
and the system’s service life depend on this.
5
Bracket
To secure the
hydraulic model
6
Outdoor sensor
To monitor the outdoor
temp
Figure 9 -
Accessories provided
with the hydraulic unit
5
6
1
2
1
Elbow
For draining away the
condensates
2
Plug (x 2)
Figure 10 -
Accessories provided
with the outdoor unit
Installation and operating manual "1364 - EN"
Split system (3-phase)
- 12 -