Waterous Foam Manager Installation Instructions Manual Download Page 6

F-1031, Section 3026

Page 6 of 17

Installation

Fire Pump Mounting

For fire pump mounting instructions, see F-1031, Section 3011, 

CM/CS Installation Instructions.

Foam Pump Mounting

Required if the Foam Pump is not mounted on the Fire Pump at the factory (shipped loose).

Install Foam Pump in Apparatus:

The Motor / Pump Assembly must be mounted horizontally. The base must be

anchored to a surface or structure that is rigid and of adequate strength to

withstand the vibration and stresses of apparatus operation. For dimensions of

mounting bracket, see page 7 (Advantus 3) or page 8 (Advantus 6).

Flexible hose is required to make the hose connections from the Motor / Pump

Assembly to the foam tank.

DO NOT hard pipe the system.

Consider access requirements  for checking the foam pump. Be sure the foam
concentrate hoses can be properly routed to the inlets and outlets on the foam

pump.

Foam concentrates should gravity feed to the foam pump inlet from the foam

tank. However the systems are capable of drafting up to one meter vertically.

The Motor / Pump Assembly must be mounted in an area to avoid excessive

exhaust system heat buildup.

Protect the hoses and wiring to prevent chafing and abrasion during operation

of the foam system.

Protect the Motor / Pump Assembly from excessive road spray and debris.

Although the system is sealed and designed to be resistant to the harsh envir‐

onment of fire fighting apparatus, a protected compartment with easy operator

access is the recommended installation location.

Install foam injection hose and cables between Foam Pump and Foam

Manifold:

Advantus 3 Systems: See page 7.

Advantus 6 Systems: See page 8.

Summary of Contents for Foam Manager

Page 1: ...ation Fire Pump Mounting 6 Foam Pump Mounting Only if Foam Pump was Shipped Loose Mounting Foam Pump 6 Hose Cables and Mounting Bracket Advantus 3 7 Advantus 6 8 Panel Components Advantus Foam Pump OI...

Page 2: ...am Manager System Other installation instructions available CS CSU CM CMU Series Fire Pump F 1031 Section 3011 Priming System F 1031 Section 3006 Manifold Drain Valves F 1031 Section 3008 Pressure Con...

Page 3: ...am Concentrate Strainer 4 Foam Manifold 5 Advantust Foam Pump OIT Control Panel 6 Advantust Operation Instruction Panel Plate 7 OIT Cable Items not Furnished by Waterous Description Discharge Ball Val...

Page 4: ...F 1031 Section 3026 Page 4 of 17 System Components 5 6 3 7 Items Shipped Loose with Advantus Foam Pump 1 4 2 3 To Foam Tank...

Page 5: ...l of the foam pump and add if necessary AdvantusR Foam Pump Oil Foam Pump Model Level from Top of Oil Fill Port Use Oil Advantus 3 3 4 inch 19 mm Synthetic 10W 30 Mobil 1 recommended Advantus 6 1 inch...

Page 6: ...onsider access requirements for checking the foam pump Be sure the foam concentrate hoses can be properly routed to the inlets and outlets on the foam pump Foam concentrates should gravity feed to the...

Page 7: ...le Connections Foam Pump Mounting Bracket 1 2 NPT x 3 8 NPT Adapter Foam Manifold Mounted on Fire Pump 90_ Street Elbow 1 2 NPT 48 in Hose furnished if longer hose required contact Waterous Note If lo...

Page 8: ...le Connections Foam Pump Mounting Bracket 1 2 NPT x 3 8 NPT Adapter Foam Manifold Mounted on Fire Pump 90_ Street Elbow 1 2 NPT 48 in Hose furnished if longer hose required contact Waterous Note If lo...

Page 9: ...mine a location for the Operator Interface Terminal OIT on the operator panel of the equipment Consider the routing path of the cable from the OIT to the pump motor driver assembly see Page 13 If nece...

Page 10: ...e Connection Optional Foam Tank Level Switch Inject Bypass Valve Waterous offers two types of tank level switches as shown below 1 Install in tank according to NFPA see Page 15 for wiring details Side...

Page 11: ...031 Section 3026 Page 11 of 17 1 Waterous furnishes a mix manifold mounted on the pump with 2 1 2 in Victaulic or 3 in Victaulic discharge 2 Distribution manifolds piping and valves are not furnished...

Page 12: ...ntus unit are tested at the factory with that unit Improper handling and forcing connections can damage these cables which could result in other system damage 11 Always disconnect the ground straps an...

Page 13: ...e Conductivity Probe Conductivity Probe Flow Sensor To Product Sensor on Foam Pump Motor Resettable Voltage Breaker Ground Auto Run Tank B Float Switch Tank A Float Switch Tank B Select Power to the P...

Page 14: ...ng cables take care to avoid routing them next to antenna cables radio power lines and radio compon ents When there is extra cable double the cable back on itself and secure in a flat bundle with plas...

Page 15: ...F 1031 Section 3026 Page 15 of 17 Foam Tank Switch Dual or Single...

Page 16: ...tting 2 Use the UP and DOWN arrow buttons to select one of the following measurement units GAL will select U S Gallons IPL will select Imperial Gallons LTR will select Metric Liters 3 Pushing the SELE...

Page 17: ...Condition applies to tanks utilizing a common wall s between the foam tank and the water tank If a leak is confirmed repair the foam tank and flush the water tank and pump until foam is cleared Foam p...

Reviews: