Waterous Foam Manager Installation Instructions Manual Download Page 10

Advantust 3 Systems

Advantust 6 Systems

Foam Tank Hose Connection,

1/2 in. NPT

Foam Tank Hose Connection,

1 in. NPT

Inject/Bypass Valve

In-line

Strainer

In-line

Strainer

IL2959

Foam Tank Connection to Advantus

®

 Foam Pump

Flexible hose is required to make the hose connections from the foam pump to
the foam tank. Note hose from the foam tank to the foam pump is not fur­
nished by Waterous. The in-line foam concentrate strainer must be installed in
the line and be accessible for maintenance.

To ensure adequate concentrate supply, size hose as follows:

·

Advantus 3 - minimum of 3/4 inch ID tubing

·

Advantus 6 - minimum of 1 inch ID tubing

Foam Tank Connection to Advantus

®

 Foam Pump

When specifying an integral foam tank, make sure provisions are made for in­
stallation of the optional low tank level sensor as well as foam suction connec­
tions and tank drainage according to NFPA.

Most water tank manufacturers will build the foam tank into the booster tank.

1.

Place the foam tank so that refilling can be done safely.

2.

Foam concentrates should gravity feed to the foam pump inlet from the foam
tank. However, the systems are capable of drafting up to 1 meter vertically.

Foam Tank

 - Not Furnished by Waterous

Foam Concentrate Connection

Optional Foam Tank Level Switch

Inject / Bypass Valve

Waterous offers two types of tank level switches as shown below.

1.

Install in tank according to NFPA (see Page 15 for wiring details).

Side Mount

Bottom Mount

1/2 in. NPT

1/8 in. NPT

The Inject / Bypass valve is mounted on the discharge side of the foam pump.
This valve shall be accessible by the pump operator during normal operations.
The valve is a 3-way directional valve that selects where the output of the foam
pump will go.

Check to make sure the valve is installed properly. look at the ports as you move
the handle. The flow should go from the center port to each of the other ports.

The hose and fittings from the inject port to the foam injector fitting should have
a minimum rating of 3/8 of the maximum fire pump discharge pressure.

The hose from the bypass port may have a lower pressure rating since it is
plumbed to the atmosphere and will not receive high pressures. This hose is
used for pumping the concentrate into a container to empty the tank or to assist
in priming of the foam pump. The hose from the bypass port must be long
enough to reach a container outside the truck. This hose must be coiled for
storage when not in use.

F-1031, Section 3026

Page 10 of 17

CAUTION

Shut-Off Valves. May cause damage to the foam pump.

Never install shut-off valves between the pump and discharge
pressure regulator or in the regulator bypass line.

Summary of Contents for Foam Manager

Page 1: ...ation Fire Pump Mounting 6 Foam Pump Mounting Only if Foam Pump was Shipped Loose Mounting Foam Pump 6 Hose Cables and Mounting Bracket Advantus 3 7 Advantus 6 8 Panel Components Advantus Foam Pump OI...

Page 2: ...am Manager System Other installation instructions available CS CSU CM CMU Series Fire Pump F 1031 Section 3011 Priming System F 1031 Section 3006 Manifold Drain Valves F 1031 Section 3008 Pressure Con...

Page 3: ...am Concentrate Strainer 4 Foam Manifold 5 Advantust Foam Pump OIT Control Panel 6 Advantust Operation Instruction Panel Plate 7 OIT Cable Items not Furnished by Waterous Description Discharge Ball Val...

Page 4: ...F 1031 Section 3026 Page 4 of 17 System Components 5 6 3 7 Items Shipped Loose with Advantus Foam Pump 1 4 2 3 To Foam Tank...

Page 5: ...l of the foam pump and add if necessary AdvantusR Foam Pump Oil Foam Pump Model Level from Top of Oil Fill Port Use Oil Advantus 3 3 4 inch 19 mm Synthetic 10W 30 Mobil 1 recommended Advantus 6 1 inch...

Page 6: ...onsider access requirements for checking the foam pump Be sure the foam concentrate hoses can be properly routed to the inlets and outlets on the foam pump Foam concentrates should gravity feed to the...

Page 7: ...le Connections Foam Pump Mounting Bracket 1 2 NPT x 3 8 NPT Adapter Foam Manifold Mounted on Fire Pump 90_ Street Elbow 1 2 NPT 48 in Hose furnished if longer hose required contact Waterous Note If lo...

Page 8: ...le Connections Foam Pump Mounting Bracket 1 2 NPT x 3 8 NPT Adapter Foam Manifold Mounted on Fire Pump 90_ Street Elbow 1 2 NPT 48 in Hose furnished if longer hose required contact Waterous Note If lo...

Page 9: ...mine a location for the Operator Interface Terminal OIT on the operator panel of the equipment Consider the routing path of the cable from the OIT to the pump motor driver assembly see Page 13 If nece...

Page 10: ...e Connection Optional Foam Tank Level Switch Inject Bypass Valve Waterous offers two types of tank level switches as shown below 1 Install in tank according to NFPA see Page 15 for wiring details Side...

Page 11: ...031 Section 3026 Page 11 of 17 1 Waterous furnishes a mix manifold mounted on the pump with 2 1 2 in Victaulic or 3 in Victaulic discharge 2 Distribution manifolds piping and valves are not furnished...

Page 12: ...ntus unit are tested at the factory with that unit Improper handling and forcing connections can damage these cables which could result in other system damage 11 Always disconnect the ground straps an...

Page 13: ...e Conductivity Probe Conductivity Probe Flow Sensor To Product Sensor on Foam Pump Motor Resettable Voltage Breaker Ground Auto Run Tank B Float Switch Tank A Float Switch Tank B Select Power to the P...

Page 14: ...ng cables take care to avoid routing them next to antenna cables radio power lines and radio compon ents When there is extra cable double the cable back on itself and secure in a flat bundle with plas...

Page 15: ...F 1031 Section 3026 Page 15 of 17 Foam Tank Switch Dual or Single...

Page 16: ...tting 2 Use the UP and DOWN arrow buttons to select one of the following measurement units GAL will select U S Gallons IPL will select Imperial Gallons LTR will select Metric Liters 3 Pushing the SELE...

Page 17: ...Condition applies to tanks utilizing a common wall s between the foam tank and the water tank If a leak is confirmed repair the foam tank and flush the water tank and pump until foam is cleared Foam p...

Reviews: