Installation Instructions

Foam Manager

t

 System

with Advantus

R

Section

3026

Form No.

F-1031

Issue Date

Rev. Date

05/11/12

01/18/08

Waterous Company  125 Hardman Avenue South, South St. Paul, Minnesota  55075  USA  (651) 450-5000

Instructions subject to change without notice.

 

Introduction

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Components

3, 4

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Lubrication:

Foam Pump Oil Fill

5

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Installation:

Fire Pump Mounting

6

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Foam Pump Mounting:
(Only if Foam Pump was Shipped Loose)

Mounting Foam Pump

6

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Hose, Cables and Mounting Bracket:

Advantus 3

7

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Advantus 6

8

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Panel Components:

Advantus Foam Pump:

OIT (Operation Interface Terminal - Control Panel)

9

. . . . . . . 

Optional Dual OIT (Control Panel) Kit

9

. . . . . . . . . . . . . . . . . . . 

Instruction Panel

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Optional Schematic and Rating Panels

9

. . . . . . . . . . . . . . . . . 

Foam Concentrate Connection

10

. . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Foam Tank

10

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Foam Tank to Advantus Foam Pump Connection

10

. . . . . . . . . . 

In-Line  Foam Concentrate Strainer

10

. . . . . . . . . . . . . . . . . . . . . . 

Optional Foam Tank Level Switch

10

. . . . . . . . . . . . . . . . . . . . . . . 

Inject/Bypass Valve

10

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Water/Foam Solution Distribution

11

. . . . . . . . . . . . . . . . . . . . . . . . . . 

Water Drains:

Water Distribution Check Valves

11

. . . . . . . . . . . . . . . . . . . . . . . . 

Foam Manifold

11

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Electrical Wiring:

Electrical Components

12

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Power to Foam Pump

12

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Wiring Schematic

13

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Cables and Grounding

14

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Foam Tank Switch - Single or Dual

15

. . . . . . . . . . . . . . . . . . . . . . 

Foam Pump Calibration:

16

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Troubleshooting Guide

17

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

  Table of Contents

Foam Manager System with Advantus

Summary of Contents for Foam Manager

Page 1: ...ation Fire Pump Mounting 6 Foam Pump Mounting Only if Foam Pump was Shipped Loose Mounting Foam Pump 6 Hose Cables and Mounting Bracket Advantus 3 7 Advantus 6 8 Panel Components Advantus Foam Pump OI...

Page 2: ...am Manager System Other installation instructions available CS CSU CM CMU Series Fire Pump F 1031 Section 3011 Priming System F 1031 Section 3006 Manifold Drain Valves F 1031 Section 3008 Pressure Con...

Page 3: ...am Concentrate Strainer 4 Foam Manifold 5 Advantust Foam Pump OIT Control Panel 6 Advantust Operation Instruction Panel Plate 7 OIT Cable Items not Furnished by Waterous Description Discharge Ball Val...

Page 4: ...F 1031 Section 3026 Page 4 of 17 System Components 5 6 3 7 Items Shipped Loose with Advantus Foam Pump 1 4 2 3 To Foam Tank...

Page 5: ...l of the foam pump and add if necessary AdvantusR Foam Pump Oil Foam Pump Model Level from Top of Oil Fill Port Use Oil Advantus 3 3 4 inch 19 mm Synthetic 10W 30 Mobil 1 recommended Advantus 6 1 inch...

Page 6: ...onsider access requirements for checking the foam pump Be sure the foam concentrate hoses can be properly routed to the inlets and outlets on the foam pump Foam concentrates should gravity feed to the...

Page 7: ...le Connections Foam Pump Mounting Bracket 1 2 NPT x 3 8 NPT Adapter Foam Manifold Mounted on Fire Pump 90_ Street Elbow 1 2 NPT 48 in Hose furnished if longer hose required contact Waterous Note If lo...

Page 8: ...le Connections Foam Pump Mounting Bracket 1 2 NPT x 3 8 NPT Adapter Foam Manifold Mounted on Fire Pump 90_ Street Elbow 1 2 NPT 48 in Hose furnished if longer hose required contact Waterous Note If lo...

Page 9: ...mine a location for the Operator Interface Terminal OIT on the operator panel of the equipment Consider the routing path of the cable from the OIT to the pump motor driver assembly see Page 13 If nece...

Page 10: ...e Connection Optional Foam Tank Level Switch Inject Bypass Valve Waterous offers two types of tank level switches as shown below 1 Install in tank according to NFPA see Page 15 for wiring details Side...

Page 11: ...031 Section 3026 Page 11 of 17 1 Waterous furnishes a mix manifold mounted on the pump with 2 1 2 in Victaulic or 3 in Victaulic discharge 2 Distribution manifolds piping and valves are not furnished...

Page 12: ...ntus unit are tested at the factory with that unit Improper handling and forcing connections can damage these cables which could result in other system damage 11 Always disconnect the ground straps an...

Page 13: ...e Conductivity Probe Conductivity Probe Flow Sensor To Product Sensor on Foam Pump Motor Resettable Voltage Breaker Ground Auto Run Tank B Float Switch Tank A Float Switch Tank B Select Power to the P...

Page 14: ...ng cables take care to avoid routing them next to antenna cables radio power lines and radio compon ents When there is extra cable double the cable back on itself and secure in a flat bundle with plas...

Page 15: ...F 1031 Section 3026 Page 15 of 17 Foam Tank Switch Dual or Single...

Page 16: ...tting 2 Use the UP and DOWN arrow buttons to select one of the following measurement units GAL will select U S Gallons IPL will select Imperial Gallons LTR will select Metric Liters 3 Pushing the SELE...

Page 17: ...Condition applies to tanks utilizing a common wall s between the foam tank and the water tank If a leak is confirmed repair the foam tank and flush the water tank and pump until foam is cleared Foam p...