Operating and maintenance instructions
ABM Active Chilled Beams
Installation
General Information
Foreword
These instructions
are given as a guide to good
practice in the installation, start-up, operation, and
maintenance by the user, of Waterloo ABM 300 Active
Chilled Beams.
8QLW,GHQWL¿FDWLRQ
Units arrive on site with an unit model size, coil type,
SUHVHQFH LGHQWL¿FDWLRQ VWLFNHU ZLWK RI DQ HOHFWULF
heater, unit handing pictograms, which clearly
indicates important information such as the customer
order number, job name, unit model size, coil type,
unit handling etc.
5HFRPPHQGHG$LUDQG:DWHU4XDOLW\
To maintain unit performances, ensure that the air
HQWHULQJWKHXQLWLVRIVXI¿FLHQWTXDOLW\
Table 1).
:DWHU4XDOLW\5HFRPPHQGDWLRQVIRU:DWHU
Coils
At installation and then yearly, the manufacturer
recommends having water analyzed for bacteria
IHUUREDFWHULD EDFWHULD JHQH
2
S and
reducing sulfates) and also a chemical analysis, to
avoid corrosion and scaling. The water circuit must
LQFOXGH ZDWHU WUHDWPHQW GHYLFHV ¿OWHUV DGGLWLYHV
intermediate exchangers, purges, vents, isolating
valves, etc, depending on the results of these analyses.
The results of the analyses must correspond to values
LQWKH
Table 2).
'XFW,QOHW&RQGLWLRQV
As with all types of ATD, the duct inlet conditions are
very important to the correct function and operation of
WKLVSURGXFW%HVWSUDFWLFHSURFHGXUHVDQGWHFKQLTXHV
should always be followed.
,W VKRXOG EH QRWHG WKDW LQVXI¿FLHQW FRQVLGHUDWLRQ RI
duct entry conditions can result in:
Poor velocity distribution
Excessive turbulence
Unpredictable throw
%UHDNGRZQRIFHLOLQJDWWDFKPHQW
+LJKQRLVHOHYHOV
'LI¿FXOWEDODQFLQJSURFHGXUHV
Table 1- Air Quality Recommendations
Table 2- Water Quality Recommendations
Air Quality Recommendations
SO
2
<0.02 ppm
+
2
S <0.02
ppm
NO <1.00
ppm
NO
2
<1.00
ppm
1+
3
<6.00
ppm
N
2
O <0.25
ppm
Water Quality Recommendations
Total hardness in
French degrees
7+
Chloride [C L-]
< 10 mg/l
Sulfate [SO42-]
< 30 mg/l
Nitrate [NO
3
-]
= 0 mg/l
Dissolved iron
< 0.5 mg/l
Dissolved oxygen
4 < [O
2
] < 9 mg/l
Carbon dioxide [CO
2
]
< 30 mg/l
Resistance
2000<Resistance<5000 cm
S+
S+