Technical data
04.12.2015
45 / 48
Copyright
2014 by: WATERKOTTE GmbH. Subject to changes.
15
Technical data
Performance table EcoTouch DS 5050T with R410A
5028.5T 5034.5T
5045.5T
5056.5T
Groundwater source heating
1) 3)
Power cons./output W10/W35
3)
, kW
4,4/26,8
5,9/34,1
8,1/45,2 10,1/56,4
Performance factor (COP)
6,0
5,8
5,6
5,6
Space heating energy efficiency class
A++
A++
A++
A++
Efficiency class of the package of space heater
5)
/
A+++
A+++
A+++
A+++
Groundwater flow rate, m³/h (W10/W35),
T=3K
6,5
8,2
10,8
13,5
Pressure loss in the evaporator, mWS
1,9
2,2
2,4
2,6
Groundwater flow rate, minimum m³/h
2
)
T=6
3,3
4,1
5,4
6,7
Heating water flow rate, m³/h (W10/W35);
T=5K
4,6
5,9
7,8
9,7
Pressure loss in the condenser, mWS
1,2
1,2
1,3
1,4
Operating limit
W10/W65
Heat source ground
Power cons./output B0/W35
3)
, kW
4,4/20,2
5,7/25,6
7,6/34,1
9,4/42,4
Performance factor (COP) (EN14511)
4,5
4,5
4,4
4,5
Space heating energy efficiency class
A+
A++
A++
A++
Efficiency class of the package of space heater
5)
/
A++
A++
A++
A++
H
eat source flow rate
4)
, m³/h (B0/W35),
T=3K
5,2
6,6
8,7
10,8
Pressure loss in the evaporator, mWS (30 % ethylene
glycol)
1,7
1,8
2,0
2,1
Heating water flow rate, m³/h (B0/W35),
T=5K
3,5
4,4
5,9
7,3
Pressure loss in the condenser, mWS
0,6
0,7
0,8
0,8
Operating limit
B-5/W60 , B0/W65
Compressor
tandem-scroll
Electrical data 3 x 400 V, 50 Hz
5028.5T 5034.5T
5045.5T
5056.5T
Compressor
400 V, 3~, 50 Hz
Starting current, A
58,9
71,7
88,0
117,3
Starting current soft start, A (standard)
33,4
40,7
50,5
66,3
Max. operating current,, A
14,8
19,4
26,0
30,6
Main fuse, provided by customer, delay A
C 25 A
C 25 A
C 32 A
C32 A
Control fuse, provided by customer, delay A
B 10 A
B 10 A
B 10 A
B 10 A
Dimension, weights, connections
5028.5T 5034.5T
5045.5T
5056.5T
Number of scroll compressors
2
2
2
2
Compressor volume oil filling (l)
2x1,24
2x 1,24
2x 1,89
2x 1,77
Refrigerant volume R410A (kg)
3,65
--
--
--
Minimum volume, installation room, ref. to EN 378-1 (m
3
)
8,3
--
--
--
Weight of device (kg)
221
232
265
286
Connections: Heat source / use
R2“ ext.
Dimensions W x H x D, mm
750x1470x611
1)
Heat source ground water with intermediate circuit. For details refer to our product range. The energy rates are basing on th is
system configuration.
2)
W10/W35 and ∆t=6K.
3)
Tolerances stated in EN 12900 and EN14511 apply for the performance data
listed above.
4)
Heat source (70 % water + 30 % ethylene glycol). .
6)
When the composite label Waterkotte WWPR controller class
III was considered (without room temperature sensor).