OPERATING AND MAINTENANCE

 

Your Excelight NX UV System is “ON” continuously during normal operation.  After 

periods of not using your water supply exceeding two to three days, it is 

recommended to open all faucets and flush your plumbing system for one to two 

minutes. 

 

WARNING!

 

ULTRAVIOLET LAMP REPLACEMENT 

THE ULTRAVIOLET LAMP INSIDE THE REACTOR CHAMBER WILL 

OPERATE EFFECTIVELY ROUND THE CLOCK, FOR APPROXIMATELY ONE 

YEAR OR 9000 HOURS. THE LAMP WILL NOT LIGHT LONGER THAN THAT, 

THE UV LIGHT INTENSITY MAY FALL BELOW THE PRESCRIBED SAFETY 

LEVEL. (40MJ/CM

2

) THEREFORE, ANNUAL LAMP REPLACEMENT IS 

NECESSARY REGARDLESS OF APPARENT LAMP CONDITION. 

 

 

Replacing the UV Lamp and Cleaning the Quartz Sleeve: 

 

A reminder that the chamber will be full of water so have a bucket and towels 

handy.

 

 

1.  Unplug the system from the electrical outlet and turn off the water supply to the 

unit. It is advisable to wait 5-15 minutes before proceeding to the next step. The 

water in the chamber can heat up 

to 57 ˚C (135 ˚F);

 

 

2.  Loosen the thumb screw on the electrical cap and carefully extract the lamp 

connector from the electrical end cap assembly to just expose the top of the UV 

lamp. While holding the lamp base firmly, disconnect the lamp 4-pin connector. 

Gloves should be worn as

 

the lamp base can be very hot

. Be careful not to 

drop the lamp into the quartz sleeve as both are easily broken. 

 

3.  Carefully slide the lamp out of the quartz sleeve and discard. 

 

4. 

Use caution as the water in the chamber may still be very hot at this stage

Loosen and remove both end caps. Place a bucket below the chamber and your 

hand under the bottom of the sleeve. Using your other hand, carefully remove 

the white and black rings from the top of the sleeve. Once the rings are off of 

the sleeve top, the sleeve should fall into your lower hand. Carefully extract the 

quartz sleeve from the reactor housing.  

The quartz sleeve is very fragile and 

is easily chipped or broken -  use extreme caution when installing or 

removing it from the reactor vessel.

 

 

NOTE:

 

Do not touch the lamp or quartz sleeve with your fingers. Handle by the ends 

only or wear soft non-abrasive gloves. 

 

 

5.  Clean the quartz sleeve with vinegar or a readily available scale-removing 

product. (Lime Away, CLR) 

 

6.  Examine the quartz sleeve O-rings. If they look worn or cracked, replace them.  

Re-install the quartz sleeve. (See replacement parts.) 

 

7.  Install new lamp by reversing the procedure described in items #2-4 above. 

 

Summary of Contents for Excelight EL08NSFAK

Page 1: ...R S MANUAL For Excelight Ultraviolet system model EL08NSFAK IMPORTANT READ AND UNDERSTAND THE TERMS OF THE MANUFACTURER S WARRANTY ON PAGE 14 OF THIS MANUAL FILL OUT THE WARRANTY REGISTRATION CARD WIT...

Page 2: ...HAVE DRINKING WATER TESTED REGULARLY UV RADIATION HAZARD NEVER OPERATE A UV LAMP OUTSIDE THE DISINFECTION CHAMBER EXPOSURE TO UV LIGHT CAN RESULT IN SERIOUS INJURY AND EXTREME BURNING OF THE SKIN AND...

Page 3: ...unit for anything other than its intended potable water application The use of attachments not recommended approved or sold by the manufacturer distributor may result in an unsafe condition Before doi...

Page 4: ...Transmittance Ballast Quartz Ultraviolet Thermal Control Sensor 120vac Sleeve Lamp Valve Adapter BALLAST AND DISPLAYS Function display mj cm2 Reset Transmittance indication Button Monitor Port 2 pin...

Page 5: ...the temperature does not fall below 4 C 40 F and the humidity level is low to prevent condensation on the chamber This unit functions optimally between 9 29 C 49 85 F 3 Use Teflon tape on all plumbing...

Page 6: ...e UV lamp and sensor Fig 2 6 Install the flow restrictor to the inlet port lower port The arrow on the restrictor indicates the direction of the water flow Fig 3 4 The arrow should be pointing towards...

Page 7: ...f the lamp plug cover and place the cover over the ledge of the electrical end cap Tighten the set screw Fig 12 13 Remove the nut on the grounding stud and place the grounding wire green yellow onto t...

Page 8: ...CONTACT YOUR LOCAL HEALTH AUTHORITY RESPONSIBLE FOR WATER SAFETY During the UV disinfection process the only place disinfection takes place is within the reactor chamber There is no residual disinfect...

Page 9: ...ve system operation timer The unit is available with an optional shutoff solenoid which will activate when there is an alarm turning off the water until the alarm is corrected The LCD display shows th...

Page 10: ...econds and then reconnect the AC power source If the failure was due to the Out of Limits AC Power the unit will re ignite the lamp and operate normally Total Running Hours The UV power source tracks...

Page 11: ...mbly to just expose the top of the UV lamp While holding the lamp base firmly disconnect the lamp 4 pin connector Gloves should be worn as the lamp base can be very hot Be careful not to drop the lamp...

Page 12: ...If there are leaks turn UV unit off close the shut offs disconnect the power to the unit and repair leaks SYSTEM REPLACEMENT PARTS EXCELIGHT NX System Replacement Components 1 Excelight NX8 UV Lamp S...

Page 13: ...35 200 Bacillus subtillis vegetative 11 000 Penicillum digitatum olive 88 000 Bacillus subtillis spore 58 000 Penicillum expensum olive 22 000 Clostridium tetani 22 000 Penicillum roqueforti green 26...

Page 14: ...00 Virus of Infectious Hepatitis 8 000 Staphylococcus aureus 7 000 YEAST Streptococcus faecalis 10 000 Baker s yeast 8 800 Streptococcus hemolyticus 5 500 Brewer s yeast 6 600 Streptococcus lactis 8 8...

Page 15: ...y is also subject to the conditions and limitations outlined under the heading General Conditions and Limitations below Warranty for Replacement Lamps and Parts Waterite Inc warrants replacement lamps...

Page 16: ...15 WATERITE INC Winnipeg Manitoba Canada www waterite com...

Reviews: