INSTRUCTION GUIDE: ElITE COmmUNICaTING ThERmOSTaT
IG1602EW 06/12
Advanced Settings
Security Lockout
This thermostat has the option to set
security features to lockout everything but
the adjustment of the temperature or a total
keypad lockout.
1. From the main menu, scroll to mENU
and press the center button ■ on the
keypad.
2. Select SECURITY lOCKOUT.
3. Select whether you want to lockout
everything but TEmP aDJUST ONlY or
TOTal KEYPaD lOCKOUT.
4. Either selection will bring you to the
Enter Pin Number screen.
5. Using the up and down arrows ▲▼, select a pin number
to lock out the thermostat. The right arrow ► moves you to
the next pin digit.
6. Once you’ve entered the 4-digit pin number, press the
center button ■ to save the pin. The screen will display
lOCKED and return to the main Screen.
7. Once you return to the main Screen, in the upper left of the
screen will alternate between lOCKED and the date and
time.
8. If you selected TEmP aDJUST ONlY, you will only be able
to adjust the set point temperature. any other operation will
require the pin number to unlock the thermostat.
9. Once unlocked, you’ll have to set a pin number again to
lockout the thermostat again.
10. In the event pin number is lost default is 9999.
Offsets
1. MENU → SETTINGS → OFFSETS
Temperature Offsets
This option allows calibration (or deliberate
miscalibration) of the room temperature sensor(s). There
are various reasons why the displayed temperature
would be adjusted to a higher or lower value. NOTE: Do
not adjust for 30 minutes after installation because board
may be heated by handling. The selected number is the
number of degrees, plus or minus, which will be added to
actual temperature. The numbers can range between -5˚
and +5˚. Default values are set to 0˚ offset.
Temperature Offset
Remote Indoor Offset (if sensor is attached)
Outdoor Offset (if sensor is attached)
Humidity Offset
This option allows calibration of the humidity sensor.
adjustments can range between -10% and +10%. Default
is 0% offset.
Auto Changeover
With auto changeover, the thermostat automatically switches itself
from heating to cooling, or vise versa, based on the setpoints.
When setting up the thermostat you have to enter both a cooling
setpoint and a heating setpoint. The thermostat will also prevent
the user from setting the cooling setpoint lower than the heating
setpoint. mode is set to aUTO for this operation to work.
MENU → SETTINGS → AUTO CHANGEOVER
Auto Changeover Time
– This setting sets the minimum off time
before the thermostat can change from one mode to
another. Default is 5 minutes. Range is from 0-120
minutes in 15 minute increments.
Auto or Manual Change
– Default is aUTO. If maNUal is
chosen, you will need to change from heating to
cooling or vise versa. When maNUal is set, aUTO is
removed from the mODE screen as a choice.
Instantaneous Energy Monitoring
Instantaneous Energy monitoring
can be found under the main menu,
if the energy monitoring option has
been enabled on the aurora Control
System. The screen displays energy
usage in real time, the current mode
of the heat pump, and the outdoor air
temperature (if installed).
Superboost (Variable Speed Heat Pumps ONLY)
Superboost can be found under the main menu. The Superboost
option temporarily enables a larger cooling capacity range. The
screen will allow the homeowner to turn on or off the Superboost
option. The option will enable by default for a 24 hour period of
time and then will automatically be disabled.
WARNING: OVERUSE OF THIS OPTION MAY
CAUSE OVERHEATING OF LOOPS.
Intermittent Fan
Temperature conditions can vary widely between the thermostat
location and extremities of the space the thermostat serves.
This air stratification problem can be especially pronounced
during mild outdoor conditions when long periods elapse
between space conditioning demands from the thermostat. This
intermittent fan operation can also improve the performance of
air cleaning or special filtration systems that locate the cleaning
or filtration media at the return air side of the fan.
SUPERBOOST
STATUS:
OFF
TURN ON SUPERBOOST
◄ BACK
SUPERBOOST
STATUS:
ON
TURNING OFF IN:
23HRS 15MIN
TURN OFF SUPERBOOST
◄ BACK
INST ENERGY MONITOR
MODE: STANDBY
BLOWER
0 W
COMPRESSOR
0 W
ELEC HT
0 W
PUMP
0 W
TOTAL
0 W
OUTDOOR AIR NA
◄ BACK