WaterFurnace SPECTRA SX Series Installation Manual Download Page 17

17

SPECTRA COMMERCIAL AND RESIDENTIAL INSTALLATION GUIDE

Before Starting Unit, Check The Following:

High voltage is correct and matches nameplate

Fuses, breakers and wire size correct

Low voltage wiring complete

Piping completed and water system cleaned and flushed

Air is purged from closed loop system

Isolation valves are open, water control valves or loop pumps wired

Condensate line open and correctly pitched

Transformer switched to lower voltage tap if needed

Dip switches set correctly (commercial microprocessor only)

DHW pump switch off unless piping is completed and air has been purged

Blower rotates freely - foam shipping support has been removed

Blower speed correct (taps on correct pins)

Air filter is clean and in position

Service/access panels are in place

Return air temperature is between 60-80

°

F in heating and 70-95

°

F in cooling

Air coil cleaned

Start Up Steps:

1)

Initiate a control signal to energize

the blower motor. Check blower

operation.

2)

Initiate a control signal to place the

unit in the cooling mode. Cooling

set point must be set below room

temperature.

3)

First stage cooling will energize

after a time delay.

4)

Be sure that the compressor and

water control valve or loop pumps

are activated.

5)

Verify that the water flow rate is

correct by measuring the water

pressure drop through the heat

exchanger using the P/T ports and

comparing to water pressure drop

found in Table  3.

6)

Check the temperature of both the

supply and discharge water. Refer

to Start Up Performance Table 2

7)

Check for an air temperature drop

of 15

°

 to 25

°

 F across the air coil,

depending on the fan speed and

entering water temperature. Refer

to unit operating pressures on

page 13.

8)

Adjust the cooling set point above

the room temperature and verify

that the compressor and water

valve or loop pumps deactivate.

Unit Start Up

Table 3 - 

Water Pressure Drop Table

Table 2 - 

Temperature Change Through Heat Exchanger

Water Flow Rate

   Water Temperature

(GPM)

      Change (Deg 

°

F)

Rise (Clg)

Drop (Htg)

For Closed Loop: Ground Source or

9 - 12

4 - 8

Cooler/Boiler systems at 3 gpm/ton
For Open Loop: Ground Water systems

20 - 26

10 - 17

at 1.5 gpm/ton

FLOW RATE

PRESSURE DROP (PSI)

MODEL

GPM

30

°

F

50

°

F

90

°

F

1.5

2.1

2.0

1.9

SX010

2.0

3.4

3.2

3.0

2.5

5.2

4.9

4.6

1.5

2.0

1.9

1.8

SX013

2.5

4.6

4.4

4.1

3.5

8.1

7.7

7.2

2.0

3.0

2.9

2.7

SX016

3.0

5.9

5.7

5.3

4.0

9.7

9.3

8.7

3.0

1.2

1.2

1.1

SX019

4.0

2.1

2.0

1.9

5.0

3.5

3.3

3.1

3.0

1.5

1.4

1.3

SX024

4.5

3.2

3.1

2.9

6.0

6.0

5.8

5.4

4.0

1.2

1.2

1.1

SX030

5.5

2.1

2.0

1.9

7.0

3.2

3.1

2.9

5.0

2.4

2.2

2.1

SX036

7.0

3.9

3.7

3.5

9.0

6.2

5.9

5.5

5.0

1.7

1.6

1.5

SX042

8.0

3.5

3.3

3.1

11.0

6.2

5.9

5.5

6.0

3.5

3.1

2.3

SX048

9.0

6.7

5.9

4.2

12.0

10.7

9.5

7.0

8.0

4.1

3.7

2.8

SX058

11.0

6.6

6.0

4.7

14.0

10.0

8.9

6.6

10.0

6.1

5.4

3.9

SX068

13.0

9.3

8.2

6.0

16.0

13.0

11.7

9.0

Note: To obtain maximum performance the air coil should be cleaned
before start up. A 10% percent solution of dishwasher detergent and water
is recommended for both sides of coil. A thorough water rinse should follow.

Summary of Contents for SPECTRA SX Series

Page 1: ...s for shipping damage removing the units from the cartons if necessary Units in question should also be internally inspected If any damage is noted the carrier should make the proper notation on the d...

Page 2: ...side or end discharge and may be field converted from one to the other by replacing the discharge panel The new panel must be ordered Horizontal units are normally suspended from a ceiling by four 3...

Page 3: ...ase isolated from the ceiling joists by additional layers of vibration absorbing mesh Duct System An air outlet collar is provided on vertical top flow units and all horizontal units to facilitate a d...

Page 4: ...connector has a rubber gasket seal similar to a garden hose gasket which when mated to the flush end of any 1 threaded pipe provides a leak free seal without the need for thread sealing tape or compo...

Page 5: ...nsate drain assembly consists of a drain tube which is connected to the drain pan a 3 4 PVC female adapter and a flexible connecting hose The female adapter may exit either the front or the side of th...

Page 6: ...e brought directly to the unit although it is not recommended since no vibration or noise attenuation can be accomplished Cleaning and Flushing Prior to start up of any heat pump the water circulating...

Page 7: ...t up Obtain these forms from your commercial representative or contact WaterFurnace Ground Source Systems Once piping is completed between the unit flow center and the ground loop Figure 7 on page 8 f...

Page 8: ...be disposed of in various ways depending on local building codes i e recharge well storm sewer drain field adjacent stream or pond etc Most local codes forbid the use of sanitary sewer for disposal Co...

Page 9: ...r faucet 5 Flush the tank by opening the cold water inlet valve to water heater to free the tank of sediments Close when draining water is clear 6 Disconnect the garden hose and remove the drain valve...

Page 10: ...faces of both connecting water lines with 3 8 wall closed cell insulation Figure 9 Water Heater Connection Kit Cold Drain Valve Coaxial Drain Tee In Out P T Relief Valve Long Elbow Venting Waste Valve...

Page 11: ...age heat 3 DHW pump should be running Be sure DHW pump disable switch SW1 2 is ON refers to commercial microprocessor only 4 The temperature difference between water entering and leaving the desuperhe...

Page 12: ...al strip PS and contactor CC Figure 12 Spectra SX Line Voltage Blower Relay Compressor Control Module Transformer Compressor Contactor Ground Lug Typical Electromechanical Control Box Configuration Te...

Page 13: ...0 60 28 3 34 2 50 50 208 230 60 3 197 254 21 0 13 5 99 0 4 6 18 1 21 4 30 30 460 60 3 414 506 11 5 7 4 49 0 2 3 9 7 11 5 15 15 575 60 3 518 633 9 0 5 8 40 0 2 3 8 1 9 5 15 15 SX068 208 230 60 1 197 25...

Page 14: ...3 Air flow Settings 4 L2 Orange Factory low voltage wiring Legend Switch High pressure Switch Low pressure Relay coil Temperature Limit Switch Field wire lug Ground Relay Contacts N O N C Polarized c...

Page 15: ...pressure Polarized connector Condensate Overflow Factory low voltage wiring Factory line voltage wiring Field low voltage wiring Field line voltage wiring Optional block Internal junction Quick conne...

Page 16: ...M 9 x 7 1 6 720 690 685 680 670 660 650 640 620 600 L 590 570 560 550 545 540 530 520 510 500 H 790 780 775 770 765 760 740 720 690 670 610 SX019 M 9 x 7 1 6 720 690 685 680 670 660 650 640 620 600 L...

Page 17: ...ble 3 6 Check the temperature of both the supply and discharge water Refer to Start Up Performance Table 2 7 Check for an air temperature drop of 15 to 25 F across the air coil depending on the fan sp...

Page 18: ...tem to desired normal operating mode and set temperature to maintain desired comfort level 20 Instruct the owner operator of the proper operation of the thermostat and system maintenance NOTE If perfo...

Page 19: ...t mode Check thermostat and field control wiring If steps above show that the unit control board is not indicating proper results i e LED indication replace board If LEDs are indicating properly repla...

Page 20: ...without notice WaterFurnace is a registered trademark and Spectra is a trademark of WaterFurnace International Inc 1999 WaterFurnace International Inc 9000 Conservation Way Fort Wayne IN 46809 9794 P...

Reviews: